BLD2014-0752 BERESFORD TI.doc MEMORANDUM Date:August 25, 2014 To:Jessica Cross, jcross@tgbarchitects.com From:Fire Marshal John J. Westfall 425.771.0213 rd Subject:BLD2014-0752 Beresford Booth PLLC TI, 145 3 Ave S #200 This Review is conducted in accordance with 2012 IFC and Edmonds Community Development Code. 1) Sheet A0.00 a. No fire sprinkler or fire alarm installations to modify according to Building Department records, hence, no DEFERRED SUBMITTAL requirement for 3) FIRE SUPPRESSION, and 4) SMOKE DETECTION. Delete requirements 3 & 4, however, see #2c below. b. If fire alarm system is approved, Knoxbox series lock box will be required for installation. See www.knoxbox.com and follow directions for purchase of Snohomish Fire District #1 series box. 2) Sheet A0.10 nd a. Will there be single tenant for entire 2 floor, responsible for control of both doors to EXIST HALLWAYs (203), and (211)? b. If multiple tenants; i. Call out the door and hardware for door separating EXIST HALLWAY (211) and EXIST OPEN OFFICE (221). ii. Also call out the door and hardware for assembly separating EXIST HALLWAYs (201) and (203). c. Clarify installation of FIRE ALARM panel in EXIST VESTIBULE (003). Per Building Department records, no historic permits show approved fire alarm installation. d. Emergency pathway lighting shall be (provided, or) maintained in EXISTING HALLWAYs leading to exit doors (203) and (104), as well as stair and entry hallways. IFC 1006.3(3). e. EXIT illumination shall be (provided, or) maintained IFC 1011.1. ND f. LIFE SAFETY-LEVEL 1: Show OCCUPANCY FROM 2 FLOOR for stair S1. 3) Sheet A2.02 a. It appears door 201 is intended to be locked during periods other than “during business hours”. This allowance is intended only at the “main exterior door(s)” to the building and does not apply to individual tenant entries for leased spaces nd inside Group B buildings. Provide alternative proposal for security on 2 floor. cc: Building Official Leif Bjorback City of Edmonds Office of Fire Marshal   2