Building Comments 1.pdfCity of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION (425) 771-0220 DATE: March 4, 2019 TO: Emerald Aire, Inc. permits kemeraldaire. com FROM: Chuck Miller, Senior Plans Examiner chuck.miller(a-),,edmondswa. gov RE: Plan Check: BLD2019-0118 — 1st review Project Address: 22214 Highway 99 Project: Doug's Mazda mechanical Scope: Installation of rooftop/wall-mounted split system heat pumps/electric forced air heater/DOAS ERVs/garage exhaust and associated ductwork /controls — nonseparated Business group B/Storage group S-2 occupancies — 160 occupants — IIB construction — NFPA 13 sprinkler system — structure, plumbing, fire sprinkler, fire alarm, etc. under separate permits Please be advised that the building plans for the above referenced project have been disapproved for the purposes of obtaining a building permit. During a review of the plans by the Building Division for compliance with the applicable building codes, it was found that the following information, clarifications, or changes are needed. Reviews by other divisions, such as Planning, Engineering, or Fire, may result in additional comments that require attention beyond the scope of this letter. A complete review cannot be performed until the revised plans/documents, including a written response in itemized letter format indicating where the `clouded' or otherwise highlighted changes can be found on the revised plans, have been submitted to a Permit Coordinator. Only those sheets specifically referenced as follows need to be resubmitted. Resubmittals must be made at the Development Services Department on the 2nd Floor of City Hall. Permit Center hours are M, T, Th, & F from 8am-4:30pm and from 8:30am-12pm on Wednesdays. On sheet M0.0 — HVAC COVERSHEET: BASEMENT CAR STORAGE NARRATIVE a. Clarify on the plans the specified type of ventilation system to be provided for the `BASEMENT CAR STORAGE' area. While identified elsewhere on these plans as an `INVENTORY STORAGE' area of vehicles for retail sale, the use of the area has been classified on the approved plans for the structure under permit BLD2017-1119 as a Storage group S-2 occupancy — enclosed parking garage. While it is understood that the space will not be used for the parking of employee or visitor vehicles, the concerns of the International Mechanical Code (IMC) regarding those that are stored there are the same. The presence of carbon monoxide/nitrogen dioxide anytime a vehicle is started and running while being moved into or out of a space, especially those where additional vehicles are first required to be moved, must be addressed by a system complying with IMC Table 403.3.1.1/404/Washington State Energy Code (WSEC) C403.2.6.4 — see also plan review comments `4' and `6.a'. b. Change on the plans the provided information regarding the appliance used to semi - heat the car storage area to that corresponding with the `ELECTRIC FORCED AIR HEATER' specified on sheet'MO. V — HVAC EQUIPMENT SCHEDULES. 2. SERVICE RECEPTION — Clarify on the plans the difference in the stated space - conditioning of the SERVICE RECEPTION area and of that noted on the `Low Energy and Semi -Heated Spaces' portion of the 2015 WSEC `Compliance Forms for Commercial Buildings including R2, R3, R4 over 3 stories and all R1' Mechanical Summary — MECH- SUM — form — see also plan review comment `8.c'. On sheet MO.1 — HVAC EQUIPMENT SCHEDULES: 3. ENERGY RECOVERY VENTILATORS — ERV-1 — Clarify on the plans the model specified to serve the areas noted on sheet `M0.2' — HVAC LOADS & CALCS — VENTILATION CALCULATIONS — and represented on sheet `M1.2' — MAIN LEVEL HVAC PLAN — MAIN LEVEL PLAN. It does not appear to have the capacity required to comply with IMC Table 403.3.1.1/403.3.1.1, Exception — see plan review comment `6.b' for specific information. 