Loading...
BLD20110196 7929 LBW.doc MEMORANDUM Date:April 18, 2011 To: Ms Jennifer Patterson jpatterson@arcv.com From:Fire Marshal John J. Westfall 425.771.0213 Subject:BLD2011-0196 Panera Bread 7929 Lake Ballinger Way Fire Prevention Services provides comments in accordance with 2009 IFC and ECDC: 1. Sheet C4 provide private hydrant to current standard detail. See COE Dwg E7.1 http://www.ci.edmonds.wa.us/engr_toc_std_details.stm 2. Sheet C4 Callout locations for fire department connection (FDC) and fire sprinkler post-indicator valve. FDC shall be single four inch ¼-turn Storz-type fitting. 3. Sheet G-CS CODE CLASSIFICATION: “Fire suppression system per IFC 903.3.1.1”. 4. Sheet G-CS “Permits required: Fire connection, Fire sprinkler, Fire alarm.” 5. Sheet G-CS “Fire Dept lockbox required for installation. Contact Edmonds Fire Services of SCFD#1 for Knox application; 425.771.0213. 6. Sheet A3.1 & EQ2.1 Secure exterior umbrellas OU102 and OU78 to patio floor to prevent moving or provide exterior/sidewall sprinkler protection under patio canopies (IFC 903.3.3). 7. Sheet A2.1 & A3.1. Sprinkler riser area is contiguous with very active food service production area. Callout dedicated area using exterior entry closet, screens, or floor striping and signage where sprinkler riser valves, components and trim are kept undisturbed yet remain accessible for testing and maintenance. 8. Sheet EQ2.1 Provide minimum 2A:10B:C-rated portable fire extinguisher in vicinity of C6.5. 9. Reconcile north arrow of floor plans with Sheets A5.1& .2 building elevations. Cc: Building Official Leonard Yarberry City of Edmonds Office of Fire Marshal  