BLD2015-0846 Point Edwards 10.pdf
MEMORANDUM
Date:
December 10, 2015
To:
Aidan Bird
From:
John Westfall, Fire Marshal 425-771-0213
Subject:BLD2015-0846 Point Edwards Building #10 50 Pine Street
The Fire Department provides the following comments reviewed under 2012
International Codes and Edmonds Community Development Code.
CIVILS:
1. C7 Revise note: Stripe & mark FIRE LANE AERIAL NO PARKING on
Pine Street.
2. C6 Revise/note in exterior parking area: Fire access roads shall be striped on
spaced 50 lineal feet on alternating insides of lane.
ARCH & DESIGN:
3. G001 DEFERRED PERMITS:
a. Add: DISTRIBUTED ANTENNA SYSTEM (DAS), WHEN REQUIRED.
b. A third party inspection report will be required for city to evaluate the
necessity for DAS system per IFC 510.
4. G001 DEFERRED PERMITS:
a. Add: FIRE CONNECTION PERMIT, WHEN REQUIRED.
b. Fire connection permit is required for the installation of the underground
supply for your fire protection system. Underground design plans and
details must be stamped by registered PE or a Level III (WA) fire sprinkler
contractor AND the installer must also stamp the plans. The installer
the State. Provide three copies of plans showing all valves, vault location,
post indicating valve, fire department connection and piping to include
size and material, hydraulic calculations, thrust blocking with calculations,
pipe bury depth and any and all other materials used and their fire
protection listings. RCW 18.160.070 / RCW 18.27.110
City of Edmonds Office of Fire Marshal
1) G001 DEFERRED PERMITS:
a) STANDPIPE PERMIT may be incorporated with FIRE SUPPRESSION permit.
b) FIRE ALARM is a separate permit.
2) G001A FD NOTES
A) Revise: SNOHOMISH COUNTY FIRE DISTRICT #1, CONTACT IS FIRE
MARSHAL KEVIN ZWEBER, 425.775.7720.
b) Delete fire permits required. All fire permits are applied for at city, approved and
issued by the city, and are noted on G001.
C) ORDER FD1 KNOXBOX ACCESS AND KEYSWITCHES THROUGH
WWW.KNOXBOX.COM FOR SNOHOMISH COUNTY FIRE DISTRICT 1
SERIES.
3) G002 Revise: SPRINKLERED BUILDING PER 2012 IBC 903.3.1.1.
4) G002 Revise: WASTE & LINEN COLLECTION s/b TABLE 509.
5) G003 & A313 ELEVATORS
a) Add NOTE: ELEVATORS SHALL BE UL 2200 LISTED.
b) Callout manual transfer switch control location. Automatic backup power transfer
is required after 60 seconds for both elevators.
c) Callout necessary operational, venting, and signal equipment tied to backup
power for the purpose of elevator egressability.
d) Callout standardized fire service elevator key per IFC 607.
6) A108 & A110
Explain process for collection and removal of building rubbish from L107 and L210.
7) A108 (typical)
Detail how elevator doors meet shaft and corridor fire- and smoke-protection.
8) A108 & A128
Reconcile labels for L103 FIRE SYSTEMS CONTROL ROOM and STORAGE
ROOM.
9) A120 Unit Plans (Typical)
Callout smoke alarm locations and carbon monoxide detection details.
10) A311 DTL 4 Stair plans
Callout 2 hr FR protection for L5 STAIR PLAN.
11) A312 DTL D & A802 DTL 10 Egress Gates
Callout gate location(s) on plans.
12) A314 DTL B Rubbish Chute
Add NOTE: AUTOMATIC SPRINKLER SYSTEM INSTALLED AT THE TOP OF
RUBBISH CHUTES AND IN TERMINAL ROOM. ADDITIONAL SPRINKLERS WILL
BE INSTALLED AT ALTERNATING FLOORS AND AT LOWEST INTAKE.
2
13) A601 Door Schedule
a. IBC Table 1018.1 requires CORRIDOR openings to be provided with no less
than 0.5 Hr FR doors. Revise FR door specifications along corridor at this
minimum when not already a 20 minute unit door assembly and where not
otherwise prescribed a greater FR rating.
b. Sign FIRE CONTROL ROOM exterior door 107.
14) Call out EMERGENCY GENERATOR location on plans. Specify model, type and
quantity of fuel. Specify the minimum emergency functions to power.
FIRE PROTECTION Comments:
15) Incorporate Class I standpipe with sprinkler design and permit. IFC 905.3.1 (exc1).
16) Sprinkler riser room is identified as Fire Systems Control and fire alarm control panel
will be collocated with sprinkler riser here.
17) Sprinkler over fuel fired appliances installed under attached canopies and covers.
18) Sprinkler control signage.
end