Loading...
BLD20071181 PCC 9803 Edmonds Wy.doc MEMORANDUM Date:December 16, 2007 To:Development Services Lead Marie Harrison From:John Westfall, Fire Marshal, 425-771-0213 Subject:BLD20071181 PCC Natural Markets 9803 Edmonds Way The Fire Department provides the following comments and corrections in accordance with the 2006 International Fire Code and Edmonds Community Development Code: 1. Sht A0.0 APPLICABLE CODES: a. EDMONDS MUNICIPAL COMMUNITY DEVELOPMENT CODE, TITLES 16 AND 17 … b. 2003 WASHINGTON STATE BUILDING CODE (CHAPTER 51-50 WAC) c. 2005 KING COUNTY RULES AND REGULATIONS, 05-06 (FOOD CODE) 2. Sht A0.0 GENERAL SCOPE OF WORK - BUILDING WORK – 14 Modifications such as sprinklering unprotected areas of building (Sht A1.3) or altering sprinkler locations and sprinkler piping will require separate sprinkler permit. Call out on cover sheet. 3. Provide current service reports for existing automatic fire sprinkler and fire alarm systems in accordance with NFPA 25 and backflow assembly test report. 4. Commercial cooking systems creating grease-laden vapors will require separate Type I hood mechanical permit and hood suppression system permit. Call out on cover sheet as applicable. 5. Provide shelves & furnishings plan. 6. Sheet A0.0 Callout required permits/submittals include: a. Fire Sprinkler System Permit See #2 b. Fire Safety & Evacuation Plan Callout Fire Safety & Evacuation Plan. Provide an egress plan showing primary and secondary exits and which show all locations, describes all functions and use of fire protection equipment and safety appliances accessible to tenant, including fire sprinkler system, fire alarm system, and portable fire extinguishers. Email westfall@ci.edmonds.wa.us for example. IFC Section 404 7. Sht A1.0 Callout designated exits and interior sprinkler riser room. City of Edmonds Office of Fire Marshal   8. Sht A1.0 Callout exit signs and emergency illumination throughout. Exit signs are required within 100’ along exit path. 9. NEW EXIT CORRIDOR shall remain clear for egress. Propose signage or other means of assurance. 10. Sheet A2.0 SOUTH ELEVATION Address numbers should be “9803”. Post building address on west elevation in a position plainly legible and visible at frontage on Edmonds Way. 6” height (as shown) are too small and require greater elevation. 11. Sheet A2.0 SOUTH ELEVATION Provide Fire Department lockbox. Coordinate with Fire Department for a “Lockbox Authorization Letter” and instructions to obtain and install lockbox outside the sprinkler rooms on your site. 425.775.7720 Cc: Mr. George Ostrow, VELOCIPEDE Architects george@velocipede.net Mr. Joe McLaughlin Woodman Construction, Inc, joe@woodmanconstruciton.com Engineering Program Technician Jeanne McConnell Assistant Building Official Ann Bullis 2