I am reviewing the Firestopping information that was submitted 7/3/08. The requested listed and tested fire stopping
assemblies were still not submitted. All that was provided was product information on Firetemp CI, which is a product
found in many listed and tested assemblies. Please read item #1 of my 6/27/08 comments where I have tried to explain
how to find these listed and tested assemblies on the Johns Manville website. Again, you may want to contact the
manufacturer directly for assistance.
In reviewing the letter dated 4/10/07 from SDA (submitted 7/9/08), the City has not approved items 1 and 2 noted in the
letter. Please have SDA inspect these items and provide a letter approving construction. Where missing holdowns must
be retrofitted, provide special inspection report for installation. With regards to the last statement in the letter, the
structural engineer of record shall provide a letter that all structural discrepancies have been addressed and the structure
complies with the revised structural plans approved by the City on 9/5/07.