Cambridge Condo CG Eng letter dated 1-4-08.pdfENG[NEERING Memorandum MAR 14 2DIL To: City of Edmonds Building Inspector From: C. Chevy Chase, PB, SE Date: January 4, 2008 Re: Cambridge Condominiums Dry Rot Repairs (Permit No.'s: BLD20071183, BLD20071184, BLD20071186, BLD20071186, BLD20071187) ll�?.4a7 ~ C11rl It is our understanding that the City's Inspector was unable to view the nailing patterns of the plywood during the framing inspection. Based on the original approved plans, the walls where plywood was replaced were not shear walls. Therefore the minimum nailing required for 15132" sheathing per IBC 2006 Table 2304.5.1 is 6d common nails spaced at 6 -incites on center at edges and 12 -inches on center at intermediate supports. Based on photographs of the nailing patterns taken during the repairs and correspondence with the contractor, these minimum nailing requirements were met. SVY C t � TEg�'q 10 L � SPIRES: 7 1? z 08 NOTES: 1. CONTRACTOR SHALL CONTINUOUSLY MONITOR EXISTING FRAMING DURING REPAIRS FOR POTENTIAL DEFORMATION CAUSED BY UNOBSERVABLE DRY ROT, AND NOTIFY CG ENGINEERING IMMEDIATELY IF DEFORMATION IS OBSERVED. 2. WE RECOMMEND THAT THE CONTRACTOR TREAT ALL STAINED WOOD MEMBERS PER RECOMMENDATIONS OF A MOLD REMEDIATION CCNSULTANT. STEEL ANGLE FOR TEMPORARY - SUPPCRT OF EX. 6x10 HDR. REMOVE DRY -ROTTED BOTTOM— PLATE AND REPLACE W/ LIKE KIND WHILE TEMPORARY SHORING IN PLACE. EX. 6x10 i HEADER SUPPORTING BUILT-UP STUD COLUMN ABOVE. INSPECT EX, POST BELOW FOR DRY ROT NOTIFY CG ENGINEERING IF FOUND TO BE ROTTED. TEMPORARY SHORING PLAN PARTIAL THIRD FLOOR FRAMING SHOWN SCALE: 1/4!' = 1'-0" <t C C CAMBRIDGE CONDOS DRY AOT REPAIR Cep12/0f/07 cauaNG AD. 630 WALNUT ST. UNIT #201 � eCI No,07M.10 ENGINEGFZM EDMONDS WA 88020 S= '/l -V 'gE TEMPORARY SHORING PLAN moo=• mow„ DRAD` 1°' , Piwxe caws ne-esoa CHS wu eAx �an� ne-ssse APPMAD of Ctt /2' L6x6x3/8 x 0'-6" W/ (6)-5/8"0 x 4" LAG SCREWS INTO END OF EX. 6x10 HEADER 1" AND (4)-5/8"0 x 4" LAG SCREWS INTO '^ EX. 7 x 11 1/4 RSL (10 -TOTAL) f EXISTING 7 x 11 1/4 PSL iK— O O O O EXISTING 6x1O HEADER TEMPORARY SHORING DETAIL SCALE: 1 1/2" = 1'-0" � �j"qy � G� C� .23125 � 1w EXPIRES; 7/6/2008 CAMBRIDGE CONDOS DRY ROT REPAIR DATE 12/04/07 DWiV19NG N0. 630 WALNUT ST. Pi20JEcr No-. 07253.10 ENGINEERING EDMOND3 WA. 98020 SCALE i t/z•=]'-o' TEMPORARY SHORING DETAIL OU Ini" . s., TO?l sauoNnE WASFIfHGB- �i�Eo ire e;7 n til -2 se6sa 020 PHOHE (125) 776-SSaO � FAY (125) 778-SS36 APPROVED BY NAR f 2008 tclCry,d GfTy g 0�fPAM'f'?s§LNs_ ��(ifVf1 11 MIN. NOTES: 1. PROVIDE A MINIMUM OF (2) -HOLES PER STEEL. ANGLE AND (1) -HOLE WITHIN 5" OF FROM EACH END. ADDITIONAL HOLES FOR EX. L6x4xl12 SCALE: 3" = 1'-O" V,NY 237 8T�g`�9 Cs SINAL � vA EXPIRES; 7 6 2008 CAMBRIDGE CONDOS DRY ROT REPAIR DATE 12/04/07 DMWING NO. 530 WALNUT ST. PROD€cT NO. 07203.10 ENGINEERING EDMONDs WA. 98020 sckE ADDITIONAL HOLES FOR EX. L6x4xl/2 SNGSURE CHE�E 8Y klcv SS-�` WORM 9U2D PHOHE (125) 776-0 850 iAx {125) 778-5539 APPROVED HY OCC 2x6 STUD WALL ATTACH BRICK TO STUD WALL W/ ANCHOR TIES @ 24" O.C. 5/8"0 x 5" LAG SCREWS @ 9" O.C. MAX. SPACING W/ MIN. (2) PER STEEL ANGLE. RE—OSE L6x4x1 /2. PROVIDE ADDITIONAL HOLES PER SS -4 1„ GAP.77 ON A35 DE iF#2 ING 3d TOE NAILS EA. f BLKG. RI TYPICAL BRICK VENEER CONNECTION DETAIL SCALE: 1 1/2" = l'-0" �Wy c4v �.V'4 O� �Tttpl'� GtsTF 0NAL EXPIRES: 7/6/2008 CAMBRIDGE CONDOS DRY ROT REPAIR GATE 12/04/07 ORAVMG NO. 530 WALNUT ST. PROJECT NO. 07236.10 ENGINEERING EDMONDS WA. 98020 scut: 11/2'_1'-0• TYPICAL BRICK VENEER CONNECTION EUYOND5, WAVNOTOH $8020 DRAWN BY S _ PHONE (425) 778-SWO FAX (425) 778-5535 n DETAIL C1tECKEO t m A(fA[ APPROM fff CCC Page 1 of 1 Bullis, Ann From: Mike Maechler [mikem@cgengineering.com] Sent: Friday, March 14, 2008 8:43 AM To: Bullis, Ann Subject: Cambridge Condos Ann, Please see the attached pdf, which includes all of the documents we issued to the contractor to keep on site for the Cambridge Condos. There is a memo regarding nailing of the sheathing, temporary shoring plans and details, and (2) details for the re -attachment of the brick veneer support angle. Note that SS -3 is missing as it was never used or issued. Feel free to call or email me with any questions you have. Thanks, Mike Maechler CG Engineering, PLLC 2504th Ave. South, Suite 200 Edmonds, WA 98020 P (425) 778-8500 F (425) 778-5536 RF 'OJ F MAR 3/14/2008