Loading...
Bldg Comments 1.pdfCity of Edmonds i )?t PLAN REVIEW COMMENTS BUILDING DIVISION Fsr: ts9� (425)771-0220 DATE: March 5, 2008 TO: Dwight McGrew FAX: 425-778-9086 FROM: Ann Bullis, Assistant Building Official RE: Plan Check 4 2008-0031 Project: Michel 7 Unit Condominium Project Address: 316 Walnut Street Below are combined comments from the City's plan review consultant and myself. Provide written responses to each comment and where changes can be found on the plans. Please resubmit to Theresa Umbaugh, Permit Coordinator. 1. Sheet P1: a. Notes 16, 17, 18: Provide separate total floor areas for the building floor area, decks and patios. b. Note 19: State the actual type of mechanical system proposed (ie. force air furnace, hydropic (in floor, radiant wall units), etc.). c. Note 21: Based on the floor areas noted on this sheet, the occupant load of the basement floor should be 32 (both parking and residential have a factor of 200) — IBC Table 1004.1. 15t floor should be 30 including decks, 2nd floor should be 32, 3`d floor should be 30. Please revise. d. Note 41: Revised ICC/ANSI Al 17 edition to 2003 instead of 1998. e,. Note 43: See below for list of required special inspections. f. Note 44: List separate permits and deferred submittals for this project so that it is clear what work will be issued under this permit. Common items are plumbing, mechanical, fire sprinkler, fire alarm, State electrical, State elevator, listed and tested firestopping assemblies, shop drawings (truss cut sheets and layout, I joist layout, etc.), etc. g. Note 46: Revise to note requirements of firestopping per IBC 712. 2. Sheet A2: a. Revise Ul occupancy noted at floor areas to S2 (or remove occupancy reference). b. Clarify plans to show location and extent of interior garage walls. c. Label the long gray rectangles and large squares on the plan. d. Dimension the accessible parking stall (minimum 8'-0" wide stall with 5'-0" adjacent access aisle that runs the full length of the stall). The column between the stall and access aisle obstructs use of the access aisle. Vehicles have different types of access requirements, therefore the column cannot obstruct access to the 5'-0" access aisle. e. Dimension the finished clear width of the corridor. f. Dimension the clear width of the stairway and landings. g. Dimension minimum 18" accessible maneuvering clearance on the push side of the door to the access aisle. h. Show/dimension 12" minimum top and bottom handrail extensions (except where handrail is continuous). L Note the stairway rise and run. Detail N/A13 notes that it is per plan, but nothing is provided. It might be on the stair notes on the floor plans, but is cut off. j. Change R1 reference to R2 at the corridor. k. Clarify that the 30 minute rating of the corridor applies to the corridor/sprinkler room wall only since VA construction and 1 -hour fire barriers will require 1 -hour rated assemblies elsewhere. 1. Revise doors from garage to the corridor so they meet doors in series requirement of ICC/ANSI A117.1404.2.5. m. Although mechanical ventilation may be deferred, make provision for ventilation (supply and exhaust/return) to the corridor (VIAQ 304 and Table 3-4). n. Clearly show/note that the 1 -hour fire barrier walls (elevator shaft, stair enclosure and occupancy separation between R2 and S2) must extend to the underside of the floor sheathing above. 3. Provide story calculations to justify the lower floor as a basement (see definitions of basement (WAC 51-50 502) and grade plane (IBC 502)). This building was reviewed as a 3 -story with basement — not a 4 -story building. If it cannot qualify as a 3 -story with basement, a redesign to meet additional 4 -story requirements is required. 4. Explain symbol "fire detector interconnected" on the floor plans notes and show where it applies. 5. Add symbol for steel column to the floor plan legend and cross reference fire rated assembly for steel columns. 6. Revise "overall building dimension" note on floor plan notes to match this building. 7. Revise floor plan note regarding headroom to 7'-6" (see IBC 1003.2 for means of egress) 8. Provide listed and tested assembly detail for the steel fire barrier wall and cross-reference on the plans. 9. Revise label of I/A14 to note S2 and R2 occupancies only. 10. Revise label of J/A14 to note applicable separations as they are used on the plans. 