Loading...
CambridgeRepair1.pdf City of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION (425) 771-0220 DATE: December 7, 2007 TO: Mike Maechler CG Engineering E-mail: mikem@cgengineering.com FROM: Ann Bullis, Assistant Building Official RE: Plan Check # 2007-1183 Project: Cambridge Condos -- Dryrot repair of decks Project Address: 530 Walnut Street 100, 101, 200, 201, 300 During review of the plans for the above noted project, it was found that the following information, clarifications or changes are needed. Provide written responses to each comment and where changes can be found on the plans. Please resubmit to Theresa Umbaugh, Permit Coordinator. 1.Since structural repairs will be made per the original approved building plans (permit 1998- 0870), provide 2 copies of the applicable structural sheets from the approved plans, highlight the areas of work, and submit for review. 2.This is a Type VA (1-hour) building. Fire resistive assemblies (walls, floor-ceiling, etc.) damaged or removed to complete the structural repair, must also be repaired. Submit 2 copies of applicable sheet(s) from the original approved building plans for review. 3.Description of work notes that Bee Consulting will be providing waterproofing details and overseeing installation. Submit 2 sets of building enclosure documents stamped and signed by the architect/engineer from Bee Consulting, including a signed statement from the architect/engineer that the building enclosure design documents satisfy the requirements of RCW 64.55.005 through 64.55.090 (see RCW 64.55.020(2).