BuildingREVcomments7-15-08.pdf Bullis, Ann Bullis, Ann From: Tuesday, July 15, 2008 10:41 AM Sent: 'cmg@triadlawgroup.com' To: Harrison, Marie Cc: 155 3rd Ave S -- partial resubmittal Subject: Mr. Greenberg, I am reviewing the Firestopping information that was submitted 7/3/08. The requested listed and tested fire stopping assemblies were still not submitted. All that was provided was product information on Firetemp CI, which is a product found in many listed and tested assemblies. Please read item #1 of my 6/27/08 comments where I have tried to explain how to find these listed and tested assemblies on the Johns Manville website. Again, you may want to contact the manufacturer directly for assistance. In reviewing the letter dated 4/10/07 from SDA (submitted 7/9/08), the City has not approved items 1 and 2 noted in the letter. Please have SDA inspect these items and provide a letter approving construction. Where missing holdowns must be retrofitted, provide special inspection report for installation. With regards to the last statement in the letter, the structural engineer of record shall provide a letter that all structural discrepancies have been addressed and the structure complies with the revised structural plans approved by the City on 9/5/07. Sincerely, Ann Bullis, CBO Building Official City of Edmonds 121 5th Ave N Edmonds, WA 98020 425-771-0220