BLD2012-0925 Walgreens.doc MEMORANDUM Date:November 27, 2012 Mr Eric Evensen erice@baysingerpartners.com To: Mr Craig Harris craigh@aaleng.com Mr James Tormey james.tormey@mfia-eng.com From:Fire Marshal John J. Westfall 425.771.0213 Subject:BLD2012-0925 Walgreens Drugstore: 9797 Edmonds Way The following pre-application has been evaluated under the 2009 International and Edmonds Community Development Codes. CIVILS 1. Sheet C-100 Show turn radius calculation at NE corner of lot, minimum 20’ inner and 40’ outer radii. 2. Sheet C-100 & A-100 Fire access roads shall be striped on both boundaries with 4” yellow perimeter or curb striping and identified with words “FIRE LANE – NO PARKING”. Letters shall be 12” high with 2” stroke spaced 50 lineal feet on alternating insides of lane. 3. Sheet C-111 or F-510 Callout fire protection system double check detector assembly (DCDA) location, or, If interior installed: Callout Fire Connection Permit (sheet G-010). Fire connection permit is required for the installation of the underground supply for your fire protection system. Underground design must be stamped by registered PE or a Level III (WA) fire sprinkler contractor AND the installer must also stamp the plans. The installer must be either Level III or Level “U” fire sprinkler contractor licensed by the State. Provide three copies of plans showing all valves, vault location, post indicating valve, fire department connection and piping to include size and material, hydraulic calculations, thrust blocking with calculations, pipe bury depth and any and all other materials used and their fire protection listings. RCW 18.160.070 / RCW 18.27.110 4. Sheet C-111 Provide post protection for FDC along access drive at SE corner. City of Edmonds Fire Marshal   SITE/GENERAL: 5. Sheet G-020 & E-121 Add illuminated exit signs in retail area clearly indicating the direction towards nearest exit at following locations: (D.9-1.8), (A.9-1.8). 6. Sheet G-020 & E-121 Mounting height for retail exit signs should provide for greatest visibility over floor shelving, under hanging fixtures, and in-between signage. 7. Sheet A-111 or F-510 Provide minimum rated 2A:10B:C fire extinguishers for light hazard, conspicuously located no greater than 75’ travel distance throughout. 8. Sheet A-111 & F-510 Provide floor paint with 4” wide yellow striping with “KEEP CLEAR” for \[21 10 01\] fire riser area. 9. Sheet A-111 & F-510 & E-161 Collocate FACP at fire riser area \[21 10 01\] . 10. F-510 & E-161 Fire alarm system is provided for fire sprinkler monitoring and notification throughout. 11. Sheet A-210 & A-730 Callout building address numbers “9797” minimum 6” with ¾” stroke on contrasting background at south-southwest exterior elevation and visible from Edmonds Way. 12. Sheet A-210 & F-510 Callout FIRE PROTECTION CONTROLS or similar approved wording for sign at west access door to sprinkler riser area. 13. Sheet A-610 Door J and associated hardware at location (C1) must be openable from exterior with key from Snohomish Fire District 1 Knoxbox, mounted adjacent to door. 14. Sheet A-610 & F-510 Add note “Fire Dept lockbox required for installation. Contact Edmonds Fire Services of SCFD#1 for Knox application; 425.775.7720”. Install box at suppression room entry. 15. Sheet F-510 Identify exterior canopies 4’ wide and greater with combustible construction that will require sprinkler protection, or callout noncombustible canopies and overhangs. 16. Sheet F-510 Correct telephone for AHJ is 425 771-0213 17. Sheet M-520 I calculate approx 125 lbs of type A1 refrigerant R-404A. This is under the IFC-regulated control requirement of 220 lbs. Is this the correct amount, intent, and only refrigerant utilized on-site? Fire Protection Footprint for DRUGSTORE Cc: Building Official Yarberry Engineering Manager McConnell