BLD20070886 Swedish 21605 76th.doc
MEMORANDUM
Date:September 15, 2007
Development Services Lead Marie Harrison
To:
From:Fire Marshal John J. Westfall 425.771.0213
th
Subject:BLD20070886 Swedish Cancer Institute 21605 76 Ave W 2pp
The following project has been evaluated under the Edmonds Community Development
Code, 2006 International Fire Code.
1. Separate fire sprinkler modification permit required.
2. A0.1 Delete ref to ’97 UBC
3. A0.1 Update construction type “I FR SPRINKLERED.”
4. A0.1 and A0.2 Clarify floor level of work on PLOT and SITE plans.
5. A0.4 2003 2006 International Codes required
6. A0.4 Deconflict “Occupancy Group I2” with sheet A0.1 “General Project Info
OCCUPANCY I.1”
7. A0.4 delete reference to CITY SEDRO WOOLEY.
8. A0.4 No existing fire barriers or partitions are called out on plan.
9. A0.5 INTERIM LIFE SAFETY: Provide min. 2A:10B:C portable fire extinguisher
no greater than 75’ within project barrier.
10. A0.5 INTERIM LIFE SAFETY: Call out fire alarm system impairment procedures
for period of construction.
11. A0.5 INTERIM LIFE SAFETY: Maintain unobscured fire sprinkler protection
throughout project.
12. A15.0 Remove architectural specification for CITY SEATTLE throughout.
13. Call out medical gas systems affected by work.
14. E2.1 Add smoke detector in TREATMENT PLANNING Room 136
City of Edmonds Fire Marshal
15. E2.1 Acceptance test for project fire alarm system devices required for final
project approval.
Cc: Mr. Jon Decker, AIA, jdecker@deckerarchitects.com
Mr. Dave S, GLY Construction, daves@gly.com
Asst. Building Official Ann Bullis