Engineering Plan Review Comments
PermitApplication:Date:
#BLD20151115February 18, 2016
th
Project Name/Address:
Crosby Homes Inc –23207–75Pl W
Contact Person/Address, Fax or E-mail:
chuckcrosby@cox.net
Reviewer: JENNIFERLAMBERTDivision:
ENGINEERING
During review of the subject submittal, it was found that the following information, corrections, or
clarifications would need to be addressed. All Handouts referred to in these comments can be accessed at
our website: www.edmondswa.govunder City Government / Development Services Department /
Engineering Division then scroll down to Handouts:
st
1Review –10/23/15
nd
2Review –1/11/16
rd
3Review –2/18/16
SITE PLAN(1OF 3)
1)10/23/15 Comment -As changes are made to other plan sheets, please revise this sheet as needed.
2)OK
3)OK
4)2/18/16 –New Comment –Please show the 10’ Sewer Easement on this plan sheet.
GRADING & TESC PLAN (2 OF 3)
1)OK
2)OK
3)OK
DATE E-MAILED2/18/2016PAGE (1)
City of EdmondsBLD20151115
TH
121 5AVENUE NORTHEDMONDS, WA 98020 • (425) 771-0220FAX (425) 771-0221
Website: www.edmondswa.gov
PUBLIC WORK DEPARTMENT
Planning • Building • Engineering
Engineering Plan Review Comments
4)OK
5)1/11/16 –Revise this plan sheet as needed when revising the other plan sheets.
DRAINAGE/UTILITY PLAN (3 OF 3)
GENERAL
1)OK
2)OK
3)2/17/16 –Comment not addressed.
1/11/16 –Comment was partially addressed. Please state what material is proposed below the deck.
10/23/15 Comment -Please label the deck (i.e. spaced deck with permeable surface below, impervious
deck, etc.).
WATER
1)OK
2)OK
SEWER
1)OK
2)OK
3)OK
DATE E-MAILED2/18/2016PAGE (2)
City of EdmondsBLD20151115
TH
121 5AVENUE NORTHEDMONDS, WA 98020 • (425) 771-0220FAX (425) 771-0221
Website: www.edmondswa.gov
PUBLIC WORK DEPARTMENT
Planning • Building • Engineering
Engineering Plan Review Comments
4)OK
5)OK
STORM
1)2/18/16 –Comment does not appear to be addressed.
a.The impervious surface calculations do not appear to include the area of the driveway
approach that is located within the right-of-way. Please revise accordingly.
b.It does not appear that the runoff from the portion of the driveway located within the
right-of-way is discharging to the onsite stormewater management system. Please revise the
plans accordingly(i.e. thickened edge, curb, sloping of the driveway, etc. along the east
edge of the proposed driveway) .
10/23/15Comment -The area of the driveway located in the City right-of-way must be included in the
impervious surface calculcations. That area does not have to be collected to the onsite stormwater
managemet system if itis not feasible. If it is, please direct it to the stormwater management system.
Please revise the plans accordingly.
2)OK
3)OK
4)2/18/16 –New Comment. Per the plan sheets, there is retaining wall proposed along the west side
of the driveway; however the wall is not shown in the detail ‘Section B-B’. Please revise
accordingly.
Comments by the City Stormwater Engineer Program Manager, Jerry Shuster, PE
Drainage & Design Narrative, RMS Engineering, August 24, 2015
1.OK
2.OK
3.OK
4.OK
5.OK
DATE E-MAILED2/18/2016PAGE (3)
City of EdmondsBLD20151115
TH
121 5AVENUE NORTHEDMONDS, WA 98020 • (425) 771-0220FAX (425) 771-0221
Website: www.edmondswa.gov
PUBLIC WORK DEPARTMENT
Planning • Building • Engineering
Engineering Plan Review Comments
DRY UTILITIES
1)2/18/16 Comments –Comments were partially addressed. There is no power located on the pole
where it is shown for power to be pulled from (per PUD). The power will need to be pulled
th
(underground) from the pole located on the east side of 74Ave W. It is unclear if the same is
true for phone and cable as well. Please revise the plans accordingly.
10/23/15 Comment:It appears that the power is proposed to be aerial; however, all utilities must go
underground. Please revise the plans accordingly.
2)2/18/16 –This commentis remaining in case utilities are relocated as plans are revised.
10/23/15 Comment: Please show all proposed dry utilities (gas, phone, cable, etc.) on the plans so that
utility separation can be verified. Minimum of 3’ horizontal separation between the dry utilities and
water, sewer, storm.
Please resubmit 3 copies of the revised plansand associated documents with a written response to each
item to a Permit Coordinator. Please contact me at 425-771-0220ext 1321or by e-mail at
jennifer.lambert@edmondswa.govif you have specific questions regarding these plan corrections.
DATE E-MAILED2/18/2016PAGE (4)