Building Comments 1 (2).pdfCity of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION (425) 771-0220 DATE: August 17, 2017 TO: Blue Hope Construction, Inc. Billy Rho hoperho (&hotmail. com FROM: Chuck Miller, Plans Examiner RE: Plan Check: BLD2017-1036 Project Address: 22001 Highway 99, Suite 400 Project: DTC Hunan Restaurant plumbing and gas piping Scope: Install plumbing and gas piping for fixtures and appliances in a commercial kitchen — separated A-2 occupancy — 98 occupants — VB construction - no sprinkler system installed — Type II hood suppression, fire sprinkler, fire alarm, etc. under separate permits Please be advised that the building plans for the above referenced project have been disapproved for the purposes of obtaining a building permit. During a review of the plans by the Building Division for compliance with the applicable building codes, it was found that the following information, clarifications, or changes are needed. Reviews by other divisions, such as Planning, Engineering, or Fire, may result in additional comments that require attention beyond the scope of this letter. A complete review cannot be performed until the revised plans/documents, including a written response in itemized letter format indicating where the `clouded' or otherwise highlighted changes can be found on the revised plans, have been submitted to a Permit Coordinator. Resubmittals must be made at the Development Services Department on the 2nd Floor of City Hall. Permit Center hours are M, T, Th, & F from 8am-4:30pm and from 8:30am-12pm on Wednesdays. General Review Note: The following comments regard the installation of the plumbing and gas systems associated only with the proposed tenant improvement to be completed under BLD2017-0275. There are still unresolved concerns regarding the size/capacity of the existing water service and grease interceptor serving the existing tenants and the ability to meet the additional demands proposed under this permit. Subsequent review of those items may result in additional work required to be completed under a separate permit prior to the final inspection approval of this permit. On sheet P-1: Plumbing Specifications a. Note #15 — Change on the plans the minimum distance from the plumbing system vent termination to the fresh air intake of the roof -top mechanical unit from ` 10 inches' to `10 feet' per Uniform Plumbing Code (UPC) 906.2. b. Note #16 — Eliminate from the plans the allowance for `18" tall air chambers' `at Contractor's option' as an alternative to the required water hammer arrester(s) per UPC 609.10. 2. Table No. 1-G — Pipe Insulation Thickness — In the note regarding the required portions/types of the service water heating system required to be insulated - Change on the plans the provided information to reflect that required per the Washington State Energy Code (WSEC) C404.6. 3. Plumbing Sizing Form a. PRV — Change on the plans the response to the requirement to install a pressure regulating valve (PRV) from `NO' to `YES' per UPC 608.2 and the City of Edmonds design requirements. Due to the variability/timeliness of measurements taken and the effects of infrastructure improvements on the `available pressure', PRVs are required for all water supply and distribution systems. b. Plumbing Utility Load — Sewer Load — Change on the plans the indicated number of `new' fixture units to that noted on sheet `P-4' — Floor Plan (Waste & Vent). c. Plumbing Utility Load — Water Demand — Change on the plans the indicated number of `new' fixture units to that noted on sheet `P-3' — Floor Plan (Hot & Cold Water). On sheet P-2: 4. Site Plan a. Change on the plans the `site plan numbering' of the gas meter and gas supply line from `8' to `9'. b. Change on the plans the `site plan numbering' of the grease interceptor vent from `9' to `10'. Site Plan Numbering Notes a. Change on the plans the `site plan numbering' of the gas meter and gas supply line from `8' to `9'. b. Change on the plans the `site plan numbering' of the grease interceptor vent from `9' to ` 10' . On sheet P-3: 6. Floor Plan (Hot & Cold Water) — Clarify on the plans the represented installation of the heated water supply serving the public lavatory faucets. It does not appear to meet the maximum piping lengths of WSEC Table C404.3.1. Extending the `recirculating loop' closer to the lavatories (especially in the `Mens'restroom) or the utilization of an instantaneous water heater for each of the lavatories are typically proposed to avoid having to install a tank -type water heater in the same space and still meet the accessibility requirements of ICC Al 17.1-2009. On sheet P-4: Page 2 of 3 7. Floor Plan (Waste & Vent) a. Change on the plans the `floor plan numbering' of the `new' grease waste line from `9' to 10'. b. Change on the plans the location reference on sheet `P-2'- Site Plan - of the `new' grease waste line from `B' to `C'. On sheet P-5: 8. Floor Plan (Gas) — Change on the plans the location reference on sheet `P-2'- Site Plan - of the gas supply line from `C' to `D'. Page 3 of 3