BLD2014-0914 GW Auto FOLLOWUP.pdf MEMORANDUM Date: June 3, 2015 To: Henry Byam, hb@wescogroupinc.com From: John Westfall, Fire Marshal 425.771.0213 Subject:BLD 2014-0914 GW Auto Rebuild 23510 Highway 99 COMMENTS ON RESPONSE The Fire Department provides the following comments and corrections in accordance with the 2012 International Fire Code and Edmonds Community Development Code Title 19. CITY REQUIREMENTS 1. NOTE: Open fire alarm permit BLD20150547 for replacement FACP & AES. Verify work and provide system service report. 2. NOTE: Verify existing/modified sprinkler system service report 3. NOTE: Knox box will be required at gated entry. 4. NOTE: Field check clearances and signage for fire protection FDC(s), appliances and equipment access locations. 5. Install sign in PAINT ROOM or that provided by manufacturer: MAXIMUM ALLOWABLE QUANTITY NOT TO EXCEED 120 GALLONS OF FLAMMABLE LIQUIDS. 6. Post address 23510 at east elevation 7. Occupancy type is indicated as S1 throughout. Group F-1 includes finishing, repair or processing operations for automobiles. This reviewer suggests that SANDING AND PAINT, SANDING & PREP SHOP and SANDING-PREP-PARTS-STORAGE EAST be retyped. New addition DETAIL AREA may remain S1/S2. IBC 508.4 allows S1 and F1 to share building space with no required separations. 8. Occupant load factor is 200. Occupant load is calculated at 6577/200=32. Only one exit is 9. Install EXIT sign at NEW EXIT. 10. Call out HOT WORK AREA(s). 11. NOTE: Remove or protect existing electrical wiring in CTOF/Paint room installation area safe separation (NFPA 33 Fig.14.3.5.1) 12. Provide Hazardous Materials Inventory Statement (HMIS) for building. Indicate individual container sizes, aggregate daily inventory, hazardous classification (flammable /combustible) and locations. IFC 5001.5.2 13. Spill control and secondary containment is required for individual containers greater than 55 gallons or aggregate quantity greater than 1000 gallons (IFC 5004.2.1) 14. Pre-manufactured GFS paint room assembly What functions are tied to interlock? NOTE: Field test proximity sensor controls for correct operation. City of Edmonds Office of Fire Marshal 15. Applicant indicates for downdraft CTOF, all maintenance can be done from inside cabin (Safety Precautions & FIRE letter response #14), however, CTOF ASSEMBLY INSTRUCTIONS sheet GA-CTVDP-241409 specifies (PLAN VIEW drawing) that access should be left on wal 16. Where suppression system is provided, a separate permit is required. Where sprinkler system is additionally modified, an additional permit will be required. 17. Location of 4A:40B:C fire extinguisher provided in SANDING PREP SHOP is approved. (IFC 5704.3.7.5.2) 18. PAINT-MIX ROOM door. (IFC 5704.3.7.5.2) 19. Additionally, provide two 2A:10B:C fire extinguishers; one in DETAIL AREA near EXIT, and one in SANDING-PREP-STORAGE-EAST for other building hazards. (IFC 906.3) 2