Engineering Plan Review Comments
PermitApplication:Date:
#BLD20131081 November 15, 2013
Project Name/Address:
S & D –936Walnut St
Contact Person/Address, Fax or E-mail:
Wayne Scharbach –scharco@msn.com
Reviewer: JENNIFERLAMBERTDivision:
ENGINEERING
During review of the subject submittal, it was found that the following information, corrections, or
clarifications would need to be addressed. All Handouts referred to in these comments can be accessed at
our website: www.ci.edmonds.wa.usunder City Government / Development Services Department /
Engineering Division then scroll down to Handouts:
Grading, Fill, & ExcavationPlan
1)Please revise the title to state “Grading and TESC Plan”.
2)Please revise the line type legend (differentlinetypesare stated as the same utility).
3)What does PS represent?
4)Pleaseadd a note that the filter socks will be added as needed per Edmonds Standard Detail E1.3.
Stormwater/Erosion Control Plan
5)Please revise the title to state “Stormwater/Utility Plan”.
6)Please revise the line type legend (differentlinetypesare stated as the same utility).
7)Please label the retaining wall.
8)If required, please show where thedrainage for the retaining wall will dischargeto.
9)In the text describing the design of thegraveless chambers, it is stated that the footing drains are
directed to the chambers. Please remove ‘footing drains’since they are directed to a separatedrywell.
10)The cleanouts located to the west of the infiltration systems are not required, please revise as needed.
DATE E-MAILED11/15/2013PAGE(1)
City of EdmondsBLD20131081
TH
121 5AVENUE NORTHEDMONDS, WA 98020 • (425) 771-0220 FAX(425) 771-0221
Website: www.ci.edmonds.wa.us
PUBLIC WORK DEPARTMENT
Planning• Building • Engineering
Engineering Plan Review Comments
11)Observation wells are required onthe gravelless chambers. Please show the wells located near the west
portion of the chambers.
12)It appears that the portions of the drivewaylocated within the right of way are not included in the
impervious surface calculations. Please revise the calculations to include this area.
See the comments below from Jerry Shuster, P.E., Stormwater Engineering Program Manager
The geotechnical report does not provide a design infiltration rate per one of the methods in Appendix C of the
Edmonds Stormwater Code Supplement (ESCS).
(http://www.edmondswa.gov/images/COE/Government/Departments/Public_Works/Stormwater_Utility/pdf/Ed
mondsStormwaterSupplementFinal20100428.pdf).
The sizing of the gravelless chamber cannot be reviewed without such data.The soil samples for the grain size
analysis orthe location of the PIT tests,per Appendix C of the ESCS,must be at the proposed location of the
infiltration chambers and go below the anticipated bottom of the chambers.Note that the pre-sizing table do not
provide for 100% infiltration of runoff.
Please resubmit 3 copies of the revised plansand associated documents with a written response to each
item to a Permit Coordinator. Please contact me at 425-771-0220ext 1321or by e-mail at
jennifer.lambert@ci.edmonds.wa.usif you have specific questions regarding these plan corrections.
DATE E-MAILED11/15/2013PAGE(2)