BLD20070935 Edmonds LS 22319 76 Ave W.doc
MEMORANDUM
Date:September 15, 2007
Development Services Lead Marie Harrison
To:
From:Fire Marshal John J. Westfall 425.771.0213
th
Subject:BLD20060977 Edmonds Landscaping 22319 76 Ave W
The following project has been evaluated under the 2003 International Fire Code and
the Edmonds Community Development Code.
1) Provide building addresses for structures on site plan. Contact Development
Services for approved addresses.
2) Site plan shows both OFFICES existing. Which is COU?
3) Indicate occupancy types and area for each structure on site.
4) How is access made to EXIST. GRAVEL PARKING? Show access from East, as
applicable.
5) If not applicable, Fire Department access roads shall be provided for every building
extending to within 150 feet of all portions of the exterior walls of the first story of
the building as measured by an approved route around the exterior of the building.
From previous records, rear STORAGE BUILDING is likely in excess of this 150’
dimension and lane width is less than required 20’. Provide fire access or
alternative fire protection provision.
6) What are the materials, quantities, and equipment being stored in STORAGEs?
7) Indicate fire hydrant locations from north and south approach on site plan. Hydrants
are required to be spaced every 300’
8) Sheet A3 provide 2A:10B:C minimum rated portable fire extinguisher inside main
entry/exit.
Cc: Applicant Mr.Warren LaFon, WLA, warrenlafon@earthlink.net
Assistant Building Official Ann Bullis