Building Comments 1.pdfCity of Edmonds
PLAN REVIEW COMMENTS
BUILDING DIVISION
(425) 771-0220
DATE: March 13, 2018
TO: John Ginn
j ginn&tgbarchitects.com
FROM: Chuck Miller, Plans Examiner
chuck.miller(a-),,edmonmdswa. gov
RE: Plan Check: BLD2018-0123 - I" review
Project Address: 21632 Highway 99
Project: Swedish Cancer Institute -Edmonds pharmacy tenant improvement
Scope: Remove/add non -bearing interior walls/doors and ceiling finishes to
reconfigure/add spaces — relocate 3/add 2 lights — nonseparated Business group B
occupancy — 231 occupants — VB construction — NFPA 13 sprinkler system —
mechanical, plumbing, fire sprinkler, fire alarm, etc. under separate permits
Please be advised that the building plans for the above referenced project have been disapproved
for the purposes of obtaining a building permit. During a review of the plans by the Building
Division for compliance with the applicable building codes, it was found that the following
information, clarifications, or changes are needed. Reviews by other divisions, such as Planning,
Engineering, or Fire, may result in additional comments that require attention beyond the scope of
this letter.
A complete review cannot be performed until the revised plans/documents, including a
written response in itemized letter format indicating where the `clouded' or otherwise
highlighted changes can be found on the revised plans, have been submitted to a Permit
Coordinator. Only those sheets specifically referenced as follows need to be resubmitted.
Resubmittals must be made at the Development Services Department on the 2nd Floor of City Hall.
Permit Center hours are M, T, Th, & F from 8am-4:30pm and from 8:30am-12pm on Wednesdays.
On sheet A6.01 — Door & Relite Schedules, Legends & Hardware:
1. Partition -Type Legend — Provide on the plans information regarding the construction of
partitions identified on sheet `A2.11' — Floor & Ceiling Plans — as `W3'.
2. Partition -Type: Vertical Configuration Legend — Provide on the plans information regarding
the required attachment at the base and the top or optional bracing of the partitions. Include
the specified fasteners and their spacing along with the material for, and spacing of, the
optional bracing.