Fire marshals will not be attending your meeting due to scheduling conflicts.
Normally Development
Review Committee provides verbal comments, in this case I am writing them down for
you and please
respond with any questions/clarifications you need.
Fire questions/comments in accordance with 2012 IFC and Chapter 19.25 ECDC.
1) Reviewer sees comments from previous approval (2008), however, no
architectural plans are
within reach for this DRC review.
2) It appears that the following system permits were required for previous
plans: Fire
connection(supply), Fire sprinkler, Fire alarm.
3) Access to the fire system riser room is preferred directly from exterior.
Similar arrangements
have been made in neighboring small multi-residentials.
4) One existing fire hydrant is provided, and with sprinkler system no
additional fireflow is
necessary.
5) Access will be made from Glen Street and using the side yards/setbacks
minimum 4’ wide
(IBC). Alleys are not approved for access consideration.
6) One new requirement in the codes is for carbon monoxide detection in the
dwellings where
attached garages and fuel-fired appliances.
Let me know if you have something more specific to ask or explore.