BLD20071162-3 Sound & Oly View Apts.doc MEMORANDUM Date:December 2, 2007 To:Development Services Lead Marie Harrison From:John Westfall, Fire Marshal, 425-771-0213 rd Subject:BLD20071162 Sound View Apts 417 3 Av S BLD20071163 Olympic View Apts 303 Howell Wy The Fire Department provides the following comments and corrections in accordance with the 2006 International Fire Code and Edmonds Community Development Code: Both permits: 1. Add General Note: Replace apartment smoke alarms greater than ten years old (NFPA 72 11.8.1.4). Smoke alarms shall be hard-wired, interconnected, with battery backup. 2. Sheet A2.5 & A2.15 Call out interior sprinkler riser area. 3. Sheet A1.0 LIST required permits/submittals include: a. Fire Connection Permit Fire connection permit is required for the installation of the underground supply for your fire protection system. Underground design must be stamped by registered PE or a Level III (WA) fire sprinkler contractor AND the installer must also stamp the plans. The installer must be either Level III or Level “U” fire sprinkler contractor licensed by the State. Provide three copies of plans showing all valves, vault location, post indicating valve, fire department connection and piping to include size and material, hydraulic calculations, thrust blocking with calculations, pipe bury depth and any and all other materials used and their fire protection listings. RCW 18.160.070 / RCW 18.27.110 b. Fire Sprinkler System Permit c. Fire Alarm Permit d. Fire Protection Footprint (example below) 4. Provide approved automatic closing fire-door auto closing by the actuation of smoke detector and sprinkler water flow switch for following locations: i. Sheets A2.5 & A2.15 COMMUNITY ROOM - CORRIDOR ii. Sheets A2.5 & A2.15 LOBBY - OFFICE iii. Sheets A2.6 & A2.17 LAUNDRY iv. Sheet A2.7 BEAUTY SALON v. Sheets A2.8 & A2.18 LIBRARY vi. Sheets A2.6-A2.8 & A2.16-A2.18 CORRIDOR - ELEVATOR LOBBY City of Edmonds Office of Fire Marshal   5. Sheets A2.5-8 & A2.15-A2.18 General Note #4 Call out relocated exit signs and emergency lighting fixtures with battery backup & field test operation. 6. Sheet A3.1 & A3.2 Change note #21: Relocate cigarette receptacle no closer than 25’ from building openings. 7. Sheet A3.1& A3.2 Add note: Update keys for Fire Department lockbox. 8. Sheet A3.1 & A3.2 Add note: Post building address in a position visible from building. Building numbers shall be a minimum of 4 inches high with a minimum stroke width of ½ inch. These numbers shall be Arabic numerals and contrast with their installed background. 9. Regarding fire protection/sprinkler systems design: a. Fire connection standard details for COE backflow prevention may be found at http://www.ci.edmonds.wa.us/engr_toc_std_details.stm . Fire sprinkler may be integrated with existing fire standpipe system design and new sprinkler permit. b. It appears NFPA 13R system will meet the minimum standards for fire protection purposes. c. Balconies & decks will be sprinklered. d. Provide current inspection, test & maintenance reports for fire standpipe systems iaw NFPA 25-02. e. Verify seismic bracing for existing standpipe system. 10. Regarding fire alarm system design: a. Manual & automatic fire alarm system modifications are required for the purposes of egress path detection and corridor integrity, off-site sprinkler system monitoring, local alarm audible/visual notification and exterior audibility. b. Notification in public areas must meet accessibility requirements. 2 Attachment: Fire Protection Footprint Cc: Mr. Glenn Hydahl,Housing Authority-Snohomish County glenn@hasco.org Mr. Scott Schreffler Dykemman Architects, scotts@dykeman.net Engineering Program Technician Jeanne McConnell Assistant Building Official Ann Bullis 3