CITY OF EDMONDS
DEPARTMENT OF FIRE PREVENTION
MEMORANDUM
July 3, 2017
To: David Estes
DHESTES_aia@frontier.com
From: Kevin Zweber, Fire Marshal
Kzweber@firedistrict1.org
Re: Plan Check: BLD20161684
Address: 21300 Hwy 99, Edmonds, WA 98020
Project: Magic Toyota
Scope: New Commercial Building
During review of the plans for the above project, it was found that the following
information, clarifications or changes are needed. Please provide written responses as
to where the changes can be found on the plans; please cloud the changes or additions.
It is preferred that only the affected plan sheets be resubmitted:
1. Please provide a section for Fire Marshal Notes consisting of the following:
a. Emergency Responder Radio System evaluation required to determine the
b. Fire Extinguishers to be provided in accordance with IFC Table 906.3(1).
c. If site access gate(s) cross a fire access road they must comply with the Fire
Department Emergency Access Standard.
d. Provide guard post where hydrants, tanks, generators, gas meters are subject
to vehicle impact. IFC Section 312.
e. Provide fire protection and utility identification (signs) and access. IFC Section
509.
f. If an onsite generator is proposed it must comply with IFC Section 604.
g. The fire alarm control panel shall be located in the fire riser room.
h. Provide Knox Boxes: 1) at fire riser room, 2) at main entrance. Additional
as required. Order at www.Knoxbox.com.
i. Provide signage for weight limit of ramp to upper level parking.
j. The following IFC Chapters or sections may apply: 24 flammable finishes,
35 welding and hot work, 50 - hazardous materials, 53 compressed gases,
and 57 flammable and combustible liquids.
K. Fire Department Contact: DFM Karl Fitterer, 425-775-7720.
2. Call out separate permits: Automatic fire sprinkler system, fire alarm system,
Emergency Responder Radio System (if required after evaluation).
3. Provide premise identification on the North and East side of the structure, 12
tall, minimum contrasting in color to the building, location to be
4. Service area must comply with the requirements of IFC 2311 Repair Garages.
5. Provide a code summary page providing the following for each room and/or floor:
occupancy class, occupant load per room or area, exit access travel distance
and common path of egress travel.
nd
6. I am requesting you provide a dry standpipe for firefighting operations on the 2
floor parking area, possibly in the mechanical covered area (center). The
estimated hose distance up the ramp and to the furthest parking area is greater
than 200. A single fire department connection for this dry standpipe could be
located on the west side of the building near a fire hydrant.
Please let me know if you have questions,
Kevin Zweber
Deputy Chief Fire Marshal
City of Edmonds,
Department of Fire Prevention
425-771-0213 Office