BLD2014-0357 Sherwin Williams.pdf
MEMORANDUM
May 9, 2014
Date:
Amy Colby amyc@jpcarchitects.com; Carrie Walker
To:
carriew@jpcarchitects.com, Scott Thompson
scott@scottathompson.com.
John Westfall, Fire Marshal 425.771.0213
From:
Subject:BLD 2014-0357 SHERWIN-WILLIAMS WESTGATE
TH
22804 100 AVE W.
The Fire Department provides the following comments and corrections in accordance with the 2012
International Fire Code and Edmonds Community Development Code Title 19 for existing 4810 s.f.
Mercantile group compartment.
1. Sheet 1-0.0 Deferred submittals omit FIRE ALARM SYSTEM and FIRE SPRINKLER
SYSTEM unless voluntary systems are desired.
2. Sheet 1-0.0 Note: INTENT IS TO MAINTAIN TENANT SPACE AS MERCANTILE
OCCUPANCY GROUP WITHIN LIMITS OF SINGLE NONSPRINKLERED CONTROL AREA
FOR FLAMMABLE AND COMBUSTIBLE LIQUID STORAGE. INVENTORY OF CLASS IB, IC, II,
AND IIIA WILL VARY DAY TO DAY, NEVER IN EXCESS OF 1,600 GALLONS LIMIT FOR
NONSPRINKLERED SPACE PER 2012 IFC TABLE 5704.3.4.1. or other approved wording.
3. Submit letter with application from Robert Sommers, Senior Project Engineer for Sherwin
Williams, dated February 7, 2014, attached in this email.
4. Sheet I-3.1 Label space with exterior access @ NW corner of project.
5. Sheet I-3.1 Provide minimum rated 2A:20B:C portable fire extinguisher (typical) for
ordinary (moderate) Class B hazard.
City of Edmonds Office of Fire Marshal