MEMORANDUM
Date:
September 07, 2011
To:
Jerry Zenczak, studio@zpaaia.com
From:
Fire Marshal John J. Westfall 425.771.0213
Subject:BLD2011-0621 Columbia Bank 9601 Edmonds Way: Corrected
Fire Prevention Services provides comments in accordance with 2009 IFC and ECDC:
1. Sheet C1 move PIV to location visible from Edmonds Way and away from
landscape shrubbery.
2. Sheet C4 provide current hydrant standard detail COE Dwg E7.1
http://www.ci.edmonds.wa.us/engr_toc_std_details.stm
Hydrant is located in Olympic View Water District.
3. Sheet A0.1 Callout required permits/submittals include:
a. Fire Connection
Callout Fire Connection Permit. Fire connection permit is required for the
installation of the underground supply for your fire protection system.
Underground design must be stamped by registered PE or a Level III (WA) fire
sprinkler contractor AND the installer must also stamp the plans. The installer
must be either Level III or Level “U” fire sprinkler contractor licensed by the
State. Provide three copies of plans showing all valves, vault location, post
indicating valve, fire department connection and piping to include size and
material, hydraulic calculations, thrust blocking with calculations, pipe bury
depth and any and all other materials used and their fire protection listings.
RCW 18.160.070 / RCW 18.27.110
b. Fire Sprinkler
Callout Fire Sprinkler System permit installed in accordance with IFC 903.3.1.1.
c. Fire Alarm
Callout Fire Alarm permit required for the purposes of off-site sprinkler system
monitoring, local alarm audible/visual notification and exterior audibility installed
in accordance with NFPA 72.
4. Add note “Fire Dept lockbox required for installation. Contact Edmonds Fire
Services of SCFD#1 for Knox application; 425.771.0213”. Install box at
Mechanical room entry.
5. Add note: “Post building address on south elevation in a position plainly legible
and visible from Edmonds Way. The numbers shall contrast with their
City of Edmonds Office of Fire Marshal
3/4
background and shall be a minimum of 6 inches high with a stroke width of
inch”. See South Elevation Sheet A2.1
6. At drive through, the horizontal roofline to curb narrows to less than 10’ wide.
Provide signage to indicate clear height underneath drive through canopy.