CGENG2.pdf City of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION (425) 771-0220 DATE: March 5, 2008 TO: Chevy Chase, PE FROM: Ann Bullis, Assistant Building Official RE: Plan Check # 2008-0078 Project: TI CG Engineering th Project Address: 250 4 Avenue S, Suite 101 During review of the plans for the above noted project, it was found that the following information, clarifications or changes are needed. Please redline the plans and attach calculations to expedite review. Please resubmit to Theresa Umbaugh, Permit Coordinator. 1-4. OK 5. Show existing return air duct(s). See IMC 403 which states, ‘mechanical ventilation shall be provided by a method of supply air and return or exhaust air. The amount of supply air shall be approximately equal to the amount of return and exhaust air….The system to convey ventilation air shall be designed and installed in accordance with Chapter 6.’ If you are proposing to undercut doors, provide calculation for each room to show that the net free area of theundercut dimension will equal the supply air. 6. Ok