Loading...
BLD20110778.pdfOF ED -4f CITY OF EDMONDS 121 5TH AVENUE NORTH - EDMONDS, WA 98020 PHONE: (425) 771-0220 - FAX: (425) 771-0221 Expiration Date: 4/19/2012 Parcel No: 00434204300700 Permit #: BLD20 t Project Address:, DALEY ST 4 EDMOND' I_...:._.:.:....:._ __ _ w_� STEPHEN HARPER STEPHEN HARPER CHERMAK CONSTRUCTION 1026 DALEY ST 1026 DALEY ST 655 EDMONDS WAY EDMONDS, WA 98020 EDMONDS, WA 98020 EDMONDS, WA 98020 (425)775-3864 (425)775-3864 (425)776-1367 LICENSE #: CHERMCII I ONU EXP:8/7/2013 JOB DESCRIPTION REMOVE AND REPLACE EXISTING CONCRETE WALKWAY. PROVIDE NEW TRENCH DRAIN AT WALKWAY. INSTALL NEW FOOTING DRAIN AT WEST FOUNDATION WALL. REINFORCE EXISTING PRESSURE TREATED WOOD FRAMED WALL AT WEST FOUNDATION PER STRUCTURAL. VALUATION: $0.00 PERMIT TYPE: Residential PERMIT GROUP: 58 - Retaining Wall/Bulkhead GRADING: N CYDS: 0 TYPE OF CONSTRUCTION: RETAINING WALL ROCKERY: Y OCCUPANT GROUP: OCCUPANT LOAD: FENCE: N ( 0 X 0 FT.) CODE: Pt OTHER: N ------ OTHER DESC: ZONE: RS -6 IL L— I L. NUMBER OF STORIES: 0 1 VESTED DATE: NUMBER OF DWELLING UNITS: 0 LOT #: BASEMENT: 0 1 ST FLOOR: 0 2ND FLOOR: 0 BASEMENT: 0 1 ST FLOOR: 0 2ND FLOOR: 0 3RD FLOOR: 0 GARAGE: 0 DECK: 0 OTHER: 0 13RD FLOOR: 0 GARAGE: 0 DECK: 0 OTHER: 0 ONTSETBACK SIDE SETBACK REAR SETBACK REQUIRED:20• PROPOSED: 21 REQUIRED: 5 PROPOSED:5 RE UIRED:15 PROPOSED: 54 HEIGHT ALLOWED:O PROPOSED:O I REQUIRED: 5 PROPOSED: 5.4 SETBACK NOTES: I AGREE TO COMPLY WITH CITY AND STATE LAWS REGULATING CONSTRUCTION AND IN DOING THE WORK AUTHORIZED THEREBY, NO PERSON WILL BE EMPLOYED IN VIOLATION OF THE LABOR CODE OF THE STATE OF WASHINGTON RELATING TO WORKMEN'S COMPENSATION INSURANCE AND RCW 18:27, THIS AOA—)1v P�PLIj I N IS NOT A PERMIT UNTIL SIGNED BY THE BUILDING OFFICIAL OR HIS/HER D TY NND/AjL/L/FE��E�S CdA PAID % n7't— I t / _ M w ' //,,c '- z r. — --I. or-- ?0/,., —// lal/ /,' 1 �-lYf A � /1 ` 1 Print Date ATTENTION IT IS UNLAWFUL TO USE OR OCCUPY A BUILDING OR STRUCTURE UNTIL A FINAL INSPECTION HAS BEEN MADE AND APPROVAL OR A CERTIFICATE OF OCCUPANCY HAS BEEN GRANTED. UBC109/ IBC 110/ IRC I 10. = ONLINE = APPLICANT = ASSESSOR STATUS: ISSUED BLD20110778 • Final approval on a project or final occupancy approval must be granted by the Building Official prior to use or occupancy of the building or structure. Check the job card for all required City inspections including final project approval and final occupancy inspections. • Any request for alternate design, modification, variance or other administrative deviation (hereinafter "variance") from adopted codes, ordinances or policies must be specifically requested in writing and be called out and identified. Processing fees for such request shall be established by Council and shall be paid upon submittal and are non-refundable. • Approval of any plat or plan containing provisions which do not comply with city code and for which a variance has not been specifically identified, requested and considered by the appropriate city official in accordance with the appropriate provision of city code or state law does not approve any items not to code specification. • Sound/Noise originating from temporary construction sites as a result of construction activity are exempt from the noise limits of ECC Chapter 5.30 only during the hours of 7:00am to 6:00pm on weekdays and 10:00am and 6:00pm on Saturdays, excluding Sundays and Federal Holidays. At all other times the noise originating from construction sites/activities must comply with the noise limits of Chapter 5.30, unless a variance has been granted pursuant to ECC 5.30.120. • Applicant, on behalf of his or her spouse, heirs, assigns, and successors in interests, agrees to indemnify defend and hold harmless the City of Edmonds, Washington, its officials, employees, and agents from any and all claims for damage's of whatever nature, arising directly or indirectly from the