Loading...
BLD2014-0331 Smith Fire Resub.pdfAW (253) 926-1880 • FAX (253) 926-2350 SMITH FIRE SYSTEMS, INC. 1106 54th Avenue East • Tacoma, Washington 98424 July 28, 2014 Attention: Reference: Jacobsen's Marine SFS Job #: TC14003 The following is an item -by -item response to the comments noted on the City of Edmonds plan review comment letter. 1. Both plans and hydraulic calculations has been modified to reference to the 2010 version of NFPA 13. 2. This system capacity is 389 gallons and shall be permitted without a quick opening device and should not be required to meet any specific water delivery requirements to the inspection test connection as addressed in 7.2.3.3. 3. Supervision of sprinkler piping and fire detection devices is provided by others. 4. Air compressor GAST 5LCA-22-M550X will provide air supply source at all times and meets the 30 -minute fill requirement for the system as required by 7.2.6.2. 5. A minimum of 2 spare sprinklers for every type of sprinkler used on the system are provided in the spare head cabinet. 6, Alarm bell is provided by others. 7, Floor drain is provided in the fire riser room as noted on sheet 1 and meets the requirement of section 8.16.2.4.4. 8. All rooms are shown on the plan as specified in section 22.1.3. 9. 2 -Inch branch lines will be restrained as required by section 9.3.6 of NFPA 13, 2010. 10. Lateral sway bracing calculations has been revised and match the plans. SMITH FIRE SYSTEMS, INC. Denis Rabivevskiv Designer (253)248-2658