Loading...
DOH review CRS60354768.pdf Letter of Transmittal August 13, 2013 Construction Review Services 111 Israel Rd. SE Tumwater, WA 98501 PO Box 47852 Olympia, Washington 98504-7852 www.doh.wa.gov/crs tel. 360-236-2944 fax. 360-236-2321 Project Info: CRS# 60354768 Project 728 Edmonds Way Rosewood Courte Memory Care Community location: Edmonds, WA 98020-5126 Chapter 388-78A WAC Boarding Homes Interior Alterations - Phase 2 Local Permit #: Key People: Assigned DOH Kevin A. Scarlett, RA/ Mina Zarelli Reviewer: kevin.scarlett@doh.wa.gov / mina.zarelli@doh.wa.gov Facility Rosewood Courte Memory Care Community Facility Contact: Same as Administrator Administrator: Michael Hickey 728 Edmonds Way Edmonds, WA 98020-5126 (425) 673-2875 x. x. michael@rosewoodcourte.com Architect / Wright Architecture Local AHJ: City of Edmonds Engineer: Charles Wright Leif Bjorback 3517 W Government Way Ste 104 121 5th Ave N. Seattle, WA 98199 Edmonds WA 98020-3145 (206) 285-7167 x. (425) 771-0220 x. charles@wrightarch.com leif.bjorback@edmondswa.gov Consultant: N/A Consultant: N/A x. x. Contact: N/A Contact: N/A x. x. Copies To: of Edmonds DOH Child Birth Center Licensing Local AHJ: City DOH Office of Investigations & Inspections Architecture Architect / Engineer: Wright DSHS, , Div. Of Alcohol & Substance Abuse /A Consultant: N DSHS, Annette Curry, Aging & Adult Services Admin. /A Consultant: N L&I, Bill Eckroth, Electrical Section /A Contact: N L&I, John Harvey, Factory Assembled Structures /A Contact: N CRS File Page 1 of 5 Plan Review Comments for Project #60354768 Facility Data Certificate: Facility Name: Rosewood Courte Memory Care Community Licensee UBI#: 601926961 Site Address: 728 Edmonds Way Critical Access Facility: Yes No Edmonds, WA 98020-5126 Estimated Date of Occupancy: 05/01/2013 Occupancy R2 Construction 5-B Applicable Code: Group: Type: 2009 IBC S Number of Current: 45 Added: 2 Removed: 0 Total: 47 E P Beds: Y T Automatic Fire Sprinkler System: Yes No Type 13 Y T Automatic Fire Alarm System: Yes No I L I C Compartmentation : Yes No Smoke Control System Provided: Yes No A F L Special Delayed Egress Control: Yes No Location: L A Certificate of Need Required: Yes No CON Approval Granted: Yes No CON Number : Number of units: Private occupancy: Two person occupancy: E Y R Based on size of rooms used for sleeping Residents L A N C Based on size of common rooms Residents O L S A E Maximum allowable licensable beds: I T I T N I Qualifies for Assisted Living Funding Program Yes No Number of qualifying units: E L D I C I S A E F R Compartmentation and delayed egress doors are not a part of this project and are assumed existing due to the occupancy (Memory Care). Actual locations of these two elements are not indicated on the documents and are not part of this review. S E T O N The data above is based on the information presented to CRS. Any change in the facility or facility program that causes the above information to be incorrect is subject to review by CRS. Approval for construction is not approval for licensure. A copy of the facility data certificate will be sent to the licensing agency. Page 2 of 5 Plan Review Comments for Project #60354768 Rosewood Courte Memory Care Community Chapter 388-78A WAC Boarding Homes Interior Alterations -Phase 2 : Project Status - Authorized to Begin Construction - Comments Not Approved not approved This project is for use or licensure. The construction documents have been reviewed and construction can begin, subject to construction permitting from the local building official. by providing a written response to each of the comments. When referencing drawings or attached materials, provide sheet or page #, revision # and date as applicable. Additional comments may follow based on design team response and site inspections may be required to verify compliance. Please note the following: The stamped gs will be delivered to the Facility Administrator. These shall be kept available on site for inspection during construction and at post occupancy survey. Final licensing approval is subject to a site inspection by DSHS and the Office of the State Fire Marshal to verify compliance with licensing regulations and your approved documents. If stamped approved plans are not available, the site inspection may be terminated until such time they are available as determined by the licensing inspector/surveyor. Any changes/deviations (incl. change orders or addenda) from the stamped documents must be submitted to the Department for review and approval. Please include your CRS number on all communications to Construction Review Services. PROJECT CLOSE-OUT REQUIREMENTS You must notify the department when construction is complete