MEMORANDUM
Date:January 29, 2015
To:Tristan Van Slyke, tvanslyke@bhillsarch.com
From:Fire Marshal John J. Westfall 425.771.0213
Subject:DRC2015-0002 Winco, 21900 Hwy 99, Edmonds WA
This review is conducted in accordance with 2012 IFC and Edmonds Community Development
Code.
1) Correct and align cardinal directions on plans
2) Additional permits anticipated:
a. Fire sprinkler
b. Fire alarm
c. Fire suppression/commercial cooking
d. ~Distributed Antenna System (DAS) for emergency communications (IFC 510)
3) Type I Hood and cooking oil storage IFC 609-610, tie to fire alarm system for building.
4) See IBC 414.2 for hazardous material display and storage requirements.
5) See IFC Section 50 for hazardous materials control area and management requirements.
Provide hazardous material inventory statement (HMIS) for ongoing inventories of
hazardous products, materials and flammable & combustible liquids.
6) See IFC 3204 for high-rack storage requirements where applicable. This may be
consideration for fire sprinkler design.
7) See IMC and IFC 604 for new or existing emergency generator. How will the generator be
fueled and what is the fuel capacity and location of fuel storage?
8) See IMC and IFC 606 for refrigeration system requirements.
9) Provide system specifications for safe operation of forklift charging operations.
10) Sheet SD2 Original plans, revise to current for site.
11) Sheet SD2 Pave exit to public way
12) Sheet FP1 Label spaces @ NW corner
13) Sheet FP1 Qualify folding grille for consideration of egress
14) Sheet FP1 Is this mechanical hood for charging forklift?
15) Sheet FP2 Unclear where platforms are located, show plan for platform/mezzanine
areas.
16) Sheet A4 Front Provide address 21900 visible from Highway 99.
17) Sheet A4 Rear What is propane enclosure used for?
18) Sheet P0.1 Backflow preventor location must be approved by COE WQ
19) Sheet E5.3 Confirm security system controls allow for egress.
20) Sheet F0.0 Plan for building does not show
21) Sheet F3 Relocate FACU to fire sprinkler riser area. Annunciator at main entry
good.
22) Sheet F3 Fire alarm monitoring using telephone should be upgraded to other
transmission means.
23) Add knoxbox and access to fire sprinkler riser area at rear man-door entry.
City of Edmonds Office of Fire Marshal