Demetri's.pdf
August 12, 2010
Thomas Nicol
Highland Development Inc
24375 Fjord Pl. NW
Poulsbo, WA 98370
SUBJECT: Plan Review
Dear Mr. Nicol;
I have reviewed the resubmitted plans s. The plans are approvable for the general building
permit, however, there are still some items that require additional detailing.
The specifications that were provided for the fireplace unit show the general framing clearance
requirements surrounding the unit, but do not show how the unit will be vented. Please show the
construction of the venting system (chimney), materials to be used and surrounding construction
(wood, masonry?). Please refer to chapter 8 of the International Mechanical Code.
The specification sheets provided for the pizza oven indicate that it must be vented through a
-
construction of the hood and duct system to be used for this exhaust. The plans must incorporate
applicable provisions of section 506 of the International Mechanical Code for hood and duct as
well as the details for the fire-rated shaft.
These two items can be deferred to a separate permit if needed, please advise how you wish to proceed. I
have attached a copy of my original review for your reference. Also I have copied the designer on this
letter.
Sincerely,
Leonard Yarberry
Building Official
copy: Alexa Milton