Bldg Comments 1.pdfEagle Eye Consulting Engineers, P.S. PO Box 523 Olalla, WA 98359 , hoytjeter@centurytel.net 360 874 0562 Fax 360 874 0591 To: Theresa Umbaugh 121 5th Ave N Edmonds, WA 98020 Re: Weber Residence 23329 92nd Ave W Edmonds, WA 98020 Plan Review # 2008-0241 EECE # EDM 08-26 Plan review number 08 The above referenced project is in the process of plan review for compliance with Edmonds ordinances and applicable codes. The following comments, deficiencies/corrections must be addressed prior to completion of plans review and subsequent issuance of permits. Provide revised plans and calculations along with a written response to each of the items listed below to facilitate a shorter back -check time. SCOPE OF REVIEW The scope of this review is for the Ordinance, Structural, V&L4QC and Energy requirements of this project. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval. ORDINANCE COMMENTS General / i2dt// 7 kC �4 CG�•t�t.��C �a�,/,, � ✓("W 1. Please provide a roof plan for this structure. Nothing is specified at this time. Main floor 1428 Upper floor 1542 Total 2970 Garage 576 Grand total 3546 The above referenced project is in the process of plan review for compliance with Edmonds ordinances and applicable codes. The following comments, deficiencies/corrections must be addressed prior to completion of plans review and subsequent issuance of permits. Provide revised plans and calculations along with a written response to each of the items listed below to facilitate a shorter back -check time. SCOPE OF REVIEW The scope of this review is for the Ordinance, Structural, V&L4QC and Energy requirements of this project. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval. ORDINANCE COMMENTS General / i2dt// 7 kC �4 CG�•t�t.��C �a�,/,, � ✓("W 1. Please provide a roof plan for this structure. Nothing is specified at this time. Page 2 of 6 Plan Review Number 01 EECE#: EDM 08-26 Weber Residence 2008-0241 2. Please note on the drawings that the smoke alarms shall be hot-wired with battery back-up. R313.2 3. Please specify the locations of the roof drains and their required size. R 903.4 Sheet 1 Exterior Elevations 4. Please provide details for the step in the roof it is not clear on how this will be constructed. Nothing is specified at this time. 5. Please provide information for the flashing to prevent moisture from entering the wall or roof though the joints. All that is noted is flashing with out any details or information on how this will be constructed. Please modify, accordingly. Sheet 2 Main Floor Plan 6. Note minimum required finish wall material & height in the shower & bath areas. R307.2. 7. Please specify that all the penetrations through the garage to house separation wall shall be protected by filling the opening around the penetrating item with approved material to resist the free passage of flame and products of combustion. R309.1.2 S. All exterior doors shall have a minimum landing specified on the drawings including the height of the threshold. R311.4.3 9. AOR please specify the required dimension of the intermediate landing on the drawings. 8311.5.4 10. Please provide a handrail detail. R311.5.6.2. 11. Smoke alarms shall be installed outside each separate sleeping area in the immediate vicinity of the bedrooms. There shall be one placed outside bedroom #4. The one at the stairs does not meet this requirements do to the framing. R313.2 Sheet 3 Upper Floor plan 12. Please add a smoke alarm giving access to the master bedroom. One is required at this location. R313 13. Please provide a detail of the guardrail. IRC 312 and Table 301.5 14. Please specify the required light activation at the top and bottom of the stairs, per R303.6.1. Page 3 of 6 Plan Review Number 01 EECE#: EDM 08-26 Weber Residence 2008-0241 15. All rooms with closet must meet sleeping room provisions. Please add a smoke alarm in this room as required per R313. 