11. Detail B/A14: NER-200 is no longer a valid report. Provide new listed and tested assembly (such as from the Evaluation Report from the joist manufacturer, from the Gypsum Fire Resistance Design Manual, etc.). If you are using M/A15 for sound, make sure it coordinates with the minimum requirements for the fire rated assembly. 12. For decks, provide a detail showing how the fire resistive materials will be protected from the weather. 13. On detail G/A15, cross-reference the correct details. 14. Provide illuminated exit signs for second required exit to stair enclosure, including one over door from garage to corridor, and one from corridor to stair enclosure. 15. Dimension the finished clear width of the corridor. 16. Dimension the clear width of the stairway and landings 17. East stair enclosure must be 2 -hour rated since it serves 4 stories (IBC 1020.1 and WAC 51-50 502 definition of story and basement). Doors must be 90 minute rated. Page 2 of 7 18. The elevator shaft must be 2 -hour rated since it connects 4 stories (IBC 707.4 and WAC 51-50 502 definition of story and basement). Hoistway doors or additional doors must be 90 minute rated. 19. Center stair enclosure must exit directly to the outside or to a 1 -hour exit passageway. Revise 1 S� floor plan to show 1 -hour exit passageway. The exit passageway must have a 1 -hour fire rated floor -ceiling assembly with no ducts penetrating the assembly above the ceiling sheetrock (this is different than what is allowed for corridors). A redesign is required for the exhaust ducts for unit 102 if it is part of the exit passageway. Exit passageway walls are fire barrier walls and are required to extend to the underside of the floor sheathing above. Provide detail and notes to show this requirement. 20. Dimension 12" minimum maneuvering distance on the push -side of the south lobby door. 21. An accessible means of egress is required for each required exit. The general sprinkler exception is no longer in the code. See IBC 1007 please read the entire section. 22. Exit doors for each dwelling on the 2nd and 3rd floors must be spaced apart 1/3 the overall diagonal dimension of the area served (dwelling unit including deck). Show the overall diagonal dimension and distance between exits. IBC 1015.2.1. 23. Site plan shows 3' rail fence in the right-of-way. Please relocate to private property. 24. On the site plan, show the line of the 5 foot wood fence (where it starts and stops). It is existing or proposed? 25. Provide construction details for proposed fences. 26. Since the 4th Avenue entrance to the building is not accessible, provide directional signage from the base of the stairs directing occupants to the Walnut Street entrance. 27. Provide updated Prescriptive Option energy compliance form (the one submitted is outdated), and revise U and R -values on plans as needed to meet the option you select. Also, revise Notes 23 and 24 on Sheet P 1 accordingly. 28. Complete the enclosed Interior and Exterior Lighting Summary forms. Interior areas to be included are the common areas and parking areas. WSEC 1530 29. Building enclosure letter: The design professional must submit a written statement stamped/signed that "The undersigned has provided building enclosure documents that in my professional judgment are appropriate to satisfy the requirements of RCW 64.55.005 through 64.55.090" 30. A barrier gate is required at the first floor at the top of the stair to the garage to prevent occupants from exiting into the garage. (IBC 1020.1.5) 31. Stairway floor number signs are required in the east stairway (IBC 1020.1.6). 32. Dimension the required landings at exterior doors. 33. Provide a sign at the elevator to read: IN FIRE EMERGENCY, DO NOT USE ELEVATOR. USE EXIT STAIRS. (IBC 3002.3) 34. Provide a temporary shoring plan with structural calculations and details stamped and signed by a State Licensed Professional Engineer. Where slopes of 1:1 will be made instead of shoring, clearly show this on the plan as well. 35. The Engineer of Record must provide a Statement of Special Inspections on the plans in accordance with IBC 1705. 36. General Contractor is required to provide a letter acknowledging contractor responsibility in accordance with IBC 1706. 