Engineering Plan Review Comments
Permit Application :Date:
# BLD20120175 July 1, 2012
Project Name/Address:
Echelbarger – 209 Elm St
Contact Person/Address, Fax or E-mail:
Echelbarger
Reviewer: JENNIFER LAMBERT Division:
ENGINEERING
During review of the subject submittal, it was found that the following information, corrections, or
clarifications would need to be addressed. All Handouts referred to in these comments can be accessed at
our website: www.ci.edmonds.wa.us under City Government / Development Services Department /
Engineering Division then scroll down to Handouts:
st
1 Review – May 1, 2012
nd
2 Review – July 1, 2012
GRADING AND TESC PLAN
1)OK
2)OK
DRAINAGE AND UTILITY PLAN
SEWER
1)OK
2)OK
3)OK
4)OK
Additional Comments
5)7/1/12 - Please show invert elevations at the cleanouts so that coverage, clearance and depth of
pipe can be verified.
WATER
DATE E-MAILED 7/2/2012 PAGE(1)
City of Edmonds BLD20110563
TH
121 5 AVENUE NORTH EDMONDS, WA 98020 • (425) 771-0220 FAX(425) 771-0221
Website: www.ci.edmonds.wa.us
PUBLIC WORK DEPARTMENT
Planning • Building • Engineering
Engineering Plan Review Comments
1)OK
2)7/1/12 – Comment was not addressed (show both proposed and existing water mains).
5/1/12 Comment: Please show the proposed water main (as will be constructed with the City Capital
Project) along the entire frontage of the subject property.
3)7/1/12 – Comment was addressed; however, the following corrections need to be made.
a.Show the distance from the the centerport of the fire hydrant to back of curb to verify that
proper clearance can be made.
b.Please show the proposed fire hydrant to be relocated directly east of the existing fire
hydrant.
c.Please show and revise note that there is a 3’ clearance from face of port and back of fire
hydrant (scale does not match note).
5/1/12 Comment: Please show the proposed location of the fire hydrant to be at the back of sidewalk
(do not remove the existing fire hydrant).
4)OK
Additional Comments
5)7/1/12 – Please show the water service line from the house to the meter.
6)7/1/12 – Please note what pipe material and size line will be used as well as noting that tracer wire
will added to the water service line.
STORM
1)OK
2)OK
3)7/1/12 – Comment was not addressed.
5/1/12 Comment: Please provide rim and invert elevations for the connections to the catch basins for all
stormwater systems.
4)OK
DATE E-MAILED 7/2/2012 PAGE(2)
City of Edmonds BLD20110563
TH
121 5 AVENUE NORTH EDMONDS, WA 98020 • (425) 771-0220 FAX(425) 771-0221
Website: www.ci.edmonds.wa.us
PUBLIC WORK DEPARTMENT
Planning • Building • Engineering
Engineering Plan Review Comments
5)7/1/12 – Comment was addressed; however, the low spot of the footings for the rockery do not
match the location of the drainage point of the footings. Please verify that the footing drains will
drain properly.
5/1/12 Comment - Please show the drainange from the rockery connected to the city catch basin or to
the pipe for the overflow from the infiltrations sytems.
6)7/1/12 – Comment was addressed; however, the low spot of the footings for the retaining wall do
not match the location of the drainage point of the footings. Please verify that the footing drains
will drain properly.
5/1/12 Comment - Please show the drainage from the retaining wall connected to the city catch basin or
to the pipe for the overflow from the infiltrations sytems.
7)OK
UTILITIES
Additional Comments
1)Please add a note to the plans that all new utilities must go underground.
nd
2)Please show all dry utilities (gas, power, phone, etc) on Elm & 2 St.
3)Please provide cross sections through the sidewalk, retaining wall and rockery for each utility that
crosses underneath.
a.If 2’ separation between the footings of the retaining wall / rockery and pipes can not be
achieved, please show appropriate pipe material, such as ductile iron.
RETAINING WALL
1)OK
2)7/1/12 – Comment was addressed; however, the following corrections need to be made.
a.Show the distance from the the centerport of the fire hydrant to back of curb to verify that
proper clearance can be made.
b.Please show the proposed fire hydrant to be relocated directly east of the existing fire
hydrant.
DATE E-MAILED 7/2/2012 PAGE(3)
City of Edmonds BLD20110563
TH
121 5 AVENUE NORTH EDMONDS, WA 98020 • (425) 771-0220 FAX(425) 771-0221
Website: www.ci.edmonds.wa.us
PUBLIC WORK DEPARTMENT
Planning • Building • Engineering
Engineering Plan Review Comments
c.Please show and revise note that there is a 3’ clearance from face of port and back of fire
hydrant (scale does not match note).
5/1/12 Comment - Please show the retaining wall a minimum of 4.5’ from back of sidewalk where the
fire hydrant will be located (3’ clearance required around fire hydrant).
3)OK
Additional Comments
4)7/1/12 - The calculations for the retaining wall need to be based on actual conditions (i.e. slope
behind wall, slope at toe of rockery, and height of rockery). Please revise plans or calculations to
be consistent.
5)7/1/12 - Please modify the keystone detail to be consistent with the designed calculations.
ROCKERY
4)OK
5)OK
Frontage Improvements
6)OK
7)OK
8)OK
Additional Comments
9)7/1/12 - Please show the 2’ asphalt cut where new curb/gutter will be placed.
Please resubmit 3 copies of the revised plans and associated documents with a written response to each
item to a Permit Coordinator. Please contact me at 425-771-0220 ext 1321 or by e-mail at
jennifer.lambert@ci.edmonds.wa.us if you have specific questions regarding these plan corrections.
DATE E-MAILED 7/2/2012 PAGE(4)