Engineering Plan Review Comments
PermitApplication:Date:
#BLD20140182June 4, 2014
th
Project Name/Address:
Theresa Dixon –7215–175St SW
Contact Person/Address, Fax or E-mail:
Theresa Dixon–THERESA_DIXON@MSN.COM
Reviewer: JENNIFERLAMBERTDivision:
ENGINEERING
During review of the subject submittal, it was found that the following information, corrections, or
clarifications would need to be addressed. All Handouts referred to in these comments can be accessed at
our website: www.edmondswa.govunder City Government / Development Services Department /
Engineering Division then scroll down to Handouts:
st
1Review –4/11/14
nd
2Review –6/4/14
1)6/4/14 –Commentwas partially addressed.
4/11/14 Comment: Please provide a Site Plan that clearly shows the following items:
OK
a.
OK
b.
Not addressed
c.
4/11/14 Comment: The year of construction for all impervious areas
OK
d.
Comment was addressed; however, when the document wasprinted portions of the
e.
document did not print clearlyand are illegible. Please either redline the plans or resubmit
the documentsto clearly show all changes.
4/11/14 Comment: Existing rockeries, retaining walls, fences
Comment was addressed; however, when the document was printed portions of the
f.
document did not print clearly and are illegible. Please either redline the plans or resubmit
the documents to clearly show all changes.
4/11/14 Comment: Proposed retaining walls
DATE E-MAILED6/4/2014PAGE (1)
City of EdmondsBLD20140182
TH
121 5AVENUE NORTHEDMONDS, WA 98020 • (425) 771-0220 FAX (425) 771-0221
Website: www.edmondswa.gov
PUBLIC WORK DEPARTMENT
Planning • Building • Engineering
Engineering Plan Review Comments
2)6/4/14 –Comment was partially addressed. A Geotechnical Report was provided stating the
Geotechnical Engineerapprovedthe water to discharge to the existing stormwater collection
system.
Please show the location of the existing system.
a.
Please show how you will collect the retaining wall drainage andpatio surface water runoff
b.
to the onsite system (i.e. pipe material, pipe size, invert elevations, etc.)
Please provide documentation that shows the existing system can accept the additional
c.
flows.
th
Or, if the water is to discharge to the City Storm system on 175St, please show how you
d.
will collect the retaining wall drainage and patio surface water runoff (i.e. pipe material,
pipe size, invert elevations, etc.)
Please show thewater (from meter to house) and sewer (from sewer main to house) so that
e.
utility separation can be verified.
4/11/14 Comment: Please show where the drainage for the walls will discharge to. The discharge
location must be approved bythe Geotechnical Engineer.
Please resubmit 3 copies of the revised plansand associated documents with a written response to each
item to a Permit Coordinator. Please contact me at 425-771-0220ext 1321or by e-mail at
jennifer.lambert@edmondswa.govif you have specific questions regarding these plan corrections.
DATE E-MAILED6/4/2014PAGE (2)