issuance for this permit. Issuance of this permit shall not be deemed to modify, waive or reduce any requirements of any City ordinance nor limit in any way the City """"s ability to enforce any ordinance provision. THIS PERMIT AUTHORIZES ONLY THE WORK NOTED. THIS PERMIT COVERS WORK TO BE DONE ON PRIVATE PROPERTY ONLY. ANY CONSTRUCTION ON THE PUBLIC DOMAIN (CURBS, SIDEWALKS, DRIVEWAYS, MARQUEES, ETC.) WILL REQUIRE SEPARATE PERMISSION. PERMIT TIME LIMIT: SEE ECDC 19.00.005(A)(6) BUILDING (425) 771-0220 EXT. 1333 1 ENGINEERING (425) 771-0220 EXT. 1326 1 FIRE (425) 775-7720 1 PUBLIC WORKS 425) 771-0235 PRE-TREATMENT 425 672-5755 RECYCLING 425) 275-4801 When calling for an inspection please leave the following information: Permit Number, Job Site Address, Type of Inspection beine requested, Contact Name and Phone Number, Date Prefereed, and whether you prefer morning or afternoon. B -Foundation Wall B -Foundation Drainage • B -Framing • B -Building Final OV F°M Inspection Comments r BLD20110778 58 - Retaining Wall/Bulkhead Applied: 09/19/2011 Issued: 10/19/2011 Expires: 04/19/2012 �pc. t RNO Address: 1026 DALEY ST, EDMONDS INSPECTION DATE INSPECTOR ACTION 1110 - B -Foundation Wall 11/04/2011 LAWLER CMP Comment: 1112 - B -Foundation Drainage 11/04/2011 LAWLER CMP Comment: 1142 - B -Framing 11/01/2011 STEINIKE CMP Comment: 1158 - B -Building Final 11/17/2011 LAWLER CMP Comment: 11/18/2011 10:55:11 AM 121 5th Ave, Edmonds Washington - Phone: (425) 771-0220 Page 1 of 1 • o 0 i i N z z� �L0 to z w m LL i O LU ir LU QK � ® m Li u w r z o. C..Q Z s. W 3 Z W W CL U.1 o ylw in a:41 o yio, N < X—MitiJ Q } = N 0 t.Graa��J41D ! o f rn 90 v i ?. Iii a .%ix!�{13. Ivy !ox ' l0FMI�Y vi ^ V " . rANG �pF10 tpNG J o zz m t NF�!.�-�'G0(JGq=: Vim.• U a u z m o ui o o O� >j nl z ¢ F fI C7�~w� �u~ U iz >z . 1 z m o W 1 �� ZQ:03Z w~0w }� m A lL WZQ W WOW x�� ..<U4. 5z -j <N. WZIX WO�� V �s OZ~U _l ?� W of }� z< z wa O I' I WE j0 N O ���o ug Z W U) z E w 0)Z rn C7 �• �i to a0 w -K p a O N 2 Z w o - U)w Nin > Z '0 i p z < K �> ou �opc 2i _ LL W W .0- 3 o w �' '! WOE 0 O. 11 } E-owZd �. wm IZZF 5 8Q +.. CD w osm�@o • z 0 .ozz§ oz-z u� a HM. a'Yeat01N1�MiCRSB�N'.HPPOY�A1110M4etiAoep �tMWAM.WN.A 0�00'CBLBB��WP�tl��11 �CK8818 Nd R:t llR il��6 Building Sciences Inc. I i TO Steve Harper 1026 Daley St. i Edmonds WA 98020 I i EMAIL I sharper43@comcast.net REGARDING Below Grade Leak Investigation Dear Mr. Harper, F6t,0 2-61(-07?8 509 FAIR'ViEW AVE N 4100 ; EL 206 324 2272 5EA@RDHBE.COM SEATi ILEVJA98109-5507 FAX 206 324 6339 WW'W.RDHBE.COM B5203.00 — Harper Residence Below Grade Leak Investigation August 3, 2011 L' S� 1 2011 BUGTM OFDEDMONDS EPARTMENT Follow are our observations and recommendations regarding the below grade leakage issues into the utility space at your house. BACKGROUND Tony Thompson of RDH visited the Harper Residence located at 1026 Daley St Edmonds Washington on July 07, 2011 to review existing conditions subject to periods of water infiltration, to conduct water testing, and to identify the causes and pathways leading water intrusion and silt accumulation problems in the below grade utility space. The utility room where the homeowner has observed water infiltration is situated partially below grade on the northwest corner of the house. We understand this area was added approximately fifteen years ago to provide additional mechanical equipment and storage space. The wood -framed structure of the house bears on concrete foundation walls and spread footings approximately 2 feet tall, enclosing a 2 - foot crawl space under the home. During the expansion of the utility room, approximately 5 feet of soil was excavated from the area and a slab on grade floor placed at the bottom of the excavation. Two by six pressure -treated wood -framed and sheathed walls are constructed 6 inches away from the dirt shear cut walls. We understand that in extreme inclement weather events moderate water infiltration has been observed for years. A small sump pump exists in the northwest corner of the utility room. We further understand that within the last year water infiltration has increased and soil fines have been accumulating on the utility room floor. OBSERVATIONS 1. EXTERIOR CONCRETE WALK WEST OF THE HOME ADJACENT TO THE UTILITY ROOM: . A small concrete curb and strip is poured directly against the foundation wall in the area adjacent to the utility room.