Subject: BLD2015-0541 Westgate Clothing Outlet
Mark:
Fire comments are as follows:
1)PAINTED EXIT LANE BOUNDARY does not meet code requirements for exiting through
intervening rooms. Exit requires a 44” aisle defined by a full or partial height fixed wall or similar
construction. IFC 1014.2.4 exc 2.4
2)Calculate and callout occupant load for M (mercantile) occupancy at 30 s.f. per person.
3)Provide illuminated exit sign at rear exit access door and exit door.
4)Provide emergency egress lighting in retail area and exit access.
5)This reviewer is not sure how SLAT WALL is defined. However that is, verify wall meets Class C
finish requirements in accordance with ASTM E 84 or UL 723. (C=Flame Spread Index 76-
200/Smoke Developed Index 0-450).
Please wait until all departments have provided comment and resubmit your plans.
Thank you,
John J. Westfall
Fire Marshal