16. Please dimension the intermediate size of the landing. R311.5.4 Sheet 5 Sections and Details 17. The stair detail specified doe not reflect what is being purposed. Please modify the drawings accordingly to show what is going to be built. For example, there is required to be an intermediated landing but this is not shown. Modify the drawings accordingly. Sheet 6 Energy and General Notes 18. AOR, please clarify on the drawing the required roof ventilations. I was unable to determine this from the drawings. The drawings are showing trusses in the details but the plans are not specify the trusses but solid sawn lumber and not showing any required ventilations. Please modify the drawings to clarify what is going to be built. R806 19. AOR, please clarify how the attic ventilations was determined. The required ventilations shall be based off the net free ventilated area. This should be specified on the drawings to assure compliance. R806.2 20. Provide attic access size & location. Details reflect attic access will be required. R807.1. STRUCTURAL COMMENTS General 21. Please reference the details to the drawings, and remove all details that do not pertain to this structure. 22. EOR, please clarify how the sub -diaphragm and diaphragm width was determined to be 24 feet. For the garage, this will be OK but not the main structures since the dimensions do not match. Please modify accordingly. 23. EOR, the wind design used a roof slope of 7 to 12. This is not the case for this roof system. The 4:12, 3:12, etc and it is not conservative to use the 7:12 for the wind analysis. A 4 to 12 is a roof angle of 20 degrees and the wind pressure is greater then used for design. Page 4 of 6 Plan Review Number 01 EECE#: EDM 08-26 Weber Residence 2008-0241 24. EOR please provide a key plan in the analysis to show which shear is for which locations. There are 4 foot high shear walls used in the analysis it is not clear where these wall are. Please modify in order to complete the review. Sheet 2 Main Floor Plan 25. Please specify the required beam to multi stud connections on the drawings. Nothing is called out at this time. 26. Please specify the required 4x6 -post connection to the 5-118X16-112 glu-lam beam. 27. EOR, please 3specify the required shear wall to be used at the great room. The hold-downs are called out but not the type shear wall. Please modify accordingly. 28. Please specify the required connections for Beam mark H to the supporting beam mark I. 29. EOR the reactions for beam "I" being supported by beams "K" specify a hanger that appears will not support the design loads. Please modify accordingly. In additions, the beam depth is 21" and the supporting beam depth is 16-112. Provide a detail at this locations 30. EOR, please specify the required hanger to use to support the 2x12 in the garage that are flush framed with the glu-lam beam. Nothing is specified at this time. 31. Please specify the required connections of the 4x6 beam at the double post. 32. Please note the shear wall to use at the great room. Hold-down is specified without the required shear wall designations. 33. Please submit analysis or the HU48TF supporting the 3-12X10-112 GLB in the family room. ,Sheet 3 Upper Floor plan 34. Please specify the required hanger to use for the 2x14 rafter being hung from the glu-lam beam. Sheet 4 Foundation Plan 35. EOR, please submit analysis or no reinforcement for the footing mark Q. 36. EOR, please submit analysis for the 3'X5X15 footing located at the garage and house wall Page 5 of 6 Plan Review Number 01 EECE#: EDM 08-26 Weber Residence 2008-0241 37. FOR, please specify the required connections of the header 4x8 to the supporting studs/post. Sheet 5 Sections and Details 38. Detail F: Please the required connections of the stair stringer at the top. Nothing is specified at this time. 39. Detail F: Please specify he required connection of the 4x6 support to the stair stringer. Nothing is specified at this time. 40. Detail A: EOR submit analysis for the studs spaced @ 18" OIC noted in the details. 41. Please note the vertical steel into the footing shall have a 90 -degree hook. R403.1.3 42. Detail B: FOR please submit analysis for the retaining wall. None was in the package submitted. IBC 1806 43. Detail D: Provide information for the Concrete nails noted in this detail. More information is required in order to complete the review. Sheet 6 Energy and General Notes 44. Modify you typical detail to reflect the roof system that is purposed. Trusses are not specified on the roof plan. Modify the drawings accordingly. 