Loading...
EDM 14-02 Steven's Memorial Hospital_Electrical Room Sprinkler T I .docx Eagle Eye Consulting Engineers, PS West Coast Code Consultants Company PO Box 523 Olalla, WA 98359 hoytjeter@centurytel.net 206-356-7790 To: Leif Bjorback Building Official City of Edmonds Woodinville WA 98072 Re: Steven’s Memorial Hospital Thursday, June 17, 2014 Electrical Rooms – Fire Sprinkler T.I. th 21601 76 Avenue West Edmonds, WA 98026 Edmonds Permit # BLD2014-0520 EECE#: EDM 14-02 City of The above referenced project is in the process of plan review for compliance with Edmonds ordinances and applicable codes. The following comments, deficiencies/corrections must be addressed prior to completion of plan review and subsequent issuance of permits. Provide revised plans and calculations along with a written response to each of the items listed below to facilitate a shorter back-check time. A response to correction must be provided to the city within 90 days of the date of this letter or the permit application may be cancelled without notice. SCOPE OF REVIEW Fire Prevention requirements. The scope of this review is for the of this project The project was reviewed for compliance with the State of Washington Building Codes. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval. FIRE COMMENTS General 1.Please confirm that the new piping will not penetrate any existing fire-rated assemblies, and if it does specify how the requirements of Section 714 of the IBC will be met. EECE Project #: EDM 14-02 Edmonds Permit #: BLD2014-0520 Page 2 of 4 2.Please confirm that the solenoid valve is compatible with the FCP as required by Section 7.3.1.1 of NFPA 13. 3.No information regarding the proposed “release system” for this double-interlock preaction system has been provided (see Section 7.3.1.6 of NFPA 13). Please clarify. 4.Hydraulic calculations were not provided. Please provide supporting documentation for the system specified and ensure that the requirements of Sections 7.2.3.6 and 11.2.3.2.5 of NFPA 13 have been met. 5.Please note the supervision requirements of Section 7.3.2.4.1 of NFPA 13. Sheet FP-1: 6.The following items are not provided on the plans as prescribed by Section 23.1.3 of NFPA 13… a.A description of the scope of work. b.The occupancy hazard classification is not listed. c.Water supply test information (see Section 23.2.1 of NFPA 13). d.While sway bracing and hanger information have been provided, the required spacing has not been listed for either and sway bracing calculations have not been provided. In addition, the required embedment of the anchors supporting the hangers has not been provided. e.Kind and location of alarm bells. 7.Please address the following with regards to the “Manifold Detail” shown… a.Show that drains meet the discharge requirements of Section 8.16.2.4.4. b.The material data provides preaction valve information for 2-inch to 8-inch valve trim yet it appears that two of these preaction valves will be used on 1.5-inch supply pipes. Please clarify. c.No information regarding the pipe stands and anchorage has been provided (see Section 9.2.6 of NFPA 13). 8.Please clarify on the plans that the new 4-inch supply riser shall be supported in accordance with Section 9.2.5 of NFPA 13. EECE Project #: EDM 14-02 Edmonds Permit #: BLD2014-0520 Page 3 of 4 9.Please confirm that the preaction valve room is both lighted and heated in accordance with Section 7.3.1.8.2 of NFPA 13. 10.While inspector test locations are shown, please clarify that they shall meet the requirements of Section 8.17.4.4 of NFPA 13. Additional corrections may be required following receipt of corrections and additional information as requested. Your plans may also be reviewed concurrently by other departments within the City of Edmonds. Changes, clarifications or additional corrections may be required subsequent to the reviews performed by these other departments. Should you have any inquiries regarding this letter, please contact Hoyt Jeter at (206) 356- 7790 or by email at chrisk@wc-3.com. By: _______________________ Chris Kimball, P.E., S.E. ICC Fire Plans Examiner ICC Fire Inspector I/II