37. Special inspections are required for: By Geotechnical Engineer of Record: a. Excavation, grading and site preparation, including backfill of foundation walls Page 3 of 7 b. Shoring installation and monitoring c. Soil bearing verification d. Foundation drainage e. Final letter from. the Geotechnical Engineer of Record By WABO Special Inspector or State Licensed Professional Engineer £ Concrete g. Structural Steel Construction h. Wood Construction, including shear walls (nailing 4" o.c. or less), wood diaphragms, drag struts, and holdowns. i. Welding Complete the enclosed Special Inspection and Testing Agreement, have all parties sign and return for City approval. One form is required for each special inspection firm. ORDINANCE COMMENTS 38. Please clarify how the garage floor will be sloped for drainage as required per IBC 406.2.6 39. Some of the notes and details have the text cut off/overlapped and is unreadable. Please adjust accordingly. IBC 106.1.1 STRUCTURAL COMMENTS General 40. Geotechnical engineer please submit a plot showing the location of test borings and/or excavations as required for geotechnical reports. IBC 1806.2 41. EOR, please provide a break down of the dead weight of the floors to equal 15 psf. The drawings state 1-1/2 gyp-crete. The dead weight of this alone 13 psf C/4" gyp-crete =6.5 pso. This leaves only 2 psf for the plywood, joist, gypsum ceiling. The dead weight will exceed the 15 psf used in the design. Please resubmit lateral and gravity design for the dead load of this structures or justify the 15 psf dead used. (Note Appendix A for Structural Dead Weights noted in the analysis was not included.) Sheet AT Foundation Plan 42. EOR, please clarify the required size and reinforcement for the foundations under the 4' high concrete wall. The key does not specify the required size. 43. EOR, please specify the required reinforcement for the thicken slab noted on this sheet. It is not clear what will be used to support the design forces. 44. EOR please provide a detail how the 7.5X7.5 footing and the elevator pit footing will be constructed. These overlap and a detail is required to show how this will be constructed in order to complete the review. 45. EOR, please specify the required footing size supporting the column at the perimeter wall. The drawings show a footing extending in under the slab but it is not clear neither the size Page 4 of 7 nor the required reinforce. Also the post is not centered on the footing and analysis is required to show the forces will be supported to not exceed the design loads. Sheet A14: Details & Sections 46. Detail X: EOR please provide analysis for the Rockery retaining wall to resist the soil induced forces. With a sloped back fill analysis is required. The geotechnical report prepared by Dennis Bruce has not dealt with this nor was there any analysis submitted for the rockery retaining wall. 47. Detail M, N and O: There is not information on the drawing the spacing of the post or the required connection to show the code required forces will be resisted. Please add this information to the drawings in order to check the structural requirements. IBC 1607.7 48. Detail M, N and O: The notes for the infill glazing are not correct per the adopted code. The in -fills glass panel shall be design to resist a live load of 50psf Please modify accordingly and submit analysis to justify. IBC 1607.7.1.2 (Note the 200 pounds is specific for the top rail per IBC 1607.7.1.1) Sheet S 1: Structural Notes 49. EOR, the code does not allow 2 x members to be used when nail spacing is spaced at 2" OIC. The code requires the nails to be staggered and a minimum of 3X shall be used. The schedule does not reflect this for shear wall mark SW5 and SW8. Please modify accordingly. IBC table 2306.4.1 footnote e Sheet S2: Structural Details No comment for this sheet at this time Sheet 5-2.1: Structural Details 50. EOR, please specify the required connection of the W10X30 to the concrete wall. This sheet state use "2/5-2.2 TYP" but this is not for the connections to a concrete wall. Please modify accordingly. 51. EOR, please add to the drawing the grid lines. This detail state typical elevation of grid B shown but the plans does not have any grid lines specified. Please modify accordingly. Sheet 5-2.2: Structural Details 52, Detail 2B: Submit justification for the use of ITT311.88 does not require to having backing. This hanger is not in the hanger matrix options and backing helps prevent hanger rotations. Please provide this information upon response or add backing blocking members. 53. Detail 2B: EOR, nailer on top of wide flange are not approved to over hanger to flange. Based off the beam size and the flange width the nailer will over hanger 1.374" and the maximum even recommend is .25". Simpson C-2008 page 80 wood nailers (This is also in the 2007 but page 92). Simpson phone number 1-800-999-5099. Page 5 of 7 54. Detail 1, 2 4 and 5: EOR, please specify the required thickness of the shear tab connections for the wide flange beams to the columns. I was unable to determine this from the submitted drawings. Please clarify where this information is specified or add to the details accordingly. 