45. Framing Notes 7: Please clarify what a big beam is to be in order to assure the correct stresses are used. Big beam is a relative term. Sheet S-2.0 Structural Notes 46. Detail 3: FOR please specify the required ledger connections with analysis to support the rafter. ENERGY Prescriptive method Used No comment at this time VENTILATION & INDOOR AIR QUALTY CONTROL General Page 6 of 6 Plan Review Number 01 EECE#: EDM 08-26 Weber Residence 2008-0241 47. Please correct the ventilation work sheet. The office spaced on the upper floor is considered a bedroom and must be considered when determining the whole house exhaust fan size. Please correct accordingly. Sheet 3 Upper Floor plan 48. Please clarify on the drawings how the laundry room exhaust fan will terminated to the exterior of the building. WSV&IAQC 303.4.1.4 Sheet 6 Energy and General Notes 49. Modify the ventilations table to match the square footage. 50. The number a bedrooms for this structure is not a 4 bedroom but a 5 bedroom. All rooms with closet must be considered a sleeping room for code compliance. Please modify accordingly. Additional corrections may be required following receipt of corrections and additional information as requested. Your plans are being reviewed concurrently with the Building Department, Fire Department, Zoning Department and Public Works Engineering. Changes, clarifications or additional corrections may be required subsequent to the Building Department plan review when comments are received from the other concerned departments. Should you have any inquiries regarding this letter, please contact Hoyt Jeter at (360) 874- 0562 between 8:00 a.m. and 5:00 p.m. In Hoyt Jeter, P.E. President exc�v�h� •mob a� � '�' �' 3 /wo8. %ova dcc r,E-e�c•� Gam/ // y Property Owner Name #B57 Property Address SAMPLE PLOT PLAN Tax Account Parcel # Scale. 1"=20` +13 4+109 IMPERVIOUS SURFACE CALCS (SOLID SURFACES) +106 `08. Exist_ Building Roof Outline: 2200 A. (constr. in 1962) Existing Covered Porch: 75 sf. (constructed in 1962) +104 -- " Existing Driveway. 610 st: (constructed in 1987) ' +102I - Existing Patio: 200 sf. (constructed in 1985) +100 Proposed Addition: 440 sf. aA; Proposed Garage: 500 sf. g Proposed Deck: 90 A. +98 HEIGHT CALCS A +99' 1 �` B=+107' C=+100' D=+105' I $ -0 c, -- — w ---- 2 I AVE GRADE _ 102.75' �,� x � - - . -• B ACTUAL = 123' �� +99,r :+107 I MAXIMUM[ = 127.75' 1 � J, 1 1 � I Existing Rockery I - , - 1 1 Existing oW, , 1 LOT COVERAGE: r 25'-0" Exist n 351s sQ.FT. (26%) Residence t, ° 1 c, Yatioi 2000 sq -ft.. I co LOT AREA _ 13,527 SQ.F'T. I , LOT SLOPE: 11%- oI CV I Z eq -t , j i a Covered Porch I existing , [] U x ; - Grade - 15� Contours 1 �� ,N I { C i DI �'� FU1 +'100' � - - L � ------ -j i Existing y Asphalt I Property Line I I i Driveway' I Slope 6 � - I� I 100' r9g Si'dewatk, ], ]- FH Water Meter Q. ��! M MAIN STREET 'telephone Pole Revised 7107 DATUM PT- +100' Center of Right -of -Way Top of S5 Manhole Cover � L.0x pL%building�hmd°ut,addfbonpaLVSd7,oa — — — � — —ATTACHMENT A Revised 7107 PLOT PLAN CHECKLIST It is the owner/applicant's responsibility to submit a true and accurate plot plan to the City for review. ❑ Property owner's name, tax account parcel number and street address. ❑ Plan Scaled 1 "=20', with North arrow designation. ❑ Streets, approaches, driveways, sidewalks, alleys, easements (public and private), paved areas, street dedications and adjacent City right- of-way (developed or undeveloped). Show all dimensions. ❑ Side sewer stub location and proposed sewer lines, water meter location, water service line location, gas, cable and phone lines, fire hydrants, telephone poles, utility transformers. ❑ Existing physical features and water courses of any size (i.e., streams creeks, ponds, ditches, etc.). ❑ Dimension all buildings and structures (label existing or proposed), indicate setback distances, lot area and lot coverage. ❑ Accessory structures and projections; decks, porches, hot tubs, pools, cantilevered structures, bay windows, chimneys, roof overhangs, eave lines, breezeways, patios, sheds, pool mechanical rooms, etc. ❑ Retaining wall or rockery location (for retaining walls provide typical section detail). (See Handout #B62) ❑. Fences existing and proposed. (See Handout #B31 ❑ Building height calculations, average grade, actual height, maximum allowed height (See Handout #B41). Datum point (benchmark) must be located off-site (i.e. top of sewer manhole lid, top of fire hydrant, mark on telephone pole, etc.). Indicate lowest footing or slab elevation. ❑ Elevation grades at the property corners. Topographic grades to be shown at two foot intervals across the lot. Indicate lot slope and driveway slope. (See Handout 037) ❑ Existing impervious area calculations (Pre and Post July 1977) and new proposed impervious area calculation. See Handout #E72 Revised 7/07