Loading...
Door Rating Revision.pdf. . .. ....... . 0 I Mi, t ant e orri e rs A R C I I I F F C l U R A 1, G R 0 U P September 19, 2011 Leif Bjorback Building Official City Of Edmonds 121 5th Ave. North Edmonds, WA. 98020 RE: 155 3rd and Dayton Building (2006 IBC) Leif, 6161 NI E 175th St,00, Suite 101 Kenrinuie, Wishmg(on Y8028 206.682 50001 RE CEIVED BL)ILDING DEPT. It appears that the original drawing's Door Schedule for this project was in error by indicating one hour rated doors in a corridor with one hour rated walls separating the corridor from the office/tenant spaces. These doors should be 20 minute rated doors as per the 2006 IBC, A one hour rated corridor requires a 20 minute rated door per the 2006 IBC Table 715.4 Type of Assemble 1 hour rated corridor walls has a minimum fire door assembly = 1/3 hour. The glass in the door shall be rated the same as the door per IBC section 715.4.3.2. If you need addition information to make this revision to the door schedule please let me know. Sincerely, cc: Elliot Shaw, Shaw Elevators REVISED PIAN APPROVED CITY OF" 13,T)MONDS B1,111,I)ING DIVISION MANS NI: X%WHNER