55. Detail 4: EOR please clarify the notes ref to detail 7/S2 for the connections. Detail 7 on this sheet is for the header beam and joist framing into it. Not the required red iron steel connections. Please modify in order to complete the review. Sheet S-2.3: Structural Details 56. Detail 2A: EOR provide documentation for the joist manufacture that blocking is not required for the hanger. The details show the hanger being held away from the wall. Please modify accordingly. 57. Detail 3: EOR, please clarify where this detail is referenced to the drawings in order to review for code compliance. I could not determine this based off the drawings. Sheet S-3: Foundation Plan 58. EOR, please specify the required connection of the 7X11-7/8 to beam mark #47. It was not clear what would be used. 59. EOR, please provide a detail for the connection of the 3.5X 11-718 PSL to the HSS 5X5X1/4 where beam BM #38 and Beam # 39 intersect the HSS column. 60. EOR please provide the required foundations and wall reinforcement for the elevator pit. There was not any information shown how this will be constructed not any analysis for this. Please add this information when responding. 61. EOR please provide a detail and analysis for the connections of the BM #50 to the concrete wall. There is a detail 1/S2-2 similar but this does not show this connections. Please clarify and modify accordingly. Sheet S-4: 1" Floor Shear Walls 62. EOR, please provide a detail for the connection of the deck joist to the main structures. It was not clear how this will be connected. 63. EOR, please specify the required connection of the deck ledger to the main structure. IBC 1604.8.3 Sheet S-5: 2nd Floor Shear Walls 64. Please provide detail for the construction of the deck at this level. TH 360 can not be used for exterior use. 65. EOR please provide detail for the required connection of the W 10X19 beams specified on this sheet. Sheet S-6 3rd Floor Shear Walls Page 6 of 66. EOR please provide detail and analysis for the connection of the truss to the supporting steel members. The code requires the design professional to specify this on the drawings. IBC 2303.4.1.6 67. EOR, please provide a detail for the connection of the W1 8X28 down and W12X19 up as shown on this sheet. 68. EOR, please specify the required connection of the glu-lam beam to the supporting post. It was not clear how this will be connected based off the drawings. All that is noted is detail 2/S-2 but this is for the shear wall. Please modify accordingly. 69. EOR, please specify the required anchorage of the trusses on the drawing. I was unable to determine where this information was clearly specified on each side of the trusses. IBC 2303.4.1.6 Page 7 of 7 of E�'o City of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION �Sr. s 890 (425) 771-0220 DATE: March 5, 2008 TO: Ken Larson ken@ken-larson.com FROM: Jenny Readwin, Plans Examiner RE: Plan Check # 2008-0155 Project: Suasand Deck Project Address: 111 lf' Ave N. During review of the above noted application, it was found that the following information, corrections, or clarifications are needed. Please redline plans or submit two (2) sets of revised plans/documents (affected sheets only) with a written response to each of the items below to a Permit Coordinator. 1) On the framing plans please show footings under each post to clearly show how all loads are carried to bearing. 2) It is unclear to me how the upper landing and the lower deck are laid out. Please clearly show stairs and if possible put both landings on the same page to see how they overlap or connect. 3) Joists sistered to the side of the posts does not meet conventional construction. To meet conventional construction show beam on top of post or provide calculations from a Washington State Licensed Professional Engineer to justify. 4) For the upper floor landing it is not clear how all loads are supported. The double joists are running the same direction as the floor joists. Please clearly show all posts and beams to verify spans and that all loads are being carried to bearing. 5) How will the deck be supported at the house? If ledger show size, as well as fastener type, size and spacing. 