BLD20160897 22727 Hwy 99 Grace Evangelical Church.doc
CITY OF EDMONDS
DEPARTMENT OF FIRE PREVENTION
MEMORANDUM
October 4, 2016
To: David Lo, Grace Evangelical Free Church
Davidlo60@msn.com
From: Kevin Zweber, Fire Marshal
Subj: Fire Plan Review for Grace Evangelical Free Church permit application
BLD20160897
This review was conducted in accordance with the 2015 International Fire Code (IFC)
and Edmonds Community Development Code. In reference to the above permit
application the following notes are provided:
1. Provide on the Plans “Deferred permit submittals: Fire Sprinkler modification,
Fire Alarm modification, Fire Operations Permit (Permit A)”.
2. Provide illuminated exit and egress lighting throughout the building. Your
symbols on the drawings only indicate “exit”.
3 Room 109 Dwg 1:
a. Provide on the plans, “Stage curtain must meet the requirements of IFC
807.3 and 807.4.”
b. The amount of flammable decorative wall coverings has limitations.
4. Room 110 – Dwg 2:
a. Call out dimensions, use of, and occupant load of each room or area.
b. Dwg 2 and 7 conflict in the space layout related to walls and doors. Clarify.
5. Room 201, call out dimensions, use of, and occupant load of each area, so the
requirement of an additional exit can be determined. Occupant load of the
office, lunch, and meeting rooms, etc will determine the ability to have the
sliding door.
Kevin Zweber
Deputy Chief – Fire Marshal
City of Edmonds,
Department of Fire Prevention