Consultant Approval with Conditions.pdf"J"11 3.4,31,161,, SFREIET SW fill OFFICE(425) 582-1719 FAX: (425) 285-5429 April 7, 2016 City of Edmonds Development Services Dept. 121 5th Ave. N Edmonds, WA 98020 Phone: (425) 771-0220 Attention: Leif Bjorback, Building Official WC3 Project #: 215 -EDM -002 Edmonds Permit #: BLD2015-1562 RIECIEIVEE) APF?0i2516 DEVELOPMENT SERVICES COUNTER Subject: Edmonds Memory Care – Fire Sprinkler Submittal – Plan Review Approval Mr. Bjorback: West Coast Code Consultants, Inc. (WC3) has completed the second review (fire only) of the fire sprinkler submittal for the Edmonds Memory Care project. Our review was based upon the following submittal documents: 1. Fire sprinkler plans dated 03/18/2016 by Fox Fire Protection, sealed and signed by Adam B. Cole, certified for fire protection sprinkler systems. 2. Hydraulic calculations dated 12/08/2015. 3. Compiled material data sheets. The Washington State Building, as currently adopted, and its referenced standards were used as the basis of our review. We do not have any comments to make at this time and recommend approval of the fire sprinkler submittal subject to compliance with the attached comments and field inspection. If you have any questions in regards to this review please do not hesitate to contact me. Sincerely, I— -a Chris Kimball, PE, MCP, CBO Attachment: Conditional Approval Plan Review Approval Letter Project Name: Edmonds Memory Care — Fire Sprinkler Submittal Location(s): 7208 210th Street SW, Edmonds, WA Date of Comments: 04/07/2016 Edmonds Permit #: BLID20151562 ApirH 7, 2016 Fire Review By: Chris Kimball The revised fire sprinkler plans and submittals for the above referenced project have been reviewed. The submittal is APPROVED subject to compliance with the following comments and field inspection. FIRE REVIEW COMMENTS: F1. All work is to conform to the 2012 International Fire Code as adopted by the City of Edmonds as well as the 2010 version of NFPA 13. F2. All items shall be installed per manufacturers' specifications, including location, spacing, height, and securely mounted. F3. All system components shall be supported and restrained as required by Chapter 9 of NFPA 13. F4. All acceptance tests shall be performed in the presence of the fire inspector as required by NFPA 13. F5. Provide a hydraulic design information sign as required by NFPA 13. F6. Provide at least six spare sprinklers, and at least two of each type, along with the appropriate wrenches in a spare sprinkler cabinet as required by Section 6.2.9 of NFPA 13. F7. Provide auxiliary drains as necessary to completely drain all portions of the wet pipe system as required by Section 8.16.2 of NFPA 13. F8. Sprinkler spacing and location with respect to obstructions shall be in compliance with Chapter 8 of NFPA 13. Proper spacing of sprinklers shall be verified during field inspection. F9. Where corrosive conditions exist or piping is exposed to the weather, corrosion -resistant types of pipe, fittings, and hangers or protective corrosion -resistant coatings shall be used per Section 8.16.4.2 of NFPA 13. F10. All control, drain, and test connection valves shall be provided with permanently marked weatherproof metal or rigid plastic identification signs per Section 6.7.4 of NFPA 13. Signs shall be secured with corrosion resistant wire or chain. F11. All sprinklers subject to mechanical injury shall be protected with listed guards per Section 6.2.8 of NFPA 13. F12. All hose connection and fire department connection threads shall be verified prior to final system acceptance per Section 11.3 of NFPA 14. Edmonds Permit #: BILD2015-1.562 WC, Project Ih, 215 EDIM-002 � . .� ....._..� _ Ilpfi " , 2016 F13. Installation of signs as required by the IFC and NFPA 13 shall be provided. Proper signage will be verified during field inspection. F14. The stamped drawings, approved by way of these comments, shall be available on site for each required field inspection. F15. Contractor shall complete and provide,a copy of the "Contractor's Material and Test Certificate" for record per Section 25.1 of NFPA 13. Should you have any inquiries regarding this letter, please contact Chris Kimball via email or phone (chrisl� we-acor, 801-682-5031). [END] .. ---- ......... ............................... .......................... Page 3 of