BLD20070886 Swedish 21605 76th.doc MEMORANDUM Date:September 15, 2007 Development Services Lead Marie Harrison To: From:Fire Marshal John J. Westfall 425.771.0213 th Subject:BLD20070886 Swedish Cancer Institute 21605 76 Ave W 2pp The following project has been evaluated under the Edmonds Community Development Code, 2006 International Fire Code. 1. Separate fire sprinkler modification permit required. 2. A0.1 Delete ref to ’97 UBC 3. A0.1 Update construction type “I FR SPRINKLERED.” 4. A0.1 and A0.2 Clarify floor level of work on PLOT and SITE plans. 5. A0.4 2003 2006 International Codes required 6. A0.4 Deconflict “Occupancy Group I2” with sheet A0.1 “General Project Info OCCUPANCY I.1” 7. A0.4 delete reference to CITY SEDRO WOOLEY. 8. A0.4 No existing fire barriers or partitions are called out on plan. 9. A0.5 INTERIM LIFE SAFETY: Provide min. 2A:10B:C portable fire extinguisher no greater than 75’ within project barrier. 10. A0.5 INTERIM LIFE SAFETY: Call out fire alarm system impairment procedures for period of construction. 11. A0.5 INTERIM LIFE SAFETY: Maintain unobscured fire sprinkler protection throughout project. 12. A15.0 Remove architectural specification for CITY SEATTLE throughout. 13. Call out medical gas systems affected by work. 14. E2.1 Add smoke detector in TREATMENT PLANNING Room 136 City of Edmonds Fire Marshal   15. E2.1 Acceptance test for project fire alarm system devices required for final project approval. Cc: Mr. Jon Decker, AIA, jdecker@deckerarchitects.com Mr. Dave S, GLY Construction, daves@gly.com Asst. Building Official Ann Bullis