BLD2014-00238 SWEDISH ED.pdf MEMORANDUM April 7, 2014 Date: Brian Hall, To: bryan.hall@providence.org John Westfall, Fire Marshal 425.771.0213 From: Subject:BLD 2014-0238 SWEDISH HOSPITAL AMBULATORY CARE th CENTER 21601 76 Ave W The Fire Department provides the following comments and corrections in accordance with the 2012 International Fire Code and Edmonds Community Development Code Title 19 for hospital emergency care facility (I2) occupancy. 1. C2.00-A0.21Snohomish Fire District 1 requests preconstruction meeting to clarify ingress & egress for emergency aid apparatus, emergency room access, continuity of operations, and emergency fire response. 2. C2.00-M1.01 Tank removal permit required for abatement & replacement of existing underground fuel tank(s). 3. Doublecheck assembly is located interior MECH ROOM 0186.000. DCDA is not specified on civils. Fire Connection Permit will be required. Provide model and type for WQ approval. Also, WQ must approve the location interior, given the 50 length of the supply pipe from main to DCDA. Contact Linda McMurphy, 425.771.0235. (see 18a) 4. C5.10, C5.14-.15 Retention pipe in emergency apparatus lane at south shall meet the live loads of fire apparatus traffic. 5. A1.01-A1.02 Show calculations and paths for egress. Are elevators intended to be used as component of egress? 6. A1.01-A1.02 Show calculations for establishing refuge areas and call out on plans IBC 407.5.1. 7. Rooms are called out for PATIENT RM and EXAMINATION only. Are any sleeping rooms within scope of project? If so, indicate locations, and patient load calculations. IBC 407.4.3.5. 8. Callout installation of carbon monoxide alarms, where required. 9. A2.01A & A2.01C Location of AFTER HOURS SECURITY GRILLE match line G.5-5.0 is unclear, please clarify. 10. A1.02 & E2.02A Provide exit signs for egress from SHELL SPACE 2A & 2B. City of Edmonds Office of Fire Marshal 11. Post address at north end of east and west elevations, scaled to existing buildings on campus. 12. M5.01A Is generator diesel- or natural gas-fueled? 13. M1.01 Is O2 control valve provided for (exterior) control of supply line? 14. M1.01-M3.01B-M7.04 Regarding oil and O2 separation note, there is existing diesel generator in lower existing mechanical room near Emergency Room. O2 comes in building at lower mechanical room. Are these separate spaces? 15. It appears fire detection will consist o alarms. Please clarify design for assist in fire alarm permit and building permit reviews. IBC 407.7-8 16. Can INTERSTITIAL SPACE be accessed for maintenance or other purpose, and what purpose? Call out access(es)? 17. A9.11-.13 Door Schedule vs. Life Safety Plan a. Overhead Coiling Fire Doors (OCFD) 0102.009A shall be connected to building fire alarm, matchline B.0-4.5 b. Magnetic hold-opens, where provided, shall be connected to building fire alarm. c. Assemblies 0103.031 and 0186.004 callout NR SMOKE protection, matchline D.5-5.0. d. Assembly 0101.004 callout NR SMOKE protection, matchline H.5-4.5. e. Assembly 0104.005 callout, matchline K.5-2.0. f. Assembly 0104.014 callout, matchline J.5-2.0. g. Assembly 0101.002F callout rating for 90 min F.R. corridor doors, matchline YA-4.0. h. Assembly 0101.003 callout rating for 90 min F.R. corridor doors, matchline YA-8.5. i. Callout NR SMOKE for all assemblies in CORRIDOR 0104.002, matchline K.0-1.5. j. Assembly 0104.001A callout rating for 90 min F.R. corridor doors matchline M.5-2.0. k. Assembly 0105.011B callout rating for 90 (or 45?) F.R. corridor doors, level one west. l. Assembly 0204.031 callout 90 min. F.R. doors at west CONNECTOR. m. Assembly 0201.002 callout NR SMOKE protection, matchline J.0-X8. 18. Required permits/submittals include: a. Fire Connection Permit (CIVIL UTILITY and PLUMBING series) Callout Fire Connection Permit (FCP) on building plans, OR callout and detail fire protection supply on civil engineering plans. Fire connection permit is required for the installation of the underground supply for your fire protection system and to de-conflict utility work. Underground design must be stamped by registered PE or a Level III (WA) fire sprinkler contractor AND the installer must also stamp the plans. The installer must prinkler contractor licensed by the State. Provide three copies of plans showing all valves, vault location, post indicating valve, fire department connection and piping to include size and material, hydraulic calculations, thrust blocking with calculations, pipe bury depth and any and all other materials used and their fire protection listings. RCW 18.160.070 / RCW 18.27.110 b. Fire Sprinkler System Permit (M6 series) i. Callout Fire Sprinkler System permit IFC 105.7.1. Automatic sprinkler is required throughout all occupancies in building. Standpipes may be included in sprinkler scope & design. 2 c. Distributed Antenna System (DAS) Permit (LOW VOLTAGE and TELECOM series) i. (TELECOM) DAS for emergency responder mobile radio coverage will require building permit and approval. Wired communications are not acceptable means of emergency communications. Reference IFC 510 for permit and technical requirements, system design, installation requirements and acceptance testing, when DAS requirement is determined. Review and concurrence will also be provided through Snohomish Emergency Radio System (SERS). d. Fire Alarm Permit (LOW VOLTAGE series) i. Automatic fire alarm system is required for purposes of off-site sprinkler system monitoring, smoke-detected egress, and local alarm audible/visual notification and exterior audibility. e. Tank Decommissioning/Installation Permit 19. Regarding fire suppression/detection systems design: a. Collocate fire alarm control panel (FACP) in fire sprinkler riser room. b. Provide fire alarm enunciator at building entry. c. M2.014 KEYNOTE 16 note Fire Department Connection provides 4 Storz connector with 30 degree angle. d. Your fire protection systems underground contractor, sprinkler designer and installer are required to be licensed by Office of the State Fire Marshal for that work. e. Gypsum-- eliminating required sprinkler at top of shaft. f. I2 occupancy requires Quick Response or residential sprinklers. 20. Provide minimum rated 2A:10B:C portable fire extinguishers in accordance with NFPA 10. 21. Provide Snohomish County FD#1 Knoxbox, located at exterior entry to MECH ROOM 0186.000. Preapproval may be had online at www.knoxbox.com . 3