(Photo SVR 01.00.02) ................................................................ SAB5203 - Harper Residence\B5203.00 - Below Grade Leak Investigation\Field Review\B5203 00 201108 04 TTT Below Grade Leak PAGE 1 OF 4 Investigation.doc RDH 1 Building Sciences Inc. www.rdhbe.com -4 Sidewalk sections are poured adjacent to the curb and strip. The neighbor's walk and soil grades adjacent to the areas are slightly higher, contributing to increased surface water runoff directed to the sidewalk area. (Photo SVR 01.00.04) The area is very pervious. Small,amounts of water in localized areas infiltrated into the west wall of the utility room within 10 minutes of initiating water penetration resistance testing. (Photo SVR 01.00.04) + (Photo SVR 01.00.05) � The remainder of the walkway leading to the rear of the home is crushed gravel. 2. N.W. CORNER OF THE HOME STAIRS/DRIVEWAY/SIDING INTERFACE: The interface between the stairs, driveway and siding at the northwest corner of the house lacks flashing and weather resistant barrier. (Photo SVR 01.01.02) Foundation modification at this location is susceptible to water infiltration. The boards used to form the added concrete .were abandoned in place and are exposed to the elements. (Photo SVR 01.01.02) --> Splash block is shimmed up with soil. Water cascading down the stairs migrates towards this area rather than away. (Photo SVR01.01.01) 3. ENTRY STOOP AND FRONT WALK AREA: -� During our. visual inspection of the utility room we observed evidence of water infiltration and soil erosion in the northeast corner of the room. (Photo SVR 01.2.00.02) -� We performed a review of the exterior components adjacent to this area and observed the following: > The concrete stoop is poured over a stone masonry wall. The stone wall interfaces with the wood -framed and siding portion of the home. Voids and cracks exist where the differing materials interface. We water -tested isolated suspect areas and observed water infiltrating the northeast corner of the utility room within 1 minute of initiating testing. (Photo SVR 01.200.01) + (Photo SVR 01.200.03) > We observed similar conditions where the front walkway interfaces with the rock wall and stoop. (Photo SVR 01.200.01) + (Photo SVR 01.200.04) 4. OTHER AT -GRADE OBSERVATIONS: The back of the home faces south; a French drain system has been installed adjacent to the home to divert water away from the foundation and crawl space areas. The east elevation of the home has a gravel walkway with a pervious keystone retention wall. Rain gutters/downspouts transport water away from the home via underground tubing day lighted away from the home. .................................................. S:\B5203 - Harper Residence\B5203.00. Below Grade Leak Investigation\Field Review\B5203 00 201108 04 TTT Below Grade Leak PAGE 2 OF 4 Investigation.doc RDH I Building Sciences Inc. wwwrdhbe.com RECOMMENDATIONS FOR NEXT STEPS AND/OR REPAIR 1. EXTERIOR CONCRETE WALK WEST OF THE HOME ADJACENT TO THE UTILITY ROOM: Provide provisions for surface water to be gathered and carried away from the west side of the home adjacent to the utility room. Ideally the concrete walkway and stairs would be removed and replaced sloping away from the home and incorporating a trench drain and drainage pipe to direct surface water away from the home. The drainage pipe could be day lighted at the base and to the west of the stairs. This will also facilitate relocating and incorporating the roof gutter downspout, which currently terminates at the northwest corner of the home, into the new drainage system. Next to the walkway we recommend installing prefabricated composite sheet drainage media against the foundation and footing to collect and channel water into a conventional footing drain, a perforated pipe surrounded by gravel and geotextile fabric. The discharge pipe would be joined with the discharge pipe of the surface water drainage system. 