Loading...
BLD2014-1295 Prestige FA 21008 76th.pdf MEMORANDUM Date: January 9, 2015 To: David Mow, david@fpiseattle.com From: Fire Marshal John J. Westfall 425.771.0213 th Subject:BLD20154-1295 21008 76 Ave W, Prestige Care FA This Review is conducted in accordance with 2012 IFC, 2010 NFPA 72 and Edmonds Community Development Code. 1) For Group I occupancies, manual fire alarms shall be installed and activate the occupant notification system or private mode signaling arrangement may be installed when approved. Install manual fire alarms or call out how alarms might be managed and from which locations in a private mode arrangement. IFC 907.2.6 exception 2 2) General Note: For I-2 occupancy, smoke detectors in corridors (CIRCULATION/HALLS) eliminates requirements for unit smoke detectors. IFC 907.2.6.2 3) Call out emergency voice/alarm communications systems and installation. In group I-2 occupancies the alarm shall sound in a constantly attended area and a general occupant notification shall be broadcast by overhead page. Call out constantly attended area and equipment required for performance. IFC 907.5.2.2 exception. 4) General Note: Smoke detector shall meet nominal 30’ spacing (typical) or clarify prescriptive performance requirements if different for smoke detectors. 5) Callout connection points for delayed egress hardware that must release during alarm event. 6) Sht FA1.3 Provide exterior notification: a. At the (interior) courtyard side of DINING 118. b. At the exterior door closest to FIRE SPRINKLER 135. 7) Sht FA 1.3 Provide additional FARA in FIRE SPRINKLER 135 for all fire controls. 8) Sht FA 1.3 Additional FARA and/or pull station may be required at NURSE STATION (see #1 & #3). 9) Sht FA1.3 Strobe only required in BATHING 126. Please make corrections and resubmit your plans. City of EdmondsOffice of Fire Marshal