DRC20170026 220 Railroad Ave - New Community Center.docx CITY OF EDMONDS DEPARTMENT OF FIRE PREVENTION 6/29/2017 DRC NOTES for– DRC20170026, 220 Railroad Ave, Edmonds – New Senior Center After review of the documents provided, the following requirements may apply:  Fire Access – IFC 503, COE Standard.  Fire Flow requirements – IFC Appendix B. Based on Const Type and square footage.  Fire Hydrants (number and locations, based on fire flow).  Automatic Fire Sprinklers required.  Fire Department Connection required (FDC and Hydrant to be within 50’ of each other).  Fire Connection Permit required.  Automatic Fire Alarm required.  If Type 1 hood is installed (Cooking), deferred fire suppression permit required.  Fire Extinguishers - IFC 906  Premise Identification – IFC 505  Emergency Access Key Boxes – IFC 506  Emergency Responder Radio Coverage – IFC 510. Only required if evaluation of building requires installation.  Co-locate riser room and fire alarm panel in a room with exterior access, preferably on the east side of the building. Kevin Zweber Deputy Chief - Fire Marshal City of Edmonds, Department of Fire Prevention Snohomish County Fire District 1 425-771-0213 12425 Meridian Avenue S / Everett WA 98208 / 425-551-1200 www.firedistrict1.org