by completing the following steps: Verify that you have resolved all of the comments on this form and have submitted any revisions Complete the Notification of Construction Completed at: http://www.doh.wa.gov/NotificationofCompletion.aspx Email a copy of the approval from the local building department (final permit approval or fslcrs@doh.wa.gov certificate of occupancy) to: fslcrs@doh.wa.gov Email a floor plan showing the scope of work to: If you have any questions please contact Construction Review Services at (360) 236-2944. You can monitor project status at www.doh.wa.gov/crs. Page 3 of 5 Plan Review Comments for Project # 60354768 Rosewood Courte Memory Care Community Chapter 388-78A WAC Boarding Homes Interior Alterations -Phase 2 Plan Review Comments: # d e D v I o d t r n e p e v p m o A r m p t po o AN C 1 Provide two sets of Fire Alarm plans as reviewed and stamped Approved by the local AHJ (City of Edmonds). Drawings must bear the City Approval Stamp including signature and date of review Approval. Upon review plans this comment will be marked Deemed (effectively same as Approved). 2009 IFC 907.1 Not Approved 7/24/13 Drawings received 6/28/13 are the as-built drawings from 1999 when the building was originally constructed. Provide drawings that show the changes to the existing fire alarm system. The new Unit 52 requires a smoke alarm per IFC 907.2.11.2(2) MZ 2 Provide two sets of Fire Sprinkler plans as reviewed and stamped Approved by the local AHJ (City of Edmonds). Drawings must bear the City Approval Stamp including signature and date of review Approval. plans this comment will be marked Deemed (effectively same as Approved). 2009 IFC 903.1 Not Approved 7/24/13 Drawings received 6/28/13 are the as-built drawings from 1999 when the building was originally constructed. Provide drawings that show the changes to the existing fire sprinkler system. MZ 3 Provide Nurse call buttons/pulls at each bed in room 52 and at toilet & shower in room 51. WAC 388-78A-2930(1)(a)(iv) Not Approved 7/24/13 A nurse call device is required at EACH BEDSIDE so that it is convenient to the resident. The drawings received 6/28/13 show a nurse call at the south wall of the unit and does not meet the intent of the code. MZ 4 Verify that wall heater and existing HVAC Supply & Return air in room 52 have capacity to adequately heat this room (able to maintain 70°F. WAC 388-78A-2990(1) Not Approved 7/24/13 Per response received 6/28/13, the thermostat for the central system is located in the corridor and additional wall heaters are provide in the sleeping room and bathroom. The supply and return outlets/inlets must be adjusted so that the air supplying this room is comfortable as a resident sleeping unit. The central system cannot supply Page 4 of 5 Plan Review Comments for Project # 60354768 Rosewood Courte Memory Care Community Chapter 388-78A WAC Boarding Homes Interior Alterations -Phase 2 air that is too cold or too hot. Provide a balance report and a statement to address these concerns. MZ 5 Indicate how the residents in room 52 have control over the HVAC Supply air into this room. WAC 388-78A-2990(5) Approved 7/24/13 Per response received 6/28/13, the residents will be able to control the supply air from the thermostat in the corridor. The residents can adjust the temperature of the room with the wall heaters. MZ 6 Verify if room 52 has a cooling capacity via the HVAC system. WAC 388-78A-2990(2) Approved 7/24/13 Per response received 6/28/13, the central system has cooling capacity. MZ 7 Indicate what the use of space 53A is intended for. Approved 7/24/13 Per response received 6/28/13, 53A will have casework used by the Nursing Director. MZ 8 Verify that room 52 will be equipped with shades or blinds on the windows WAC 388- 78A-3010(1)(e)(ii) Approved 7/24/13 Per response and drawings received 6/28/13, mini blinds will be installed in the room. MZ 9 Provide an individual towel and washcloth rack for each resident in room 52. WAC 388- 78A-3010(h) Approved 7/24/13 Per response and drawings received 6/28/13, two towel bars will be installed in the bathroom. MZ Compliance with the comments above provided by the Department of Health Construction Review Services are necessary for this facility to meet the requirements of the applicable licensing regulations found in the Washington State Administrative Code and associated references. These comments do not relieve the facility from the responsibility to meet the requirements of any other applicable federal, state or local regulations. In the event of conflicts between other jurisdictions and these written comments, the most stringent shall apply. Page 5 of 5 Plan Review Comments for Project # 60354768