CarStar2.pdf City of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION (425) 771-0220 DATE: April 3, 2008 TO: Bob Fadden Lance Mueller & Associates FAX: 206-328-0554 FROM: Ann Bullis, Assistant Building Official Mike Smith, Senior Fire Inspector RE: Plan Check # 2008-0122 Project: Car Star Remodel th Project Address: 7323 224 Street SW During review of the plans for the above noted project, it was found that the following information, clarifications or changes are needed. Provide written responses to each comment and where changes can be found on the plans. Please resubmit to Theresa Umbaugh, Permit Coordinator. The March 12, 2008 comments were based on alterations made to an existing building under the current 2006 International Building code. When an alteration is made to the building, it must comply with the current adopted codes. Plans submitted for a permit for alteration to an existing building are required to show basic code information based on the current code. Many of the plan review comments were needed due to the lack of such information provided on the plans. Lastly, the City has not adopted the International Existing Building Code, so it is not applicable to this permit application. 1.Ok – Correct occupancies shown on the plan. 2.Ok – Fire separations shown on the plan. 3.Ok – Construction details and assemblies shown on the plan. 4.Ok – Use of space shown on the plan. 5.Response regarding fire separation distance and “no build area”: The owner may apply for an Alternate Design in accordance with IBC 104.11 for a no build easement along the west property line of the east adjacent property. The written request must be stamped and signed by the architect of record and include applicable code provisions, reasons for the request and statement(s) of equivalency to what is required by the code. Have the owner’s attorney draft the easement and submit with the request for Alternate Design. The fee is $180.00 and the applicant is also responsible for all City Attorney review fees of the easement. OR, as previously noted in the past plan review comments, contact Jen Machuga, Planner, regarding the lot line aggregation procedure. 6.Ok – East elevation view of the building. 7.Ok – Notes provided. 8.Ok – plan clarified. 9.Ok – Information provided. 10.Deferred with mechanical submittal. 11.Deferred with mechanical submittal. 12.Ok – Calculation provided. 13.Ok for architectural plans – mechanical plans still to be checked. 14.Deferred with mechanical. 15.Ok – fire extinguishers shown on plan. 16.Deferred with mechanical. 17.Ok – architect verified in response letter. The International Existing Building Code is not adopted by the City of Edmonds and is not applicable to this project. Additional Fire Review Comments: No memo from WESCO was provided with the resubmittal as noted in the response letter. 18.Still awaiting resubmittal/response. 19.Still awaiting resubmittal/response. 20.Still awaiting resubmittal/response. 21.Still awaiting resubmittal/response. Page 2 of 2