Plan Review Corrections
nd
Plan Check : Date:
# BLD20120473 – 2 Comments August 22, 2012
Project Name/Address:
Echelbarger New Single Family Residence 9010 217th St SW
Contact Person/Address/Fax:
Tod todd@echelbarger.com
Reviewer: JoAnne ZulaufDivision:Engineering
During review of the subject submittal, it was found that the following information, corrections, or
clarifications would need to be addressed. All Handouts and Standard Details referred to in these
comments can be accessed at our website: www.edmondswa.gov :
Please Note: Building Handouts do not include updated Engineering Division Requirements. Refer to
Engineering Handouts for all Engineering Requirements.
General Plan:
1. 8/22/12 Done.
Site Plan:
1. 8/22/12 Partially complete. Please label sewer and water service line (ss, wsl). The plot or site
plan needs to show the location of all the utilities (ie water line, sewer line, etc.) from the
property line to the house and the stormwater system connection to house but does not need
to include the details (length, size, etc.).
2. 8/22/12 Done.
3. 8/22/12 Done.
4. 8/22/12 Done.
5. 8/22/12 Done.
6. 8/22/12 Done.
7. 8/22/12 Done.
8. 8/22/12 Done. Further regulations within the Sidewalk Policy (an extension of the code
requirements) render this property exempt from the Sidewalk Construction requirement. No
Waiver Needed.
9. 8/22/12 Partially complete. Show the 2’ sawcut in front of the existing driveway to be removed.
Also note that curb/gutter will be installed in place of the curb cut. Show 2’ sawcut area along
the property frontage.
Storm/Utility
DATE FAXED/E-MAILED 7/2/2017 PAGE ___ OF __
12
8/22/12 Done.
Erosion/Grading
1. 8/22/12 Done.
2. 8/22/12 Done.
3. 8/22/12 Done.
4. 8/22/12 Done.
5. 8/22/12 Please revise grading calculations or provide breakdown of grading quantities.
Based on a 4ft cut (existing elevation 412, bottom of footings 408.25) for the footings of the
residence (not including the garage area since slab on grade), it appears that the cut
amount is much larger than 25 cyds. Add bottom of footing (bof) elevation or slab elevation
for structure for verification of grading quantities.
***The revisions may be redlined on the existing plans if preferred.***
Please resubmit 3 copies of the revised plans/documents to a Development Services Coordinator. Please
contact me at 425-771-0220 if you have specific questions regarding these plan corrections.