2. NORTHWEST CORNER OF THE HOME STAIRS/DRIVEWAY/SIDING INTERFACE: We recommend removing approximately 3 feet of siding from each side of lower corner of this area to a height of approximately 3 feet. This will facilitate incorporating a weather -resistant barrier to protect the corner of the structure prior to replacing the concrete stairs. 3 The Previous recommendations are intended to address the primary cause of water intrusion into the utility room west wall: soil and water ingress below the wood sill plate. —� The existing wood -framed wall inhibits visual observation of the shear cut soil wall that supports the footing and foundation. Based on our limited observations, we recommend cutting several observation holes in the sheathing of the west wall to facilitate further investigation of this area. The holes should be cut near the ends of the wall and near the center, 5 feet above the finished floor; this is the height of the spread footing and foundation wall interface. > If it is deemed necessary due to erosion of soils to provide supplementary soil retention and structural support, it may be a viable and cost-saving option to use the existing framed wall as a concrete form and pour/pump a concrete wall while pouring the new walkway and stairs. We will discuss all available options after we have the opportunity to further observe the area. It would be prudent to budget for a drainage mat, drainage system, and lift pump similar to the system proposed by Bodine construction, including the cost of a shotcrete/gunite wall to structurally support the footing and foundation in that area if deemed necessary after we have opportunity to further observe the area ................................. :........................................................... .... 5:\B5203 - Harper Residence\B5203.00 - Below Grade Leak Investigation\Feld Review\B5203 00 201108 04 TTT Below Grade Leak PAGE 3 OF 4 Investigation.doc RDH I Building Sciences Inc. www.rdhbe.com 3. ENTRY STOOP AND FRONT WALK AREA: y The concrete stoop is poured over a stone masonry wall. The horizontal cold joint/crack between the concrete stoop and the stone wall could be addressed with some minor masonry repairs and installing a flashing that attaches to the vertical face of the stoop, extending and slightly sloping out over the uneven edge of the rock wall down aproxomitly 8 inches to shield this area from exposure to water. The stone wall interfaces with the wood frame and siding portion of the home. We recommend removing the siding in this area to facilitate incorporating a weather - resistant barrier and/or flashing at the vertical interface, contiguous with the vertical flashing described above. RDH observed similar conditions where the front walkway interfaces with the rock wall and stoop. Concrete cracks where the walkway interfaces with the stoop and rock wall can be routed out and sealed with a sanded caulk joint. A professional sealant installer can make these repairs visually acceptable and minimize water infiltration. The area where the front walk, front stoop, landscaping strip, and rock wall interface shows signs of moderate soil erosion. We recommend addressing this area concurrently with the soil and compaction work to be performed along the walkway to the north of the home. We look