6) Pier blocks do not meet conventional construction. Replace with poured concrete footings or provide calculations from a Washington State Licensed Professional Engineer to justify. 7) On the framing plan show how the stairs are supported on the lower deck. 2006 WSEC Chapter 6 Qualification Form- Zone I Residential Prescriptive (Chapter 6) Options For All Heat Sources Instructions: Carefully review the requirements for each of the options below_ Choose an option that best suits your dwelling design_ GIazing percentage typically Jetermines which option to choose. Your building must match the selected option requirements without exceptions or substitutions_ Disregard components or _quipment that does not apply to your project. Your permit will be processed more efficiently if you provide all of the requested information. Department staff -an help you with general questions about this form. Proposed designs which cannot meet the specific requirements of a listed option above may calculate -ompliance by Chapter 4 or 5 of the 2006 Washington State Energy Code_ Forms can be found on the WED at WW W_ENERGY.WSU.EDU tcelerence ease 0_ Nominal R -values are for wood frame assemblies only or assemblies built in accordance with Section 601.1_ I . Minimum requirements for each option listed. For example, if a proposed design has a glazing ratio to the conditioned floor area of 13% it shall comply with all of the requirements of the 15% glazing option (or higher). Proposed design which cannot meet the specific requirement of a listed option above may calculate compliance by Chapter 4 or 5 of this Code_ 2_ Requirements applies to all ceilings except single rafter or joist vaulted ceilings complying with note 3. `Adv' denotes Advanced Framed Ceiling. 3. Requirement applicable only to single rafter or joist vaulted ceilings where both (a) the distance between the top of the ceiling and the underside of the roof sheathing is less than 12 inches and (b) there is a minimum I -inch vented airspace above the insulation. Other single rafter or joist vaulted ceilings shall comply with the "ceiling" requirements. This option is limited to 500 square feet of ceiling area for one dwelling unit. 4_ Below grade walls shall be insulated either on the exterior to a minimum level of R-10, or on the interior to the same level as wall above grade. Exterior insulation installed on below grade walls shall be a water resistant material, manufactured for its intended use, and installed according to the manufacturer's specifications. See Section 602.2 5. Floors over crawl space or exposed to ambient air conditions - 6_ Required slab perimeter insulation shalt be a water resistant material, manufactured for its intended use, and installed according to manufacturer's specifications. See Section 602.4. 7_ Int_ denotes standard framing 16 inches on center with headers insulated with a minimum of R-10 insulation_ 8_ This wall insulation requirement denotes R-19 wall cavity insulation plus R-5 foam sheathing. 9. Doors, including all Eire doors, shall be assigned default U -factors from Table 10-6C 10. Where maximum glazing area is listed, the total glazing area (combined vertical plus overhead) as a percent of gross conditioned floor area shall be less than or equal to that value_ Overhead glazing with U -factor of U=0.40 or less is not included in glazing area limitations. 11. Overhead glazing shall have U -factors determined in accordance with NFRC 100 or as specified in Section 502.1.5- 12_ Log and solid timber walls with a mmimum average thickness of 3.5" are exempt from this insulation requirement. This project will take advantage of the following exceptions to the prescriptive option: 0 602.6 Exception 1. One door, that is 24 sq ft or less, that does not meet the standards is allowed. Location of door taking this exemption: 0 602.5 Exception 2. Doors with U -factor of 0.40 allowed without calculations, Option IV only. Location ofdoor(s) taking this exemption_ Glazing U -Factor Option Glazing Area10 Vertical Overhead " Door 9 U- Ceiling z Vaulted 3 Wall Above Wa114 int Wal 14 ext Floors Stab on % Of Floor Factor Ceiling Grade12 Below Below Gab Grade Grade 1 10% 0.32 0.58 0.2 R-38 R-30 R -I5 R-15 R-10 R-30 R-10 If* 15% 0.35 0.58 0.2 R-38 R-30 R-21 R-21 R -I0 R-30 R-10 25% Group R- I III and R-2 0.4 0.58 0.2 R-381 R-301 R-21/ R-15 R-10 R-30/ R-10 Occupancies U=0.031 U=0.034 U=0.057 U=0.029 Only Unlimited Group R-3 and IV R-4 0.35 0.58 0.2 R-38 R-30 R-21 R-21 R-10 R-30 R-10 Occupancies Only Unlimited Group R -I and VR -2 0.35 0.58 0.2 R-38 R-30/ R-211 R-15 R-10 R-301 R-10 s Occupancies /U=0.034 U=0.034 U=0.057 U=0.029 ---Only tcelerence ease 0_ Nominal R -values are for wood frame assemblies only or assemblies built in accordance with Section 601.1_ I . Minimum requirements for each option listed. For example, if a proposed design has a glazing ratio to the conditioned floor area of 13% it shall comply with all of the requirements of the 15% glazing option (or higher). Proposed design which cannot meet the specific requirement of a listed option above may calculate compliance by Chapter 4 or 5 of this Code_ 2_ Requirements applies to all ceilings except single rafter or joist vaulted ceilings complying with note 3. `Adv' denotes Advanced Framed Ceiling. 3. Requirement applicable only to single rafter or joist vaulted ceilings where both (a) the distance between the top of the ceiling and the underside of the roof sheathing is less than 12 inches and (b) there is a minimum I -inch vented airspace above the insulation. Other single rafter or joist vaulted ceilings shall comply with the "ceiling" requirements. This option is limited to 500 square feet of ceiling area for one dwelling unit. 4_ Below grade walls shall be insulated either on the exterior to a minimum level of R-10, or on the interior to the same level as wall above grade. Exterior insulation installed on below grade walls shall be a water resistant material, manufactured for its intended use, and installed according to the manufacturer's specifications. See Section 602.2 5. Floors over crawl space or exposed to ambient air conditions - 6_ Required slab perimeter insulation shalt be a water resistant material, manufactured for its intended use, and installed according to manufacturer's specifications. See Section 602.4. 7_ Int_ denotes standard framing 16 inches on center with headers insulated with a minimum of R-10 insulation_ 8_ This wall insulation requirement denotes R-19 wall cavity insulation plus R-5 foam sheathing. 9. Doors, including all Eire doors, shall be assigned default U -factors from Table 10-6C 10. Where maximum glazing area is listed, the total glazing area (combined vertical plus overhead) as a percent of gross conditioned floor area shall be less than or equal to that value_ Overhead glazing with U -factor of U=0.40 or less is not included in glazing area limitations. 11. Overhead glazing shall have U -factors determined in accordance with NFRC 100 or as specified in Section 502.1.5- 12_ Log and solid timber walls with a mmimum average thickness of 3.5" are exempt from this insulation requirement. This project will take advantage of the following exceptions to the prescriptive option: 0 602.6 Exception 1. One door, that is 24 sq ft or less, that does not meet the standards is allowed. Location of door taking this exemption: 0 602.5 Exception 2. Doors with U -factor of 0.40 allowed without calculations, Option IV only. Location ofdoor(s) taking this exemption_ 2006 Washington State Nonresidential Energy Code Compliance Form Interior i • Summary LTG -INT 2006 WasW=Wn slate Ntonresidentiai Enemy Code ConwiWnce Forms RMEW JUly2007 Project Info Project Address Date For Building Department Use Applicant Name: _ Applicant Address: Applicant Phone: Project Description ❑ New Building ❑ Addition ❑ Alteration ❑ Plans Included Refer to WSEC Section 1513 for controls and commissioning requirements. Compliance Option Q Prescriptive a Lighting Power Allowance Q Systems Analysis (gee Qualification Checklist (over). Indicate Prescriptive & LPA spaces clearly on plans.) Alteration Exceptions (check appropriate box -sec. 1132.3) ❑ No changes are being made to the lighting ❑ Less than 60% of the fixtures new, installed wattage not increased, & space use not changed. Maximum Allowed Lighting Wattage Location (floor/room no.) Occupancy Description Allowed Waw per R2 •` Area in fe Allowed x Area -- rrom i ante i5-1 tavert - aocument au exceptions on roan L I U -LVA I Mai Hiloweu Waasl - 'Proposed Lighting Wattage Location Number of (floodroom no.) Fixture Description Fixtures Watts/ Watts Fixture Proposed Total Proposed Watts may not exceed TOW Allowed Watts for Interior Total Proposed Watts Notes: t. For proposed Fixture Description, indicate fixture type, lamp type (e.g- T -S), number of lamps in the fixture, and ballast type (if included). For track lighting, list the length of the track (in feet) in addition to the fixture, lamp, and ballast information. 