building comments 1.pdfCity of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION (425) 771-0220 DATE: September 29, 2017 TO: Shawn Sullivan shawn&luredesimsolutions. com FROM: Chuck Miller, Plans Examiner RE: Plan Check: BLD2017-1161 - I" review Project Address: 8325 212th Street SW, Suite 103 Project: Edmonds Family Chiropractic Scope: Remove/add non -bearing interior walls/doors and cabinetry/fixtures to reconfigure spaces — separated/nonseparated (undetermined) B occupancy group — 20 occupants — VB construction - no sprinkler system required — mechanical and plumbing under separate permits Please be advised that the building plans for the above referenced project have been disapproved for the purposes of obtaining a building permit. During a review of the plans by the Building Division for compliance with the applicable building codes, it was found that the following information, clarifications, or changes are needed. Reviews by other divisions, such as Planning, Engineering, or Fire, may result in additional comments that require attention beyond the scope of this letter. A complete review cannot be performed until the revised plans/documents, including a written response in itemized letter format indicating where the `clouded' or otherwise highlighted changes can be found on the revised plans, have been submitted to a Permit Coordinator. Resubmittals must be made at the Development Services Department on the 2nd Floor of City Hall. Permit Center hours are M, T, Th, & F from 8am-4:30pm and from 8:30am-12pm on Wednesdays. On sheet A1.0 — Site Plan: 1. Site Plan — Indicate on the plans the occupancy classifications of the tenants on each side of the space to be altered under the scope of this permit per the City of Edmonds `Tenant Improvement Permit Submittal Requirements'. 2. Project Data a. Construction Type - Change on the plans the indicated International Building Code (IBC) Section 602 `type of construction' from `V-A' to `VB' per that approved and constructed under permit BLD 1989-0072. b. Project Square Footage — Change on the plans the indicated area in square feet of the `tenant improvements' from ` 1595' to ` 1512' to reflect the area within the exterior walls that are used to determine applicable code compliance. On sheet A2.2 — Proposed Floor Plan Concept Design: 3. Project Data a. Construction Type - Change on the plans the indicated International Building Code (IBC) Section 602 `type of construction' from `V-A' to `VB' per that approved and constructed under permit BLD 1989-0072. b. Project Square Footage — Change on the plans the indicated area in square feet of the `tenant improvements' from ` 1595' to ` 1512' to reflect the area within the exterior walls that are used to determine applicable code compliance. 4. Door Schedule a. Door No. `107A' — Clarify on the plans the proposed installation of a type `A' door serving space `107' — Exam Room. It does not appear to reflect that described elsewhere in the `Door Schedule' or that anticipated at that location. b. Provide on the plans a `callout' to the applicable `hardware group' from the `Door Hardware' schedule for each of the listed doors to guide proper installation and inspection. 5. Door Hardware schedule — Eliminate from, or update on, the plans the descriptions of the spaces corresponding with each of the listed door hardware `groups'. They do not all appear to reflect the uses of space noted in the `Proposed Plan' on the same sheet. 6. Occupancy Load Calc - Clarify on the plans the difference in the indicated area and occupant load factor used and of those determined using IBC Table 1004.1.2. Assembly areas where people wait for services, such as `waiting rooms', `reception areas', `lobbies', etc. have specific dimensional and `function of area' criteria (often dependent upon the availability and type of seating provided) that determine the occupant load factor to be applied when calculating occupant loads. Update the indicated `max occupancy load' determined in response to the plan review comment. 7. Wall Legend - Wall type `3' - Clarify on the plans the reference to IBC Section 717 regarding the provided `fire blocking, tapping (sic) and draft stopping' of the `existing 1 hour partition/separation wall'. IBC 717 regards ducts and air transfer openings. 8. General Notes — Note 13 — Clarify on the plans the difference in the noted requirement for the completion of mechanical and plumbing work under separate permits and of that indicated on the City of Edmonds `Commercial & Multi -family Building Permit Application'. 9. Proposed Plan a. Clarify on the plans the presence of `existing 1 hour partition/separation wall' construction between the space to be altered under the scope of this permit and the tenants on each side indicated by the wall type `mark' `3'. A record of permitted work requiring such an installation could not be found. b. Clarify on the plans the presence of `existing 2x6 load bearing partition wall' construction along the south side of space ` 108' — Corridor - indicated by the wall type `mark' W. It does not appear to reflect that approved and constructed under permit BLD1989-0072. A record of permitted alterations to the structure requiring such an installation could not be found. Page 2 of 3 Indicate on the plans the specific measures required for the `existing' restroom to comply with International Existing Building Code (IEBC) 410.7 and ICC A117.1- 2009 Section 604 regarding elements along the accessible route serving the primary function to guide proper construction and inspection. As represented, it appears that the lavatory may need to be moved slightly west to provide the required clearance around the water closet per ICC Al 17.1-2009 Section 604.3.1. Typically, the installation of a vertical grab bar per ICC Al 17.1-2009 Section 604.5.1 is also required for `existing' restrooms where little prior permitted work has occurred. The costs of providing the accessible route are not required to exceed 20 percent of the costs of the alterations affecting the area of primary function. On sheet A2.3 — Proposed RCP and Partial Wall Sections: 10. Energy Code Notes — Update the provided information to reflect that applicable to the proposed lighting and required by Washington State Energy Code (WSEC) C405.2. The indicated requirements appear to be a `mix' of those specific to `luminaire-level lighting controls' (LLLC) (note 1 and note 3) with those for the occupancy sensor and daylight responsive controls specified on the `Reflected Ceiling P1anPlan'. The `note' references on `Symbols — Lighting Controls' should also be changed in response to the plan review comment. 11. Reflected Ceiling PlanPlan a. Clarify on the plans the presence of `existing 1 hour partition/separation wall' construction between the space to be altered under the scope of this permit and the tenants on the south side indicated by the wall type `mark' `3'. A record of permitted work requiring such an installation could not be found. b. Clarify on the plans the `callout' to section `4/A2.4' regarding proposed work in space `102' — Reception. Sheet `A2.4' could not be found among the submitted construction documents, although section `2' — Interior Non -Load Bearing Partition Wall — w/GWB Soffit / T-Bar Ceiling — does appear to correspond with the context of the `callout'. c. `Darken' on the plans the `hatching/shading' used to differentiate the separate `daylight zones' from the remaining areas to be lighted. 12. Section 2 - Interior Non -Load Bearing Partition Wall — w/GWB Soffit / T-Bar Ceiling — Extend on the plans the `leader line' from the information regarding the installation of the `horizontal metal studs' for the construction of the soffit to the member represented on the plans to guide proper installation and inspection. Page 3 of 3