Engineering Plan Review Comments
PermitApplication:Date:
#BLD20150239December 7, 2015
Project Name/Address:
Kemper –9303 Olympic View Dr
Contact Person/Address, Fax or E-mail:
Keith Kemper –kkemps@comcast.net
Reviewer: JENNIFERLAMBERTDivision:
ENGINEERING
During review of the subject submittal, it was found that the following information, corrections, or
clarifications would need to be addressed. All Handouts referred to in these comments can be accessed at
our website: www.edmondswa.govunder City Government / Development Services Department /
Engineering Division then scroll down to Handouts:
st
1Review –4/24/15
nd
2Review –12/7/15
GENERAL
1)
4/24/15 Comment -There are too many plans on the submitted plan sheets that address the same
information throughout each plan. Please revise the Plan sheets as stated below.
OK
a.
OK
b.
OK
c.
OK
d.
OK
e.
f.Due to the amount of plans submittedand the overlap of information on the three sheets the
comments below will attempt to capture all changes; however, there may be additional comments
nd
after the 2submittal not addressed in this submittal.
2)12/7/15 –New Comment –Please label the private access and utility easement.
3)12/7/15–New Comment –Please make sure that theSite Plan and the Civil Plans are consistent.
Label theretaining walls, rockeries, etc on both plan sheets.
DATE E-MAILED12/7/2015PAGE (1)
City of EdmondsBLD20150239
TH
121 5AVENUE NORTHEDMONDS, WA 98020 • (425) 771-0220 FAX (425) 771-0221
Website: www.ci.edmonds.wa.us
PUBLIC WORK DEPARTMENT
Planning • Building • Engineering
Engineering Plan Review Comments
TEMPORARY EROSION CONTROL PLAN–Now called GRADING AND TESC PLAN
1)OK
2)OK
3)OK
4)OK
WATER
1)12/7/15 –Comment was partially addressed. It appears that there are two pipe sizes called out for
the water service line. Please revise the plans to make sure that all items below have been
addressed.
4/24/15 Comment -It appears that a fire sprinkler system is required for this property.Typically if there
is an existing water service line from the watermain to the meter it will not be the appropriate size and a
new tap will be required.
a.Please show the water service line from the meter to the house.
b.Please add a note that a 1” meter is to be installed.
c.Please show a 1-1/2” line to be installed (as required for a combination fire and domestic service
line).
d.Please label the pipe material andnotetracer wireto be installed on the water service line.
e.There must be a minimum of 3’ separation between the dry utilities (power, gas, cable, etc.) and
the water main. Please revise the plans accordingly.
2)12/7/15 –Current location is approved; however, since themeter needs to be upsized due to the
requirement for a fire sprinkler system, therewill be a new tap on the main.
a.The current and new water service line from themain to the meter comes or will come into
the east side of the meter. Please revise your plans to show the water service from the
meter to the house leaving the meter on the west side.
DATE E-MAILED12/7/2015PAGE (2)
City of EdmondsBLD20150239
TH
121 5AVENUE NORTHEDMONDS, WA 98020 • (425) 771-0220 FAX (425) 771-0221
Website: www.ci.edmonds.wa.us
PUBLIC WORK DEPARTMENT
Planning • Building • Engineering
Engineering Plan Review Comments
b.Please add a note to the plans that the location of the new meter to be coordinated withthe
City’s Water Department at 425-771-0235.
4/24/15 Comment -Confirmation on where the water meter can be located is currently being reviewed
by the City’s Water Department. Commentswill follow addressing this issue.
3)12/7/15 –New Comment –The water service line is showing as being replaced within the asphalt
of the private drive. Please show/notethe following,“Contractor to complete final restoration on
all trench patches for utilities installed with this development.”
SEWER
1)OK
2)OK
3)OK
4)12/7/15 –Comment partially addressed.The lamphole cover note was not added.