2. For pfoposed Watts[ fixture, use manufacturer's listed maximum input wattage of the fixture (not simply the lamp wattage) and other criteria as specified in Section 1530- For hard -wired ballasts only, the default table in the NREC Technical Reference Manual may also be used. For track lighting, list the greater of actual luminaire wattage or length of track multiplied by 50, or as applicable, the wattage of current limiting devices or of the transformer. 3. List all fixtures. For exempt lighting; note section and exception number, and leave Wattsl'Fixture blank. ATTACHMENT A 2006 Washington State Nonresidential Energy Code Compliance f=orm Monresidentlal Energy Code Compliance Forms Prescriptive Spaces Occupancy: Q Warehouses, storage areas or aircraft storage hangers QOther Qualification Checklist Lighting L] Check if 95% or more of fixtures comply with 1,2 or 3 and rest are ballasted. Note: If occupancy type Is "Other" and fixture answer is checked, the number of Fixtures: (Section 1. Fluorescent fixtures which are non -lensed with a) 1 or 2 two lamps, b) reflector fixtures in the spare is not limited by Code. 1521) or louvers, c) 5-60 watt t-1, T-2. T-4, T-5, T-8 lamps, and d) hard -wired elec- Clearfy Indicate these spaces on plans. If 1.2 tronic dimming ballasts_ Screw-in compact fluorescent fixtures do not qualify_ not qualified, do LPA Calculations. Cafeterias, fast food establishments . restaurantsibarss 2_ Metal Halide with a) reflector b) ceramic MH lamps - 150w c) electronic ballasts Post office 1.1 3. LED lights. 'rAal C A=_A I IniF I ; 11,01nZ3^*--e 11 PAI Use I.PA !s Use LPA Wls Automotive facility 0.9 Office buildings, officeladministrative areas in facilities of other use types (including but not limited to schools, hospitals, institutions, museums, banks, churches 5,7.11 1.0 Convention center 12 1 Penitentiary and other Group 1-3 Occupancies 1.0 Courthouse 1.2 1 Police and fire stations 1.0 Cafeterias, fast food establishments . restaurantsibarss 1.3 Post office 1.1 Dormitory 1.0 Retail'u, retail banking, mall concourses, wholesale stores(pallet rack shelving) 1.5 Exercise center 1.0 School buildings (Group E Occupancy only), school classrooms, day care centers 1.2 GymnasiaGymnasiZ assembly spaces' 1.0 Theater, motion picture 1.2 Health care clinic 1.0 theater, performing arts 1.6 Hospital, nursing homes, and other Group 1-1 and 1-2 Occupancies 1.2 transportation 1.0 Hotellmotel 1.0 Warehouses", storage areas 0.5 Hotel ban uet/conferencatexhibifion hall ' 2.0 Workshops 1.4 Laboratory spaces (all spaces not classified "laboratory" shall meet office and other appropriate categories) 1.8 Parking garages o.2 Laundries 1,2 Lbraries 1.3 Flans Submitted for Common Areas Only' Manufacturing facility 1.3 Main floor buildinglobbies exce t mail concourses 1.2 Museum 1.1 Common areas, corridors, toilet facilities and washrooms, elevator lobbies 0.8 footnotes Tor t anie nS-,t 1) In cases in which a general use and a specific use are listed, the specific use shall apply. In cases in which a use Is not mentioned specifically, the Unit Power Allowance shall be determined by the building official. This determination shall be based upon the most comparable use specified in the table. See Section 1512 for exempt areas. 2) The watts per square foot may be increased, by two percent per foot of ceiling height above twenty feet, unless specifically directed otherwise by subsequent footnotes. .3) Watts per square foot of room may be increased by two percent per foot of ceiling height above twelve feet. 4) For all other spaces, such as seating and common areas, use the Unit Light Power Allowance for assembly. 5) Watts per square foot of room may be increased by two percent per foot of ceiling height above nine feet. 6) Reserved. 7) For conference rooms and offices less than 150fe with full height partitions, a Unit Lighting Power Allowance of 1.10 wife may be used. 8) Reserved. :9) For indoor sport tournament courts with adjacent spectator seating over 5.000, the Unit Lighting Power Allowance for the court area is 2.60 Wife. 10) Display window illumination installed within 2 feet of the window, provided that the display window is separated from the retail space by walls or at least three -quarter -height partitions (transparent or opaque). and lighting for free-standing display where the lighting moves With the display are exempt. An additional 1.5 wife of merchandise display luminaires are exempt provided that they comply with all three of the following: a) located on ceiling -mounted track or directly an or recessed Into the ceiling itself (not on the wall). b) adjustable in both the horizontal and vertical axes (vertical axis only is acceptable for fluorescent and other fixtures with two points of track attachment). c) fitted with LED, tungsten halogen, fluorescent, or high intensity discharge lamps. This additional lighting power is allowed only if the lighting is actually installed. 