DATE: December 6, 2011
TO: Scott Shanks
scott@fwdsinc.com
FROM: Jeanie McConnell, Engineering Program Manager
RE: Application #: bld20110816
Tenant Improvement
Project: Premier Orthopedic Group
nd
Project Address: 21401 72 Ave W
During review of the above noted application, it was found that the following information,
corrections, or clarifications are needed. Please submit three (3) sets of revised plans/documents
with a written response to each of the items below to Marie Harrison.
City of Edmonds handouts, standard details and development code can be referenced on the City
website.
NOTE: Shell & Core, Civils were reviewed under separate permit - #bld20110815.
Review 1 November 16, 2011
Review 2 December 6, 2011
A0.3 REFERENCE SITE PLAN
ok
1.
ok
2.
P01 LEGEND, SCHEDULES & GENERAL NOTES
ok
1.
2.12/6/2011 Thank you for adding the vent piping to the plans. You are correct that the
backwater valve is not required, however, in this location installation would be
appropriate and beneficial to the owner. Please confirm that the owner does not desire a
backwater valve.
11/16/11 comment - Detail 1.1 shows a 2 vent on the 4 waste outlet pipe. In lieu of the vent
installation of a backwater valve seems appropriate. This would prevent any sewer backup from
entering the parking garage through this structure.
bld20110816-Premier_Ortho-TI-E2.doc Page 1 of 2
P02 FOUNDATION PLAN WASTE AND VENT
ok
1.
ok
2.
ok
3.
12/6/2011 If a backwater valve is installed per comment 2 above, please show on the
4.
plans.
11/16/11 comment - Please show location of backwater valve on the outlet side of the oil/water
separator should you choose to install one.
12/6/2011 Please show all floor drain locations. Will they be D5 drains? If so, please
5.
indicate as such on the plans.
11/16/11 comment - The oil/water separator is the only drainage basin that has been shown on
this plan sheet. There are other locations throughout the garage where it appears as though catch
basins should be/could be installed please clarify and add basins where necessary.
P03 LEVEL 1 FLOOR PLAN WASTE AND VENT
1.ok
12/6/2011 For clarification a note has been added to the plan.
2.
11/16/11 comment - The oil/water separator is shown on this plan sheet, but it is not at the level
of the waste lines that are shown. Please grey out/dash line type.
P04 LEVEL 2 FLOOR PLAN WASTE AND VENT
ok
1.
Please contact me at 425-771-0220 or by e-mail at mcconnell@ci.edmonds.wa.us if you have
specific questions regarding these plan corrections.