Loading...
BroderickDeck2.pdf City of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION (425) 771-0220 DATE: June 18, 2008 TO: Robert Borderick th 403 12 Place N Edmonds, WA 98020 FROM: Ann Bullis, Assistant Building Official RE: Plan Check: 2008-0336 Project: Borderick Deck th Project Address: 403 12 Pl N During review of the plans for the above noted project, it was found that the following information, clarifications or changes are needed. Please provide written responses to each comment as to how it has been addressed, and where changes can be found on the plans. Please submit revised plans/documents to Theresa Umbaugh, Senior Permit Coordinator. 1.The new deck framing plan submitted does not match the deck shown on the site plan. Please revise to match. 2.The new engineered plan submitted only shows bracing. Submit a new dimensioned deck framing plan (matching the deck layout shown on the bracing plan) showing: a.Joist size/spacing/species b.Beam size/species c.Post size d.Footing size e.Beam span between posts f.Span of joists g.Reference ledger detail h.Show where detail “P” applies on the framing plan i.Dimension the deck overhang j.Label the area between the deck and house that the bracing plan shows the deck is being framed around (this was not on the original framing plan). Is this a set of stairs? If so, provide stair construction detail. 3.Revise detail “P” to show span of joists 4.Revise the “typical deck section” to match how the deck will actually be built and reference correct details. (previous item 5) 5.As previously requested (item 4), have the engineer justify the “deck connection to wall”. This is not considered conventional construction and requires engineered calculation to show compliance.