Engineering Plan Review Comments
PermitApplication:Date:
#BLD20130211 April 24, 2013
th
Project Name/Address:
Dent –16330–75Ave W
Contact Person/Address, Fax or E-mail:
Paul Dent –paul@griffinmaclean.com
Reviewer: JENNIFERLAMBERTDivision:
ENGINEERING
During review of the subject submittal, it was found that the following information, corrections, or
clarifications would need to be addressed. All Handouts referred to in these comments can be accessed at
our website: www.edmondswa.govunder City Government / Development Services Department /
Engineering Division then scroll down to Handouts:
st
1Review –4/24/13
nd
2Review –7/11/13
1)OK
2)OK
3)OK
4)OK
5)OK
6)OK
7)OK
8)OK
DATE E-MAILED7/11/2013PAGE (1)
City of EdmondsBLD20130211
TH
121 5AVENUE NORTHEDMONDS, WA 98020 • (425) 771-0220FAX (425) 771-0221
Website: www.edmondswa.gov
PUBLIC WORK DEPARTMENT
Planning • Building • Engineering
Engineering Plan Review Comments
9)7/11/13 –Comment was addressed; however, there are a few additional questions.
a.The detail provided from the King County Manual states that ductile iron must be used
since the slope exceeds 30%. Please showthe appropriate material as stated by the King
County Manual if you are to use the anchor detail they provide. (Table 4.2.1.A).
b.Please note your engineer could potentially recommend another anchoring system that will
allow for use of HDPE.
c.Please note that the King County Manual also states above ground installation is
recommended on slopes greater than 40%. The proposed storm line has a slope of 40%,
please have your licensed GeotechnicalEngineer address whether the pipe should be above
ground.
d.Please provide approval of the pipe material, pipe anchors, and proposed installation
(above ground or below) from the licensed GeotechnicalEngineer and BNSF.
4/24/13 Comment: Please note that if the storm line is 20% or greater the line will need to be anchored.
Please show the locations where the storm line will be anchored.
10)OK
11)7/11/13 –Comment was addressed; however, no structures can be located within the easement or
no private utility systems may run parallel within the City Sewer Easement. Please relocate the
storm line and structure such thatit is located outside ofthe easement. It is permissible to have
the private storm line cross through the easement.
4/24/13 Comment:Please show the limits of the City Sewer (8306230279-10’) and Access Easement
(8301200190 –10’)and note the recording number on the plans (Site Plan and Civil Plans).
12)OK
13)OK
14)OK
15)OK
Please resubmit 3 copies of the revised SitePlansand associated documents with a written response to
each item to the Permit Coordinator. Please contact me at 425-771-0220ext 1321or bye-mail at
jennifer.lambert@edmondswa.govif you have specific questions regarding these plan corrections.
DATE E-MAILED7/11/2013PAGE (1)