11) Provided that a -floor plan, indicating rack location and height, is submitted, the square footage for a warehouse may be defined, for computing the interior Unit Lighting Power Allowance, as the floor area not covered by racks plus the vertical face area (access side only) of the racks. The freight allowance defined in footnote 2 applies only to the floor area not covered by racks. 2006 Washington State Nonresidential Enerqv Code Compliance Form Julv2W7 Project Info Proj Addres -. ._ _ _- -. Date - For Building Department Use Name. Appl. Name Appl. Phone,. Project Description ❑ New ❑ Addltion ❑ Alteration ❑ plans Included Refer to WSEC Section 1513 for controls and commissioning requirements. Compliance Option O Lighting Power Allowance 0 Systems Analysis Building Grounds (luminaires > 100 Watts) ❑ Efficacy > 60 lumenslW ❑ Controlled by motion Sensor ❑ Exemption (fist) Alteration Exceptions (check appropriate box -see. 1132.3) ❑ No changes are being made to the lighting L-1 Lew than 60°!v of the fixtures new, installed wafta a not increased, & s ce use not changed. Tradable Maximum Allowed Lizhtinz Wattaze Tradable Locations Allowed Watts Area (ft), perimeter Description per ft2 or per if (If) or # of items Allowed Waifs x il? (or x if) 1 otat PJIOwep vans l I Use mfgr listed maximum input wattage. For fixtures with hard -wired ballasts only, Tradable Proposed Lighting Wattage the default table in the NREC Technical Reference Manual may also be used. Numberof Location Fixture Description Fixtures Wattsl Fixture Watts Proposed 1 utdt rrupu5CU vvatE5 may nqi exceed i otai Atiowea waits Tor menor I otal t-roposed Watts) :Non -Tradable Maximum Allowed Lighting Wattage Allowed Watts Non Tradable Locations Description per ft2 or per If Area (ft), perimeter (10 or ## of items Allowed Watts x fe (or x If) Non -Tradable Proposed Lighfing Wattage Location Number of Fixture Description Fixtures Watts/ Watts Fixture Proposed rrupuseo vvaus ntdy not exceed Attoweu vvaas Tor i alegory ATTACHMENT B 2006 Washington State Nonresidential Energy Code Compliance Form 'Exterior• • Summary (back) LTG -EXT: 2006 Washington State NonrestdentIM Energy Code Compliance Forrns Revised July 2007 TABLE 15-2 LIGHTING POWER DENSITIES FOR BUILDING EXTERIORS Tradable Surfaces Uncovered Parking Areas Parking lots and drives 0.15 W!ft (Lighting power densities for uncovered Building Grounds parking areas, building Walkways less than 10 feet wide lA W/iinear foot -grounds, building entrances and exits, canopies and overhangs Walkways 10 feet wide or greater Plaza areas 0.2W/ and outdoor sales areas Special feature areas may be traded.) Stairways 1.0 W/ Building Entrances and Exits Main entries 30 W/linear foot of door width Other doors 20 W/linear foot of door width Canopies and Overhangs Canopies (free standing and attached and 1.25 W! overhan s Outdoor Sales Open areas (including vehicle sales lots) 0.5 W/fe Street frontage for vehicle sales lots in addition to "open area" allowance 20 W/linear foot .Non -Tradable Building Facades 0.2 W/ft for each illuminated wall or Surfaces (Lighting surface or 5.OW/linear foot for each power density illuminated wall or surface length Automated teller machines and night 270 W per location plus 90 W per calculations for the following applications depositories additional ATM per location can be used only for the specific application and cannot be traded between surfaces or with other exterior lighting. The following allowances are in addition to any allowance otherwise permitted in the Entrances and gatehouse inspection stations at guarded facilities 1.25 W/fe of uncovered area (covered areas are included in the "Canopies and Overhangs" section of "Tradable Sm,�c�„ Loading areas for law enforcement, fire, ambulance and other emergency service vehicles 0.5 Wlifx of uncovered area (covered areas are included in the "Canopies and Overhangs" section of "Tradable Surfaces„ Material handling and associated 0.5 Wlftx `"Tradable Surfaces" storage section of this table.) Drive -up windows at fast food 400W per drive-through restaurants Parking near 24-hour retail entrances 800 W per main entry