forward to your review and comments on the above items. We should meet to review these items, perhaps along with a contractor of your choice, to review these recommendations and discuss next steps. We are prepared to assist you with preparation of drawings as needed in order to provide a contractor the necessary direction and information to properly execute the intended repairs. Yours truly, RDH Building Sciences Inc. Anthony Thompson Senior Building Technologist tthompson@rdhbe.com encl. .........................................................................I........................ cc Michael Aoki -Kramer, RDH BuildingSciences Inc. EMAIL maokikramer@rdhbe.com .................................................. ...... SAB5203 Harper Residence\B5203.00 -Below Grade Leak Investigation\Field Review\B5203 00 201108 04 TTT Below Grade Leak PAGE 4 OF 4 Investigation.doc B5203.00 — Harper Residence Below Grade Leak Investigation SVR 01 Photos S:\B5203 - Harper Residence\135203.00 - Below Grade Leak Investigation\Field Review B5203.00 — Harper Residence Below Grade Leak Investigation SVR 01 Photos S:\B5203 - Harper Residence\B5203.00 - Below Grade Leak Investigation\Field Review ri k :q v eau r .t, y� d� nor. x .�` '� � r �' �� y � t i 4• � 1;��: i'` Fi ir)`,t, .td7u' � e •'� r ,;',r�yt�lr 4f�� r.,. � •,� Sy �t#�['i� t 1 ti`s ,. + { ti *g 1,, �fl. ,�. 17 ell 'f.° vr*.Ttx- .'r'.f� �\ t.��f�"t;`a) b:••T .:�y„ 5 B5203.00 — Harper Residence Below Grade Leak Investigation SVR 01 Photos SVR 01.00.05 West walkway isolated water test — interior west wall observation after ten minutes T , . �p Ti. •dA � � k y%• a � .. lk-j a S:\B5203 - Harper Reside nce\B5203.00 - Below Grade Leak Investigation\Field Review B5203.00 — Harper Residence Below Grade Leak Investigation SVR 01 Photos S:\B5203 - Harper Residence\B5203.00 - Below Grade Leak Investigation\Field Review B5203.00 — Harper Residence Below Grade Leak Investigation SVR 01 Photos Exterior foundation crack SVR 01.00.07 Footing undermined from soil erosion S:\B5203 - Harper Residence\B5203.00 - Below Grade Leak Investigation\Field Review Interior } Footing / foundation -1 crack adjacent to the exterior crack f , concealed behind the wood wall south -`. west corner of the utility room f . I y.; i Rr x �d y ,M SVR 01.00.07 Footing undermined from soil erosion S:\B5203 - Harper Residence\B5203.00 - Below Grade Leak Investigation\Field Review B5203.00 — Harper Residence Below Grade Leak Investigation SVR 01 Photos SVR 01.00.08 Soil erosion concealed behind the wood framed wall south west corner of the utility room Soil fines infiltrating under the wood framed w south west corner of the utility room S:\B5203 - Harper Residence\B5203.00 - Below Grade Leak Investigation\Field Review _ ` t SVR 01.00.08 Soil erosion concealed behind the wood framed wall south west corner of the utility room Soil fines infiltrating under the wood framed w south west corner of the utility room S:\B5203 - Harper Residence\B5203.00 - Below Grade Leak Investigation\Field Review , } t ' r � 4 �u4, Rt r e , t4 k � ✓M- t B5203.00 — Harper Residence Below Grade Leak Investigation SVR 01 Photos SVR 01.01.02 NW Corner `'.r... Y � walkway interface with framed structure needs "F waterproofing detail r« My xe, �'....-'� tow. / f Y } 1 1 d ✓ S:\B5203 - Harper Reside nce\B5203.00 - Below Grade Leak Investigation\Field Review B5203.00 — Harper Residence Below Grade Leak'Investigation SVR 01 Photos S:\B5203 - Harper Residence\B5203.00 - Below Grade Leak Investigation\Field Review S:\B5203 - Harper Reside nce\B5203.00 - Below Grade Leak Investigation\Field Review IM, z X""4 Wj Il 201110716i. B5203.00 — Harper Residence Below Grade Leak Investigation SVR 01 Photos SVR 01.00.10 Example of a prefabricated composite sheet drain installation rr S; \B5203 - Harper Reside nce\B5203.00 - Below Grade Leak Investigation\Field Review