Loading...
BLD20170629 - Oneal - E1.pdf CITY OF EDMONDS PLAN REVIEW COMMENTS ENGINEERING DIVISION (425) 771-0220 City Website: www.edmondswa.gov DATE:June 21,2017 TO:Don and Terri O’Neal Donald.Oneal@Onealbrokawprg.com FROM:Mitch Boyd,Stantec Consulting Services Mitch.Boyd@edmondswa.gov RE:Application #: BLD20170629 Project: O’Neal-Single Family Residence nd Project Address: 15712 72AveW During review of the above noted application, it was found that the following information, corrections, or clarifications are needed. Reviews by other divisions, such as Planning, Building, or Fire may result in additional comments. Please submit two (2)sets of revised plans/documents including a written response to each item below. nd Resubmittals can be made at the Development Services Department on the 2floor of City Hall. Permit Center hours are M, T, Th & F from 8am-4:30pmand on Wednesdays from 8:30am-noon. City of Edmonds handouts, standard details, application and other forms, and development code may be referenced on the City website: www.edmondswa.govunder Services/Permits and Development. GENERAL 1)Include construction sequence. Refer to sample on City website. 2)Include General Construction Notes. Refer to sample on City website. 3)Consistent with Edmonds Community Development Code 18.80.060, driveway slopes shall not exceed 14% slope. Please indicate this requirement on the plans. 4)Please note: additional comments not included in this reviewmay be produced after . reviewing the next submittal TESC 1)Please provide the location of the temporary stockpile. Add a note that the stockpile is to be covered within 24 hours 2)Please add a note to the plans that all disturbed soils will be compost amendedper BMP T5.13. 3)Add note: Install and maintain all TESC measures according to approved plans, City of Edmonds standard details, and all other measures that may be required during construction. DRAINAGE, GRADING, AND UTILITY PLAN 1)The Fire Department has yet to review the project set. The requirement for fire sprinklers if will be provided at a later date. Note that a fire sprinkler system is required for this property: a.Please add a note that a 1” meter is to be installed b.Show the water meter located in the right-of-way, such that the back of the meter is on the property line. The water meter shall not be located within the driveway. c.Please show a 1-1/2” water service line to be installed from the back of the meter to the house (as required for a combination fire and domestic service). d.Please label the pipe material and note tracer wire to be installed on the water service line. 2)Please show the water connection to the house. Currently, there is only the short plat water stub. 3)Please add a callout to the plans indicating where one can find the detail for the residential sewer pump.Please include the pump detail in theplan set. 4)Please show the sewer connection from the structure to theproposed grinder pump. 5)Provide a sewer cleanout within 2’ of the structure. 6)Note: the grinder pump is under further review. Additional comments regarding the grinder pump may be submitted at a later date. 7)Please note that a minimum of 2’ of cover is required for allstormwaterpipes locatedunder driveable surfaces and 1’ of cover under landscape areas. Currently there is insufficient cover at the proposed residential CB. 8)Show where the rockerydrainage will discharge to. 9)The low point of the footing drain is on the west side of the house. Please provide the IE elevation at the low point and confirm the IE is at or higher than the footing drain connection elevation. 10)Show all dry utilities and required utility separation. Please add a note that a minimum of 3’ separation is required between the dry utilities (power, gas, phone, cable, etc.) and wet utilities (sewer, water, and storm). 11)Add a note to the plan that the driveway is not to exceed 14%. 12)Please provide the tieredrockery detail, standard detail 8.10. 13)With the current spacing of the tiered rockery, there does not appear to be the minimum required spacing between each tier. Add a callout to clarify that rockery is to be constructed per COE standard detail 8.10. 14)Please add a note to the plans that all final restoration shall be completed by the contractor not the City of Edmonds. STORMWATER REPORT The following comments are provided from Robert C. Edwards, PE, Stormwater Engineer. Please contact Robert directly at 425-771-0220 or by email at robert.edwards@edmondswa.govwith any specific questions you may have regarding these comments. Page 2of 3 Stormwater Review Background This is classified as a Category 2 Small Site because it proposes impervious area exceeding 5,000 SF. Category 2 Small Site Projects are subject to Small Site Minimum Requirements 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, and 11. Minimum Requirement #1 –Preparation of Stormwater Site Plan Comments: 1.Sheet GR-01: Separate roof drains, trench drains, and catch basins from the foundation drain system. This is to prevent infiltration within the earth subsidence zone. 2.Sheet GR-01: Note 1 is for a sanitary sewer pump, but the note call out is shown on the SD system. 3.Sheet GR-01: Residential CB has insufficient cover for the 6” dia, pipe. Minimum cover requirements in landscaped areas in 1.0’. 4.Sheet Gr-01: “WALL DISCHARGE TO SURFACE OR TIE INTO SD” should be “WALL DISCHARGE TIE INTO SD” Minimum Requirement #2 –Construction Stormwater Pollution Plan Comments: None Minimum Requirement #3 –Source Control of Pollution Comments: None Minimum Requirement #4 –Preservation of Natural Drainage Systems Comments: None Minimum Requirement #5 –Onsite Stormwater Management Comments: N/A Minimum Requirement # 6 –Runoff Treatment Comments: None Minimum Requirement #7 –Flow Control Comments: N/A Minimum Requirement #8 –Wetland Protection Comments: None Minimum Requirement #9 –Operation and Maintenance Comments: None Minimum Requirement # 10 –Offsite Analysis and Mitigation Comments: None Minimum Requirement #11 –Financial Liability Comments: None Page 3of 3