Bld2016-0506 Post Off PII.pdfDate: June 23, 2016 To: Doug Spee, dls ee(cDgmaiil,co, Scott Boyer, py rscotLl mail corn, Haller Architects LLC From: Fire Marshal Kevin Zweber 425.771.0213 Subject: BLD2016-0506 Post Office Phase II, 201 Main Street This Review is conducted in accordance with 2012 IFC and Edmonds Community Development Code. 1) A2.01 call out fire hydrant and proposed FDC Location, 2) G0.02 Deferred Submittal for the following: Fire Connection, Fire Sprinkler, Fire Alarm, Fire Standpipe, Emergency Responders Radio System (if required). 3) GENERATOR. a. For what function is the generator? Will backup power be used for elevator evacuation per 3008 and what allowances are you applying with that? b. Provide specifications for generator, fuel type, and fuel quantity stored. c. Specifications for generator are provided, call location. 4) Post address on frontage with letters minimum 6" on contrasting background, 5) Take in account lower dry sprinkler piping in unheated garage spaces for vertical clearance in garage drive aisles. 6) Fire marshal does not find references to exit lighting or emergency illumination, or fire extinguisher installation on plans. 7) Provide permanent KNOX BOX at Main Street entrance and next to fire riser room for after-hours FD access. Visit www.knoxbox.com for preauthorization from Snohomish County FD#1. 8) Reminders for fire protection design: a. Collocate fire alarm control panel in SPRINKLER room and provide FA enunciator in RESIDENTIAL LOBBY. b. Sprinkler system valve(s) will be electrically supervised by fire alarm. No PIV is required in this design configuration where immediate access is provided by exterior door to FACP and riser. 9) Call out elevator size to be adequate for Fire Department gurney. cc: Building Official Leif Bjorback City of Edmonds Sb Office of Fire Marshal