BLD2013-0603 Seavue Condominiums 1130 5th Ave S.htm From: John Westfall Sent: Monday, September 02, 2013 1:34 PM To: Bjorback, Leif Subject: BLD2013-0603 Seavue Condominiums 1130 5th Ave S Leif: The proposal/requirements below for the work being proposed will provide an improvement to the existing building and system. I recommend that we approve the work under the conditions that improve the building fire alarm system by level of coverage below. IFC 104.8 Modifications and IFC 104.9 Alternative materials and methods. The level of coverage required for this fire alarm system exceeds that required by IFC 4603.6.6 for existing R-2 buildings. The level of coverage exceeds that required upon building design and acceptance. The level of coverage will substantially improve the performance and purpose over the existing fire alarm, providing location information to responding fire department resources. The level of coverage will instill confidence in the new system to provide early warning of fire incidents to the occupants. LEVEL OF COVERAGE FOR FIRE ALARM: Provide automatic and manual fire alarm system throughout the building. Install new addressable FACP and annunciators at East and North main entries. Provide new smoke detectors in corridors, common living areas, at FACP, and for door holders installed in accordance with IBC Chapter 7 and NFPA 80. Provide accessible notification in common areas. Provide and/or evaluate existing heat detection in garages and storage units. Addressing of devices is essential to improved coverage. Establish and maintain off-site monitoring for fire alarm system. John J. Westfall Fire Marshal Fire Prevention Services 425-771-0213 Desk 425-775-7721 Fax 425-231-3644 Mobile This image cannot currently be displayed.