4/24/15Comment -Show a 6” cleanout at the edge of easement (located within the easement). Please
add a note that the 6” cleanout at theedge of easementwill have a 12” cast iron lamphole cover with ½”
hexbolts.
5)OK
6)12/7/15 –Comment was not addressed.
4/24/15 Comment -Please show the invert elevations at the main and the house so that slope and
coverage can be verified. If the slope of the pipe exceeds 20% the pipe will need to be anchored.
STORM
1)12/7/15 –Comment wasaddressed; however, footing drains,sump pumps, retaining wall and
rockery drainage, typically do not discharge to the onsite stormwater managementsystem unless
the system is designed to account for theadditional water.
a.Please revise thedrainage report to address the addition of the footingdrains,sump pump,
retaining wall and rockery drainageto the proposed system.
DATE E-MAILED12/7/2015PAGE (3)
City of EdmondsBLD20150239
TH
121 5AVENUE NORTHEDMONDS, WA 98020 • (425) 771-0220 FAX (425) 771-0221
Website: www.ci.edmonds.wa.us
PUBLIC WORK DEPARTMENT
Planning • Building • Engineering
Engineering Plan Review Comments
b.Orthe footing drains,sump pump, retaining wall rockery drainagemaydischarge to a
separatesystem (i.e. drywell). If you choose this option, please provide a memo from the
Geotechnical engineer of record approving the location of the drywell.
4/24/15 Comment -Show where the footing drains will discharge to.
2)4/24/15 –Comment was not addressed. It appears that there is a retaining wall along thewest
patio. Please show where the drainage for both the retainingwall and rockery willdischarge to.
Please refer to note one above.
4/24/15 Comment -Show where the retaining wall drainage will discharge to.
3)12/7/15 –Comment (a) was not addressed.
4/24/15 Comment -Per the plat (S98-082) this lot has a detention system that was installed and designed
to collect 5000 sqft of impervious surface water. If you have 5000 sqft or less you may directly
discharge to this system without an additional detention system. To discharge to this system, please
provide the following.
a.Please submit a report that verifies that the existing system is functioning properly.
b.If the amount of impervious area exceeds 5000 sqft, a flow control system will need to be
installed to account for the additional impervious area.This configuration will need tobe
evaluated by a licensed engineer to show that the downstream system (not owned by the City) is
not adversely impacted.
4)OK
5)12/7/15 –Comment was not addressed.
4/24/15 Comment -Please provide rim and invert elevations for all pipes within the catch basins.
NEW COMMENTS
6)12/7/15 –Please show how the runoff from the drivewaywill discharge to the catch basin (i.e.
directional flow arrows, etc.).
7)12/7/15 –Note the catch basin in the driveway as a Type I.
8)12/7/15 -Add an observation well to the infiltration system.
DATE E-MAILED12/7/2015PAGE (4)
City of EdmondsBLD20150239
TH
121 5AVENUE NORTHEDMONDS, WA 98020 • (425) 771-0220 FAX (425) 771-0221
Website: www.ci.edmonds.wa.us
PUBLIC WORK DEPARTMENT
Planning • Building • Engineering
Engineering Plan Review Comments
9)12/7/15 –Showthe pipe connecting to the infiltration at the north end (not at the middle of the
pipe).
10)12/7/15 –The force line from the sump pump needs to connect to a catch basin. Please revise
accordingly.
DRY UTILITIES
1)12/7/15 –Comment was addressed; however, the 3’separation applies to stormas well. This was
not originally put in the comment since there was no conflict with storm at that time. Please
address accordingly.
4/24/15 Comment -Please showaminimum of 3’ separation between the sewer/water andallthedry
utilities(gas, phone, cable, etc.).
Please resubmit 3 copies of the revised plansand associated documents with a written response to each
item to a Permit Coordinator. Please contactme at 425-771-0220ext 1321or by e-mail at
jennifer.lambert@edmondswa.govif you have specific questions regarding these plan corrections.