4. FANS — FN-1 - Clarify on the plans the specified equipment used to ventilate the `INVENTORY STORAGE' area. The proposed fan does not appear to comply with that required for an enclosed parking garage per IMC Table 403.3.1.1/404. The fan controls and detectors must also comply with WSEC C403.2.6.4 and be identified on the plans. On sheet M0.2 — HVAC LOADS & CALCS: 5. HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY - COOLING SYSTEM PSYCHROMETRICS — Clarify on the plans the indicated `Outdoor Design Temp Heating' value in'F. It does not appear to correspond with that specified for Edmonds in WSEC Appendix C, Table C-1. 6. VENTILATION CALCULATIONS a. OCCUPANCY CLASSIFICATION — Change on the plans the indicated IMC `OCCUPANCY CLASSIFICATION' from `RETAIL STORAGE' to `ENCLOSED PARKING GARAGE'. Update/change the provided information to reflect that applicable per IMC Table 403.3.1.1/404. b. ACTUAL # OF OCCUPANTS — SHOWROOM W and SHOWROOM E — Clarify on the plans the indicated number of occupants used to determine the ventilation requirements. It appears to be significantly less than that using IMC Table 403.3.1.1 or allowed per IMC 403.3.1.1, Exception. Using the ratio of the floor area served by each of the systems to apportion the number of occupants noted on the approved plans for BLD2017-1119, the number of occupants for each area would be as follows: • SHOWROOM W — 27 occupants • SHOWROOM E — 58 occupants Page 2 of 3 Update/change the corresponding information to reflect that applicable per IMC Table 403.3.1.1/403.3.1.1, Exception. On sheet MI. I — LOWER LEVEL HVAC PLAN: 7. LOWER LEVEL PLAN — Specify on the plans bollards, or an alternative method, to protect appliance 'FUR- I' —electric forced air heater —per IMC 303.4. The height of the lower level does not appear to allow compliance with IMC 304.6 when vehicles are possibly arranged as represented on sheet `A2.2' — STORAGE — LOWER LEVEL PLAN — LOWER LEVEL PLAN. On sheet M 1.2 — MAIN LEVEL HVAC PLAN: 8. MAIN LEVEL PLAN a. Clarify on the plans the difference in the configuration of the various spaces and of that represented on sheet `A2.1' — MAIN LEVEL PLAN — OFFICE MEZZANINE — MAIN LEVEL PLAN. Update the configuration/sizing of the ductwork serving each of the rooftop units in response to plan review comments `6.b' and `8.b' in addition to this review comment. b. Indicate on the plans the required provision of an exhaust airflow rate of approximately 40 CFM in the `JANITOR' space per IMC Table 403.3.1.1. c. Indicate on the plans the proposed method/appliance used to `semi -heat' the `SERVICE RECEPTION' area as noted on the 2015 WSEC `Compliance Forms for Commercial Buildings including R2, R3, R4 over 3 stories and all R1' — Mechanical Summary — MECH-SUM — form. On sheet M3.1 — HVAC DETAILS: 9. RTU-1 INSTALLATION DETAIL and RTU-2 INSTALLATION DETAIL — Specify on the plans the minimum required attachment (fasteners and their spacing for equipment-to- curb/spacing of fasteners for curb -to -roof) of each of the equipment to resist lateral loads per American Society of Civil Engineers (ASCE) 7-16, Chapter 13. The design must be supported by structural calculations. A reference to the alterations of the roof framing to accommodate the mechanical equipment, and be completed as a revision of that represented on sheet `S 1.4' — ROOF FRAMING PLAN' — of the approved plans for permit BLD2017- 1119, must be also added to the plans. On the 2015 WSEC `Compliance Forms for Commercial Buildings including R2, R3, R4 over 3 stories and all R1': 10. Provide as part of a complete permit application submittal the 2015 WSEC `Compliance Forms for Commercial Buildings including R2, R3, R4 over 3 stories and all R1' Mechanical Permit Plans Checklist — MECH-CHK — and the Mechanical Fan System Power Allowance — MECH-FANSYS-SUM — form. Page 3 of 3