Loading...
BLD2013-0681 21605 76 Ave W.doc MEMORANDUM Date:July 12, 2013 To:Swedish Medical Group Scott Rice From:John Westfall, Fire Marshal 425.771.0213 th Subject:BLD 2013-0681 Swedish COU 21605 76 Ave W The Fire Department provides the following comments and corrections in accordance with the 2009 International Fire Code and Edmonds Community Development Code Title 19: 1. 2012 Building/Fire Codes adopted July 1, 2013. 2. G1.0 Provide plan for all floors when entire building is being evaluated for change of use. 3. G1.0 FIRE SPRINKLER PERMIT REQUIRED st For fire sprinkler submittal, show sprinklers and piping coverage for entire (1) floor/tenant space including existing coverage, where provided in CT and ACCELERATOR areas. 4. G1.0 FIRE ALARM PERMIT REQUIRED 5. G1.0 Add text: GENERAL INFORMATION 4. FIRE PROTECTION SYSTEM REQUIREMENTS (CH.9) 6. G1.0 GENERAL INFORMATION 4. FIRE PROTECTION SYSTEM REQUIREMENTS (CH.9): If ELEVATOR LOBBY is true atrium per IBC 404, does 404.3 prescription for (SPRINKLERED _____) apply, or is exception taken? 7. G1.0 “FIELD CHECK FD ACCESS KEY” (MECHANICAL ROOM exterior door) 8. G1.1 If ELEVATOR LOBBY is true atrium per IBC 404, include this consideration, separations and protections in COU SUMMARY. 9. A2.1 DOOR 108 (lobby) referenced on DOOR SKED Sheet A2.4 Table 11. REMARKS NOTE 2 references a FS “water wall”. Is this an atrium? 10. A3.1 Privacy curtains should be provided not to obstruct fire sprinkler spray patterns. City of Edmonds Office of Fire Marshal  